Skip to content

ECB violations

102 West 128 Street, Manhattan • Block 01912 • Lot 0037

74 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Nov 18, 2025 39167356Z ACTIVE CLASS - 2 OBSERVED OBSTRUCTION OF SPRINKLER HEADS THROUGHOUT THE BUILDING. IN BASEMENT HOT WATER HEATER USING STEAM FITTING ON ... $1,250 $1,250 Jul 14, 2026
Nov 18, 2025 39167382M ACTIVE CLASS - 1 CEASE USE WEIL MCLAIN GAS FIRED BOILER DUE TO HAZARDOUS CONDITION OF DEFECTIVE SAFETY RELIEF VALVE, DO NOT OPERATE BO... $2,500 $2,500 Jul 14, 2026
Jul 21, 2025 39154362M ACTIVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS FOR SU... $6,250 $5,000 Mar 31, 2026
Jul 21, 2025 39154361K ACTIVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS FOR SU... $6,250 $5,000 Mar 31, 2026
Jul 21, 2025 39154367L ACTIVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS FOR SU... $6,250 $5,000 Mar 31, 2026
Jan 24, 2025 39136418N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 COD... $3,125 $0 Mar 6, 2026
Jan 24, 2025 39136417L ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED OBSTRUCTED FIRE ESCAPE AT EXPOSURE 1. CLOTHES AT BASE... $3,125 $0 Mar 6, 2026
Jan 24, 2025 39136406X ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $12,500 $0 Mar 6, 2026
Jan 24, 2025 39136405Y RESOLVE CLASS - 1 UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED UNSAFE STORAGE UNDERNEATH STAIRCASE AT MAIN LOBBY. (BA... $6,250 $0 Mar 6, 2026
Aug 1, 2023 39091558Z RESOLVE CLASS - 2 GAS PIPING LOCATED IN THE BASEMENT RUSTED AND CORRODED. AS PER 102.3 OF THE PLUMBING CODE MAINTENANCE. INSTALLATIONS,... $625 $0 Aug 16, 2024
Aug 1, 2023 39091554L RESOLVE CLASS - 2 GAS PIPING LOCATED IN THE BASEMENT SEVERELY RUSTED ALSO CORRODED. GAS TO THE BUILDING IS LOCKED AT THE METER BANK, BU... $625 $0 Aug 16, 2024
Jul 28, 2023 39091317H RESOLVE CLASS - 1 LARGE CMU BLOCK STRUCTURE WITH ELECTRICAL WIRING BUILT WITHOUT PERMITS LOCATED AT BACKYARD EXPOSURE #3., OBTAIN PERMI... $0 $0 Nov 2, 2023
Jul 26, 2023 39091051J RESOLVE CLASS - 2 FOUND WEIL MCLAIN GAS FIRED BOILER MODEL-EGH -125 550000 BTU'S ACTIVE WITH DEFECTS. MISSING CLEANOUT AT CHIMNEY BASE.... $312 $0 Mar 12, 2024
Jun 8, 2023 39088132Y RESOLVE CLASS - 1 I OBSERVED IN THE BASEMENT THE WATER METER WITHOUT A WATER METER JUMPER AS REQUIRED., PROPERLY INSTALL GROUND ELECTRO... $4,800 $0 Aug 17, 2023
Jun 8, 2023 39088117X RESOLVE CLASS - 2 I OBSERVED ON THE SECOND FLOOR THE FAILURE TO MAINTAIN ILLUMINATION ALONG THE PATH AND AT THE POINT OF EGRESS, DUE TO... $500 $0 Aug 17, 2023
Jun 8, 2023 39088131M ACTIVE CLASS - 2 I OBSERVED IN THE BASEMENT AREA THE INSTALLATION OF A NEW PANEL AND METER PAN, NO PERMITS ON FILE IN DOB RECORDS. ALS... $800 $0 Apr 18, 2024
Jun 8, 2023 39088114K RESOLVE CLASS - 2 I OBSERVED IN THE BASEMENT THE WATER GROUND IN A STATE OF DISREPAIR THE CONDUIT IS CORRODED AND THE WIRE IS NOT PROPE... $1,200 $0 Aug 17, 2023
Jun 8, 2023 39088130K RESOLVE CLASS - 2 I OBSERVED IN THE BASEMENT AREA THE LIGHT NEAR THE ELECTRICAL PANEL WITH THE RACEWAY BROKEN AND THE ENERGIZED CONDUCT... $0 $0 Aug 17, 2023
Jun 8, 2023 39088116Y RESOLVE CLASS - 2 I OBSERVED IN THE REAR COURTYARD THE EQUIPMENT SWITCH FOR THE WALL MOUNTED CONDENSER UNIT MADE INACCESSIBLE BY THE UN... $0 $0 Aug 17, 2023
Jun 8, 2023 39088115M RESOLVE CLASS - 2 I OBSERVED IN THE BASEMENT STORAGE ROOM THE INSTALLATION OF CEILING LIGHTS WITH EXPOSED AND ENERGIZED CONDUCTORS., PE... $0 $0 Aug 17, 2023
Jun 7, 2023 39087956M RESOLVE CLASS - 2 WEILMCLAIN EGH125 GAS FIRED BOILER HERE;EVIDENCE OF CORROSION AT REAR BASE OF BOILER. EXCESSIVE HEAT IN BOILER ROOM. ... $0 $0 Jan 4, 2024
May 3, 2022 35636526X RESOLVE CLASS - 2 UNSAFE UNSUITABLE ELECTRICAL WIRING IN USE.OBSERVED IN BASEMENT EXPOSED ENERGIZED CONDUCTORS FEEDING & CURRENTLY POWE... $2,000 $0 Dec 1, 2022
Apr 11, 2022 39059980Y RESOLVE CLASS - 2 NOTED: OBSERVED AT CELLAR LEVEL, ENTIRE CEILING HAS EXPOSED COMBUSTIBLE WOODEN LATH, BEAMS AND SUB-FLOORING, WITH NO ... $312 $0 Sep 15, 2022
Apr 11, 2022 39059983J RESOLVE CLASS - 2 I OBSERVED EXCESSIVE AMOUNTS OF STORAGE IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. AS PER APPENDIX E NO ST... $312 $0 Sep 22, 2022
Apr 11, 2022 39059989K RESOLVE CLASS - 2 NOTED: OBSERVED AT CELLAR LEVEL, ENTIRE CEILING HAS EXPOSED COMBUSTIBLE WOODEN LATH, BEAMS AND SUB-FLOORING, WITH NO ... $625 $0 Sep 22, 2022
Mar 24, 2020 39020293Y RESOLVE CLASS - 1 FAILURE TO CORRECT AND CERTIFY SUMMONS #39016214P., COMPLY WITH COMMISSIONER'S ORDER; COMPLY WITH EC CODE/ OBTAIN PERMIT $2,500 $0 Aug 6, 2020
Jan 23, 2020 39016212L RESOLVE CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM IN THE BASEMENT THE SERVICE ENTRANCE CONDUCTORS INSTALLED IN A HOLLOW CEILING ... $1,600 $0 Jul 30, 2020
Jan 23, 2020 39016214P RESOLVE CLASS - 1 I OBSERVED IN THE KITCHEN FLEXIBLE EXTENSION CORDS POWERING APPLIANCES VIOLATING SECTION 400.8 IN THE NEC; 400.8, COM... $1,600 $0 Jul 30, 2020
Jan 23, 2020 39016213N RESOLVE CLASS - 1 OBSERVED NEW EMT CONDUIT, AND BX CABLE INSTALLED TO POWER LIGHT FIXTURES, RECEPTACLES, AND APPLIANCES WITHOUT AN ELEC... $800 $0 Jul 30, 2020
Jul 16, 2019 35442256J RESOLVE CLASS - 2 UNSAFE, UNSUITABLE ELECTRICAL WIRING IN USE. I OBSERVED @THE CELLAR EXIT LIGHT A LACK OF MECHANICAL & ELECTRICAL CONT... $400 $0 Dec 12, 2019
Jul 16, 2019 35442255H RESOLVE CLASS - 2 UNSAFE, UNSUITABLE ELECTRICAL WIRING EQUIPMENT/EQIPMENT IN USE I OBSEVRED IN THE CELLAR EXPOSED ENERGIZED CONDUCTORS ... $400 $0 Dec 12, 2019
Jul 16, 2019 35442257L RESOLVE CLASS - 2 UNSAFE, UNSUITABLE ELECTRICAL WIRING/EQUIPMENT IN USE I OBSERVED @THE FIRST FLOOR REAR OF BUILDING FLEXIBLE CORDS GOI... $400 $0 Dec 12, 2019
Mar 5, 2019 32098902X RESOLVE CLASS - 2 B254,11A,32A,48B,50A. 11C-BLOWDOWN VALVE ON LOW WATER CUT OFF LEAKING32A-EXPOSED WIRING AT QUASTAT MISSING COVER; 48B... $1,562 $0 May 2, 2019
Sep 5, 2018 35347391R RESOLVE CLASS - 2 EXPOSED ARMORED CABLES ARE SUBJECT TO PHYSICAL DAMAGE.OBSERVED IN THE CELLAR A SET OF BX ARMORED CABLE AND NON METALL... $400 $0 Dec 20, 2018
Sep 5, 2018 35347390P RESOLVE CLASS - 1 FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION OBSERVED THE FOLLOWING VIOALTING CONDITIO... $4,800 $0 Dec 20, 2018
May 25, 2018 35313419Y RESOLVE CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. IN 4/15/18 A ELECTRICAL VIOLATION WAS ISSUE TO THE R... $0 $0 Jul 12, 2018
Mar 15, 2018 35321718Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED THE FOLLOWING DETERIORATING CONDITION ON MAIN ELECTRICAL ... $312 $0 Oct 18, 2018
Mar 15, 2018 35321717M RESOLVE CLASS - 1 FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE W/ SECTION. OBSERVED THE FOLLOWING VIOLATING CONDITION... $2,400 $0 Oct 18, 2018
Sep 29, 2017 35279613L RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUM/VIO#35289635L ISSUED ON 08/17/17 & TO FILE A C OF C PURSUANT TO... $0 $0 Mar 15, 2018
Aug 17, 2017 35289635L RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 8/17/17AT ABOVE ADDRESS GAS PIPING IN BASEMENT IS JUST... $1,000 $0 May 24, 2018
Aug 17, 2017 35287583J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: LACK OF EMERGENCY LIGHTS FOR EXITS. EXIT 4 DISCHARGES & PUBLIC COR... $500 $0 May 24, 2018
Aug 17, 2017 35289634J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 8/17/17AT ABOVE ADDRESS SPRINKLER HEAD IN LAUNDRY ROOM... $250 $0 May 24, 2018
Aug 17, 2017 35284851N RESOLVE CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. IN 6/21/2017 A ELECTRICAL VIOLATION WAS ISSUE TO TH... $800 $0 May 24, 2018
Aug 17, 2017 35287584L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER; NO FIRE STOPPING PER BC 7I2.3 27-345 IN THE GAS METER ROOM HOLES I... $250 $0 May 24, 2018
Aug 17, 2017 35289633H ACTIVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 8/17/17 AT ABOVE ADDRESS EXCESSIVE STORAGE IN GAS METE... $500 $0 May 24, 2018
Jun 21, 2017 35271261K RESOLVE CLASS - 1 FAILURE TO GROUND ELECTRICAL SYSTEM.OBSERVED IN BASEMENT AT WATER MAINMAIN GROUNDING CONDUCTER FOR BUILDING ELECTRICA... $2,400 $0 Feb 22, 2018
Mar 15, 2017 35234987R RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIO # 35230154Y ISSUED ON 01/12/17 & TO FILE A C... $0 $0 Jun 15, 2017
Jan 12, 2017 35230154Y RESOLVE CLASS - 2 FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION# 35208037Y ISSUED ON 9/16/16 & TO FILE A... $0 $0 Jun 8, 2017
Jan 12, 2017 35230153M RESOLVE CLASS - 2 FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION# 35208035K ISSUED ON 9/16/16 & TO FILE A... $0 $0 Mar 2, 2017
Sep 16, 2016 35207165Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345. @ CELLAR PIECES OF CEILING ... $250 $0 Nov 3, 2016