ECB violations
473 Central Park West, Manhattan • Block 01843 • Lot 0032
13 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Nov 30, 2021 | 39051919Z | RESOLVE | CLASS - 2 | FOUND LEVERS MISSING ON BOTH SAFETY RELIEF VALVES, ONE VALVE MANUFACTURE LABEL NOT LEGIBLE, REPLACE SAFETY RELIEF VAL... | $625 | $0 | May 26, 2022 |
| Oct 27, 2017 | 32092063R | RESOLVE | CLASS - 2 | 15,50. (15)OPENING IN WALLS/CEILING. (50)SPILL SWITCH MISSING CORRECT ALL VIOLATING CONDITION & SUBMIT C OF C. | $0 | $0 | Dec 14, 2017 |
| Aug 16, 2016 | 32077363N | RESOLVE | CLASS - 1 | B154,51,21A,50,50A,36. 50-BOILER PIT AND SUMP SOAKED WITH OIL; 50A- SAIL SWITCH NOT INTERLOCKED; DO NOT OPERATE BOILE... | $1,000 | $0 | Oct 6, 2016 |
| Jun 24, 2016 | 35167062H | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS &/OR APPROVEDAMENDMENTS. AT TIME OF INSPECTION APT #1C,IN RE... | $0 | $0 | Aug 18, 2016 |
| Jun 24, 2016 | 35167063J | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO CONSTRUCTION DOCUMENTS &/OR APPROVED AMENDMENTS AT TIME OF INSPECTION OBSERVED 3B,3C & 5C. D... | $0 | $0 | Aug 18, 2016 |
| Aug 22, 2012 | 32072114J | RESOLVE | CLASS - 2 | B254,15,16,28B,34B,50,50A,B,C,D,E. 50- OIL PUMP LEAKING. 50A- GAS REGULATOR NOT VENTED 50B- BACK FLOW DISCHARGE ON FL... | $2,500 | $0 | Feb 7, 2013 |
| Jul 28, 2012 | 32072322Y | RESOLVE | CLASS - 1 | B154,1. | $1,000 | $0 | Sep 13, 2012 |
| Jul 6, 2012 | 32072274Z | RESOLVE | CLASS - 2 | B254,50A-F.(50A)MAN HOLE ASSEMBLE LEAKING.(50B)REMOVE WASTE OUT FROM BOILER ROOM.(50X)BOILER ROOM NOT A STORAGE ROOM.... | $250 | $0 | Sep 13, 2012 |
| Jul 3, 2012 | 32072272P | RESOLVE | CLASS - 1 | B154,3B,28B,50A,50B,51: 50A;BOILER BURNER SMOKE. 50B;DO NOT OPERATE BOILER UNTIL ALL HAZARDOUS CONDITION ARE IMMEDIAT... | $0 | $0 | Sep 27, 2012 |
| Jul 3, 2012 | 32072271N | RESOLVE | CLASS - 1 | B154: | $1,000 | $0 | Sep 27, 2012 |
| Jun 30, 2012 | 32072269Y | RESOLVE | CLASS - 1 | B154,3B,28B,50A,51,50B; 50A;BOILER BURNER EXCESSIVE SMOKE. 50B;SMOKE ALARM JUMP OUT. | $1,000 | $0 | Sep 27, 2012 |
| Feb 25, 2012 | 32071724M | RESOLVE | CLASS - 1 | 154,1. | $5,000 | $0 | May 10, 2012 |
| Feb 21, 2012 | 32071721R | RESOLVE | CLASS - 1 | B154,3A,B,7A,B,51,41B,C,34B,50A,B,C,D. 50A- SECOND LOW WATER CUT OFF INOPERATIVE. 50B- FRESH AIR INTAKE NOT (WIRED) I... | $1,000 | $0 | May 10, 2012 |