ECB violations
2250 Adam Clayton Powell Jr Boulevard, Manhattan • Block 01938 • Lot 0032
32 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Nov 17, 2025 | 39167245X | RESOLVE | CLASS - 2 | CLASS 2: MISSING CURRENT RECORDS IN THE MAINTENANCE LOG BOOK, CONDUCT ROUTINE SERVICE AND UPDATE THE RECORDS. UNDER C... | $0 | $0 | Jan 22, 2026 |
| Nov 17, 2025 | 39167298J | RESOLVE | CLASS - 2 | OBSERVED LACK OF 7TH FLOOR SPRINKLER COVERAGE. IN BASEMENT GAS LINES IN THE FIRE PUMP ROOM WITH FIRE DEPARTMENT LINE ... | $0 | $0 | Aug 6, 2026 |
| Jan 21, 2025 | 39135989M | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING EXIT DOOR LEADING FROM BASEMENT TO EXPOSURE 1. POTENTIAL FIRE H... | $0 | $0 | Sep 25, 2025 |
| Jan 21, 2025 | 39135990J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $2,500 | Nov 17, 2026 |
| Sep 22, 2022 | 39070593L | RESOLVE | CLASS - 2 | AT ROOF LEVEL, VENTILATION EXHAUSTS WITH SUPPORTS/ANCHORS DETACHED, REPAIR AND/OR REPLACE | $312 | $0 | Dec 15, 2022 |
| Sep 22, 2022 | 39070594N | RESOLVE | CLASS - 2 | I OBSERVED IN THE DIRECTOR OF SOCIAL SERVICES OFFICE IN THE REAR 1ST FLOOR AREA FLEXIBLE CORDS INSTALLED IN PLASTIC M... | $800 | $0 | Jul 13, 2023 |
| Sep 22, 2022 | 39070595P | RESOLVE | CLASS - 1 | I OBSERVED IN THE MAIN ELECTRICAL ROOM THE GROUND ELECTRODE CONDUCTOR NOT CONNECTED TO ALL SERVICE SWITCHES AS REQUIR... | $4,800 | $0 | Jul 13, 2023 |
| May 25, 2022 | 35644371K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED AT CELLAR LEVEL UNSUPPORTED GAS PIPING TO COMMERCIAL D... | $1,562 | $1,562 | Aug 25, 2022 |
| Apr 7, 2021 | 35415439Z | RESOLVE | CLASS - 2 | FAILURE TO FILE CERTIFICATE OF CORRECTION FOR NOV#35461560H ISSUED ON 3/02/2020. | $1,250 | $0 | Oct 7, 2021 |
| Mar 2, 2020 | 35461560H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE: AT TIME OF INSPECTION WATER PRESSURE TO SPRINKLERS AT 5TH,6T... | $3,125 | $0 | May 7, 2020 |
| Jan 6, 2020 | 35434246X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER OBSERVED ON 01-06-2020 AT ABOVE ADDRESS INSUFFIECIENT WATER PRE... | $3,125 | $0 | Aug 6, 2020 |
| Sep 24, 2019 | 39009994J | RESOLVE | CLASS - 2 | OBSERVED IN CELLAR WATER EXCESSIVELY LEAKING FROM PUMP., REPAIR AND/OR REPLACE | $312 | $0 | Jul 9, 2020 |
| Sep 24, 2019 | 39009993H | RESOLVE | CLASS - 1 | OBSERVED ON THE UPPER FLOORS INSUFFICIENT WATER PRESSURE TO SPRINKLER HEADS., REPAIR AND/REPLACE | $3,125 | $0 | Jul 9, 2020 |
| Feb 15, 2019 | 38268264H | RESOLVE | CLASS - 1 | 5A10,53L10,78B14. 5A10-DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITHTHIS IS A SAFETY FEATURE TO ENSURE PASSENGER SAF... | $1,250 | $0 | Apr 11, 2019 |
| Oct 4, 2018 | 35361835J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUIDLING IN COMPLIANT MANNER.OBSERVED ON 10/04/2018 AT ABOVE ADDRESS INSUFFICENT WATER PRESSURE T... | $1,562 | -$1,562 | Dec 13, 2018 |
| May 31, 2018 | 35331948Z | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED IN GAS METER ROOM IN CELLAR NO VENTILATION INSTALLED A... | $500 | $0 | Jul 19, 2018 |
| Feb 18, 2018 | 35283270K | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #352347964 ISSUED 03/07/17 AND TO FILE... | $6,000 | $0 | Jun 14, 2018 |
| Jan 2, 2018 | 35283130Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35234796Y ISSUED ON 03/07/17 AND TO FI... | $2,000 | $0 | Feb 22, 2018 |
| Nov 18, 2017 | 35280722Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAIND IN SUMMONS/VIOLATION#35234796Y ISSUED ON 03/07/17 AND TO FILE... | $2,000 | $0 | May 3, 2018 |
| Aug 8, 2017 | 35276639X | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35234796Y ISSUED ON 03/07/17 & TO FILE A C OF C PURSUAN... | $6,000 | $0 | Sep 28, 2017 |
| May 26, 2017 | 35267398J | RESOLVE | CLASS - 1 | FAILURE TO COMPLY COMMISSIONER'S ORDER CONTINUED IN SUMMONS 35234796Y ISSUED ON 3/7/17 AND TO FILE A CERTIFICATE OF C... | $2,400 | $0 | Jul 20, 2017 |
| May 1, 2017 | 35250971M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED AN APPLIANCE VALVE ON MAIN LINE OF GAS LINE ON HOUSE SIDE... | $1,000 | $0 | Aug 31, 2017 |
| Mar 15, 2017 | 35229223K | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE POWER FOR EMERGENCY EXIT LIGHTING. NOTED: AT 7TH STY CORRIDOR,EXIT LIGHT IN OPERABLE,NOT LIGHTING ... | $250 | $0 | Jun 29, 2017 |
| Mar 7, 2017 | 35234797X | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 3-7-17 BROKEN SPRINKLER CAP IN LAUNDRY ROOM AREA. REME... | $250 | -$250 | Apr 27, 2017 |
| Mar 7, 2017 | 35234796Y | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. OBSERVED ON 3-7-17 GAS PIPE INSTALLED TO STAKABLE LAUNDRY DRYERS IN BASEMENT. NO PERMITS WERE ON F... | $4,000 | $0 | Apr 27, 2017 |
| Jan 9, 2017 | 35230032X | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35214030M ISSUED ON 09/29/16 & TO FILE A C OF C PURSUAN... | $2,400 | $0 | Apr 6, 2017 |
| Nov 25, 2016 | 35221169M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/COMM'S ORDER CONTAINED IN NOV#35214030M ISSUED ON 9-29-16 & TO FILE A C OF C PURSUANT TO 28-201.1... | $2,400 | $0 | Mar 16, 2017 |
| Sep 29, 2016 | 35214031Y | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. AT THE TIME OF MY INSPECTION 12:30PM ON 9-29-16 AT THE ABOVE P... | $1,000 | $0 | Nov 2, 2017 |
| Sep 29, 2016 | 35214030M | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. AT THE TIME OF MY INSPECITON,12:30PM ON 9-29-16 AT THE ABOVE PLACE OF OCCUARANCE ADDRESS I OBSERVE... | $8,000 | $0 | Nov 17, 2016 |
| Jun 15, 2015 | 38236607Y | RESOLVE | CLASS - 2 | 11B09,08V01,17D06,41J01,02X10,53E10,71X10. 11B-ON CAR STATION-RUN/STOPSWITCH WITH KEY-REMOVE; 08V-BASEMENT OFF LEVEL;... | $250 | $0 | Jul 30, 2015 |
| Sep 14, 2009 | 34808453X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMMISSIONERS ORDER TO FILE A CERT OF CORRECTION W/THE DEPT OF BLDG.NOTED THE FOLLOWING CONDI... | $4,000 | $0 | Aug 12, 2010 |
| Jun 6, 2008 | 34642441L | RESOLVE | Non-Hazardous | FAILURE TO PROTECT ROOF ROOF OUTLETS OR SKYLIGHTS OF ADJOINING PROPERTY DURING CONSTRUCTION OPERATIONS: NOTED :AT ABO... | $500 | $0 | Jul 31, 2008 |