ECB violations
45 West 139 Street, Manhattan • Block 01737 • Lot 0015
63 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 8, 2025 | 39169597Z | ACTIVE | CLASS - 2 | FTM BOILER FOUND A FEDERAL FST-250 DUEL FUEL RATED AT 1050000 BTUS/BROKEN DRAFT REGULATOR/MISSING COVERS ON GAS TRAIN... | $1,250 | $1,250 | Feb 12, 2026 |
| Nov 17, 2025 | 39167223P | ACTIVE | CLASS - 1 | CLASS 1(CU):FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-98... | $1,250 | $1,250 | Jul 23, 2026 |
| Oct 31, 2025 | 39165516J | ACTIVE | CLASS - 2 | I FOUND A FEDRAL FST250WITH HOLES IN THE FLUE PIPE/MISSING BACKFLOW/BODY DRAIN MISSING ON SAFETY VALVES/CORRECT ALL V... | $1,250 | $1,250 | Jan 8, 2026 |
| Sep 16, 2025 | 39160510X | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT. OF BUILDINGS FOR VIOLA... | $1,250 | $0 | Nov 20, 2025 |
| May 21, 2025 | 39148540P | ACTIVE | CLASS - 2 | CLASS 2:NO SERVICE ON EMERGENCY PHONE LINE,CONNECT PHONE TO 24HRS EMERGENCY SERVICE.PIT LIGHT INOPERATIVE,REPAIR LIGH... | $625 | $0 | Jul 31, 2025 |
| Jan 16, 2024 | 37026653N | ACTIVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 9B REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $1,250 | $1,250 | Apr 25, 2024 |
| Jan 3, 2024 | 39524453N | ACTIVE | CLASS - 2 | AT TIME OF INSPECTION OBSERVED SIDEWALK SHED AT EXPO#1 OBSERVED AT 5:30 AM NO LIGHT UNDER THE SHED CREATING AN UNSAFE... | $2,400 | $2,400 | Mar 14, 2024 |
| May 16, 2023 | 39086360R | ACTIVE | CLASS - 2 | CLASS 2: CAR STATION POSITION INDICATOR DEFECTIVE CHECK WIRES & REPAIR. CAR STATION DIRECTIONAL ARROWS MISSING REPLAC... | $312 | $312 | Nov 13, 2023 |
| May 16, 2023 | 39086359J | ACTIVE | CLASS - 2 | CLASS 2: ACCESS DOOR MISSING. PROVIDE NEW DOOR TO SECURE SWITCHES & WIRES. CAR STATION DIRECTIONAL ARROW MISSING PROV... | $312 | $312 | Nov 13, 2023 |
| Apr 17, 2023 | 39083908J | ACTIVE | CLASS - 2 | AT TIME OF INSPECTION OBSERVED PROPERTY LINE FENCE GATE AUTO LOCKING SYSTEM IN STATE OF DISREPAIR CONDITION WITH BROK... | $312 | $312 | Nov 2, 2023 |
| Jul 18, 2022 | 39066087R | ACTIVE | CLASS - 1 | AT THE 11TH FLOOR, APARTMENT ABOVE MAIN ENTRANCE, WINDOWS BROKEN AND IN DANGER OF FALLING TO GRADE., REPAIR AND/REPLACE | $625 | $0 | Mar 30, 2023 |
| Dec 8, 2021 | 39052771X | RESOLVE | CLASS - 2 | PHONE NOT WORKING,DIRTY PIT. | $312 | $0 | Mar 24, 2022 |
| Sep 30, 2019 | 39010428N | RESOLVE | CLASS - 1 | CAR DOOR RESTRICTOR ALTERED REPAIR | $1,250 | $0 | Mar 12, 2020 |
| Sep 6, 2019 | 35453272N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN SAFETY MEASURES. AT THE TIME OF INSPECTION 16 STY ALT. I OBSERVED AT THE GROUND LEVEL C-HOOKS & P... | $5,000 | $0 | Jul 16, 2020 |
| Nov 20, 2018 | 35342912K | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT. AT TIME OF INSPECTION OBSERVED THAT WORK PERMIT #123468639-01-OT FOR RENOVATION OF APARTMENT 1... | $0 | $0 | Mar 8, 2019 |
| Nov 20, 2018 | 35342911Z | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT. AT TIME OF INSPECTION OBSERVED THAT WORK PERMIT #123451610-01-EW-OT FOR RENOVATION OF APT 1E E... | $0 | $0 | Mar 7, 2019 |
| Nov 16, 2018 | 38266272Z | RESOLVE | CLASS - 1 | 97X17 RESTORE TO SEVICE FOR PROPER INSPECTION BY DOB. | $1,250 | $0 | Jan 10, 2019 |
| Oct 15, 2018 | 37013520R | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPUR... | $1,250 | $0 | May 23, 2019 |
| Oct 26, 2017 | 38258958N | RESOLVE | CLASS - 1 | 97R#)WORK WITHOUT PERMIT. DEVICE #1P23646 BEING USED TO PROVIDE TRANSPORTATION FOR CONSTRUCTION PERSONNEL, TOOLS AND ... | $0 | $0 | Apr 26, 2018 |
| Oct 12, 2017 | 38258672H | RESOLVE | CLASS - 2 | 67X10,26D7,68B7,61T7,42B10,52M7,53M7,16H11. (67X)REPAIR PHONE. (26D)PROVIDE CHAIN. (68B)MAINTENANCE LOG. (61T)PROVIDE... | $0 | $0 | Nov 30, 2017 |
| Oct 10, 2017 | 38258666L | RESOLVE | CLASS - 2 | 67X10,61B7,100X10,40S9,56Y13. (67X)REPAIR PHONE. (61B)PROVIDE MACHINE MAIN DISCONNECT MAINT COMPANY. (100X)REPAIR FIR... | $0 | $0 | Nov 30, 2017 |
| Aug 4, 2014 | 36019679J | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXT... | $800 | $0 | Jan 8, 2015 |
| Mar 15, 2010 | 38209837X | RESOLVE | CLASS - 2 | 97X10. 97X- FOUND ELEVATOR SHUTDOWN AT THIS TIME RESTORE BACK TO SERVICE SO THAT A FULL INSPECTION CAN BE DONE BY THI... | $2,500 | $0 | May 6, 2010 |
| Feb 5, 2010 | 34835133K | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE THE REQUIRED FIRESTOPPING:FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.AT PUBLIC HALL,BASEMENT L... | $500 | -$500 | Apr 20, 2011 |
| Feb 5, 2010 | 34835132Z | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE AN APPROVED ACCEPTED PLANS @ JOBSITE AT TIME OF INSP!DEFECTS NOTED:CONST WORK UNDER APP#120149179-... | $500 | $0 | Apr 20, 2011 |
| Feb 5, 2010 | 34835130P | RESOLVE | CLASS - 1 | WORK W/O A PERMIT!ILLEGAL WORK NOTED:@ THE BUILDING FRONT YARD SETBACK,WEST ELEVATION,LEFTSIDE OF ENTRY FOUND W/2 AC-... | $800 | -$800 | Apr 14, 2011 |
| Mar 13, 2009 | 38201927N | RESOLVE | CLASS - 2 | 97X10.98BB5.99BB5.100#7.70O2.71L11.ALL CARS 97X10 DEVICE NOT IN SERVICE REPAIR AND RETURN TO SERVICE 98.99BB5 SHALL N... | $350 | $0 | Apr 30, 2009 |
| Jan 30, 2009 | 38200299R | RESOLVE | CLASS - 2 | 67X10.10H11.17H11.67X10 COMMUNICATION IN ELEVATOR DOESN'T WORK REPAIR 10H11 CAR DOOR GIBS ARE WORN NEED TO BE REPLACE... | $250 | $0 | Mar 27, 2009 |
| Jan 30, 2009 | 38200900Z | RESOLVE | CLASS - 2 | 97X10.97X10 ONLY ELEVATOR OUT OF SERVICE RETURN TO SERVICCE SO A FULL INSPECTION CAN BE BE PERFORMED | $500 | $0 | Mar 27, 2009 |
| Jan 30, 2009 | 38200901K | RESOLVE | CLASS - 2 | 02X10.67X10.26W06.10H11.07D10.02X10 ALARM BELL BUTTON NOT WORKING REPAIR 67X10 COMMUNICATION NOT WORKING REPAIR 26W06... | $250 | $0 | Mar 27, 2009 |
| Aug 19, 2008 | 38190401H | RESOLVE | CLASS - 2 | 70Z09, 17H11, 34O02. 70Z-WATER IN PIT. | $500 | $0 | Mar 27, 2009 |
| May 28, 2008 | 38184636L | RESOLVE | Non-Hazardous | 83X10 83X REPAIR ELEVATOR SO A FULL INSPECTION CAN BE MADE BY DOB | $0 | $0 | Jan 22, 2009 |
| May 28, 2008 | 38184635J | RESOLVE | Non-Hazardous | 5L10.2L10.66Z9. 5L CAR DOOR HANGER ROLLERS NEED REPAIR 2L ALARM SYSTEMDOESN'T WORK 66Z PIT IS FLOODED NEEDS TO BE REM... | $0 | $0 | Jan 22, 2009 |
| May 28, 2008 | 38184637N | RESOLVE | Non-Hazardous | 2L10.66Z9. 2L ALARM SYSTEM DOESN'T WORK 66Z PIT IS FLOODED NEEDS TO BE REMOVED | $180 | $0 | Jan 22, 2009 |
| Oct 23, 2007 | 34605696K | RESOLVE | Non-Hazardous | LICENSED RIGGER FAILED TO NAME A DESIGNATED FOREMAN.NO FOREMAN ON SITEAT TIME OF INSPECTION. | $0 | $0 | Aug 21, 2008 |
| May 2, 2007 | 38166633R | RESOLVE | Non-Hazardous | 83X10/.83-X-10-RETURN TO SERVICE,FOR PROPER INSP OF ELEVATOR. | $180 | -$180 | Jun 21, 2007 |
| May 2, 2007 | 38166634Z | RESOLVE | Non-Hazardous | 31J1/.31-J-1-ADJUST GUIDE ROLLERS.ELEVATOR SHAKES WHEN RUNNING. | $180 | -$180 | Jun 21, 2007 |
| May 2, 2007 | 38166635K | RESOLVE | Non-Hazardous | 83L10/.83-L-10-ELEVATOR 5/P ATER INSPECTION OF ELEVATOR.AT THE 9TH FL REPAIR & RETURN TO SERVICE. | $180 | -$180 | Jun 21, 2007 |
| Jun 30, 2005 | 34458883Z | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXTERIOR ... | $700 | $0 | Nov 17, 2005 |
| Jan 14, 2005 | 34460985M | RESOLVE | Non-Hazardous | 20050811Y PROVISIONS:PERIODIC INSPECTION OF EXTERIOR WALLS & APPURTENANCES AS REQUIRED BY LOCAL LAW 11 OF 1998 & THE ... | $1,750 | $0 | Jul 27, 2006 |
| Jun 25, 2004 | 34459539Y | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT: PERIODIC INSPECTION OF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED... | $1,750 | $0 | Aug 12, 2004 |
| Mar 31, 2004 | 34460201P | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT : PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED... | $2,500 | $0 | Jun 3, 2004 |
| Oct 22, 2001 | 38119274M | RESOLVE | Non-Hazardous | 73N11/ 57O2/ 8V1/ 973) ENTIRE DEVICE BY PASS FLOORS (52) PIT DIRTY (8) NOT LEVEL WITH LENDING | $0 | $0 | Dec 6, 2001 |
| Sep 18, 2001 | 38118874L | RESOLVE | Hazardous | 37X07, 37 CAR STOPPING FOR CALLS 5, 9, 10, 12, 14, 16, 17, ONLY DOESN'T STOP ON OTHER 11 FLOORS CEASE USE | $500 | $0 | Nov 29, 2001 |
| Nov 1, 2000 | 38109248J | RESOLVE | Non-Hazardous | 75U05 | $2,500 | $0 | Dec 21, 2000 |
| Jul 10, 2000 | 38106816P | RESOLVE | Non-Hazardous | 75U05,22Q06,37G12,36X11,08J01. 37G12- 15 AM P FUSES. 08J01- 5 FLOOR. | $0 | $0 | Aug 24, 2000 |
| Jul 10, 2000 | 38106817R | RESOLVE | Non-Hazardous | 75U05,22Q06,08J01. 08J01. FIRST FLOOR. | $0 | $0 | Aug 24, 2000 |
| Oct 19, 1999 | 38091058X | RESOLVE | Non-Hazardous | 57O2,50Y14,75B5,8O2,3A4,44H12. 3-PATCH HOLE IN CAB CEILING BY LIGHT. 44-REPLACE BEARING IN GEN SET. | $2,500 | $0 | Dec 9, 1999 |
| Oct 19, 1999 | 38091057Y | RESOLVE | Non-Hazardous | 50Y14,75B5,57O2,8O2,22D6. | $2,500 | $0 | Dec 9, 1999 |
| Oct 14, 1999 | 38091056M | RESOLVE | Hazardous | 74X,22D,10B,36L,36D,75B,50Y,54D,57O. CEASE USE SAFETY EDGE NOT WORKINGAT DOOR OPEN NOT WORKING, REPAIR DOOR OPEN BUTT... | $2,500 | $0 | Dec 2, 1999 |