ECB violations
148-150 East 124 Street, Manhattan • Block 01772 • Lot 0052
24 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 12, 2025 | 39156734N | RESOLVE | CLASS - 2 | FOUND FEDERAL FST-50 OIL FIRED BOILER WITH DEFECTIVE BAROMETRIC DAMPER, SAFETY RELIEF VALVE MANUFACTURE LABEL NOT LEG... | $1,280 | $0 | Oct 16, 2025 |
| Aug 30, 2024 | 39123576X | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF TOP THE RACEWAY SUPPLYING POWER TO THE EXHAUST FAN NOT CONNECTED OR TERMINATED PROPERLY. THE D... | $400 | $0 | Dec 19, 2024 |
| Aug 30, 2024 | 39123577H | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT BOILER ROOM THE THE WATER MAIN GROUND INSTALLED IMPROPERLY PAST THE POINT OF ENTRY TO THE ... | $2,400 | $0 | Jun 12, 2025 |
| Aug 30, 2024 | 39123579L | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF NO EQUIPMENT GROUND IN THE DISCONNECT FOR THE EXHAUST FAN., PROVIDE ADEQUATE GROUNDING; INSTAL... | $2,430 | $0 | Dec 19, 2024 |
| Aug 30, 2024 | 39123578J | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP EXHAUST FAN DISCONNECT, THE USE OF RUBBER COATED WIRING THROUGH THE LFMC, ALSO NOTED A FLEX... | $830 | $0 | Dec 19, 2024 |
| Aug 19, 2024 | 39122367P | RESOLVE | CLASS - 2 | OBSERVED IN THE BASEMENT/CELLAR GAS VALVE SHUT NOT LOCKED. THIS IS A HAZARDOUS CONDITION BECAUSE THE VALVE CAN BE OPE... | $625 | $0 | May 5, 2025 |
| Aug 19, 2024 | 39122373L | RESOLVE | CLASS - 1 | ILLEGAL HARDWARE INSTALLED ON FRONT ENTRANCE/EXIT DOOR., PROVIDE LEGAL HARDWARE | $1,250 | $0 | May 5, 2025 |
| Aug 19, 2024 | 39122374N | ACTIVE | CLASS - 2 | CLOSET BUILT WITH EXCESSIVE STORAGE OF OFFICE MATERIAL INSIDE ELECTRICAL MECHANICAL ROOM LOCATED AT CELLAR/BASEMENT L... | $1,250 | $0 | May 5, 2025 |
| Aug 19, 2024 | 39122372J | RESOLVE | CLASS - 1 | EMERGENCY EXIT WINDOW DO NOT OPEN LOCATED AT 4TH FLOOR, EXPOSURE #1. EMERGENCY EXIT DOOR DO NOT SELF-CLOSE LOCATED TH... | $1,250 | $0 | May 5, 2025 |
| Jan 27, 2020 | 39016362R | RESOLVE | CLASS - 2 | I OBSERVED FLEXIBLE EXTENSION CORDS USED AS A PERMANENT WIRING METHOD ON THE ROOF AND IN THE BASEMENT. CORDS ARE INST... | $800 | $0 | Dec 3, 2020 |
| Jan 29, 2019 | 35383800R | RESOLVE | CLASS - 3 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR`BUILDING DEPT RECORDS. NOTED: AS PER C OF O #10... | $0 | $0 | Jun 20, 2019 |
| Jan 29, 2019 | 35372674L | RESOLVE | CLASS - 2 | 358.12/UNSAFE ELECTRICAL EQUIPMENT IN USE.I OBSERVED EXIT LIGHTS EING SUPPORTED BY EMT PIPE CONNECTORS VIOLATING ARTI... | $0 | $0 | Mar 28, 2019 |
| Jan 29, 2019 | 35372673J | RESOLVE | CLASS - 2 | 110.25/ELECTRIAL ROOM BEING USED FOR OFFICE STORAGE AND PANTRY AREA.I OBSERVED THE MAIN ELECTRICAL ROOM BEING USED FO... | $0 | $0 | Mar 28, 2019 |
| Jan 29, 2019 | 35372664H | RESOLVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT.I OBSERVED NEW LED LIGHTS IN THE ENTRANCE AND IN THE CONFERENCE ROOMS INSTALLED PRIO... | $400 | $0 | Mar 28, 2019 |
| Sep 17, 2018 | 35341834J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NO FIRE STOP USED AT CELLAR ... | $0 | $0 | Dec 20, 2018 |
| Apr 23, 2018 | 32096414H | RESOLVE | CLASS - 2 | 28B FOUND FEDERAL BOILER MODEL FS750 5,375,000 BTUS WITH DEFECTS. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTI... | $310 | $0 | Jun 7, 2018 |
| Aug 21, 2017 | 35287324P | RESOLVE | CLASS - 3 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.NOTED: C OF O#103196140 INDICATES 2ND FL TO BE ... | $250 | $0 | Feb 1, 2018 |
| Aug 21, 2017 | 35287323N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. USE OF PROHIBITED DOOR &/OR HARDWARE PER BC 1008.1.8;27-371(J). NO... | $0 | $0 | Oct 5, 2017 |
| Aug 21, 2017 | 35289695N | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED IN BOILER ROOM LOCATED IN BASEMENT: MAIN ELECTRICAL GROUNDING CONDUCTO... | $4,800 | $0 | Feb 6, 2018 |
| Aug 21, 2017 | 35289697R | RESOLVE | CLASS - 2 | SEC. 110.25 ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL EQUIPMENT ONLY. OBSERVED IN MAIN ELECTRICAL ROOM LOCATED IN... | $250 | $0 | Oct 5, 2017 |
| Aug 21, 2017 | 35287322L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. NOTED: OBSERVED IN BASEMENTS... | $250 | $0 | Feb 6, 2018 |
| Aug 21, 2017 | 35289638R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 8/21/17@ ABOVE ADDRESS IN BOILER ROOM PIPR APPEARS TO ... | $0 | $0 | Oct 5, 2017 |
| Apr 7, 2016 | 35177628R | RESOLVE | CLASS - 3 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS CERTIFICATE OF OCCUPANCY ... | $400 | $0 | Aug 25, 2016 |
| Jun 28, 1990 | 32006300H | RESOLVE | Non-Hazardous | WTR LEAKING FROM BURNER AREA; REMOVE ALL RAGS & COMBUSTBLES FROM BLR ROOM. 10A, 27B, 32, 42C, 46A. | $85 | $0 | Aug 9, 1990 |