137-145 West 141 Street, Manhattan • Block 02010 • Lot 0006
84 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 14, 2024 | 39114254Z | ACTIVE | CLASS - 2 | ATOI AT APT #27 AT 2ND FLOOR OF PREMISES, A 6 STORY 49 A UNIT MULTIPLE DWELLING, ILLEGAL KEY OPERATED LOCK HARDWARE O... | $3,125 | $3,125 | Jul 18, 2024 |
| Sep 19, 2023 | 39095193N | RESOLVE | CLASS - 2 | CLASS 2: PHONE INOPERATIVE REPAIR & CONNECT SERVICE TO 24 HR EMERGENCY OPERATOR. CAPACITY PLATE MISSING FROM CAR BUTT... | $0 | $0 | Nov 30, 2023 |
| Feb 15, 2023 | 35657450L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE AT TIME OF INSPECTION OBSERVED METAL LANDING AND METAL TRE... | $625 | $625 | Nov 2, 2023 |
| Feb 15, 2023 | 35657424H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE AT TIME OF INSPECTION OBSERVED IN APT#54 INSIDE THE BATHRO... | $0 | $0 | Sep 21, 2023 |
| Sep 27, 2022 | 39070928Y | ACTIVE | CLASS - 2 | 2/X/10 OUT SIDE COMM INOPERATIVE REPAIR. | $3,125 | $3,125 | Nov 17, 2022 |
| Feb 9, 2022 | 39055769K | RESOLVE | CLASS - 2 | CORROSION AND LEAK ON PIPING TO DOMESTIC HOT WATER COIL. | $312 | $312 | Oct 28, 2022 |
| Feb 24, 2021 | 39036705H | RESOLVE | CLASS - 2 | MAIN POWER THIRD PHASE IN THE ELECTRICAL METER BOX DEFECTIVE ON PROVIDED LOW POWER TO ELEVATOR CONTROLLER, CON-ED POW... | $0 | $0 | May 27, 2021 |
| Dec 30, 2020 | 39034058L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED GARBAGE BAGS, HOUSEHOLD I... | $0 | $0 | Feb 18, 2021 |
| Jan 23, 2020 | 39016172X | RESOLVE | CLASS - 1 | 42/5/7 CAR DOOR MONITORING MISSING PERFORM AND FILE FOR TESTING BY NYC DOB. 8/V/A CAR FLOOR TO LANDING SILL NOT LEVEL... | $1,250 | $0 | Oct 22, 2020 |
| Sep 17, 2019 | 38271582K | RESOLVE | CLASS - 1 | CEASE USE 08.V.01,05.J.01,52.H.12,05.A.10,34.D.06,34.06,71.I.10,56.Y.02=CEASE USE CONTINUE RECURRING CONDITION AGGRAV... | $0 | $0 | Mar 12, 2020 |
| Sep 13, 2019 | 38271575M | RESOLVE | CLASS - 1 | CEASE USE 52.B.10,05.J.01,05.M.07,08.V.01,10.B.10,56.Y.02,34.D.06,53.M.07,52.M.07,52.D.06=CEASE USE CONTINUE RECURRIN... | $0 | $0 | Feb 13, 2020 |
| Aug 29, 2019 | 38271108N | RESOLVE | CLASS - 1 | CEASE USE 5.J.1,(C.U)52.H.12,(C.U)55.H.12,(C.U)70.O.2,59.BB.7,99.BB.7=5.T.1 CAR DOOR HAVE TOO MUCH GAP ON STRIV EPOST... | $1,250 | $0 | Oct 31, 2019 |
| May 15, 2019 | 38269734H | RESOLVE | CLASS - 1 | CEASE USE 97.X.17:OUT OF SERVICE UPON INSPECTION THE DEVICE IS FOUND TO EBOUT OF SERVICE REMEDY RESTORE TO SERVICE IM... | $1,250 | $0 | Jul 18, 2019 |
| Mar 26, 2019 | 38268823P | RESOLVE | CLASS - 2 | 08V01,37B10,41B10,34D06,71X10,53U07,52B10,52U07; (08) ELEVATOR NOT LEVEL (37)REPAIR DOOR TO SELF CLOSE/LOCK (41)REPAI... | $0 | $0 | May 23, 2019 |
| Mar 14, 2019 | 38268852Y | RESOLVE | CLASS - 1 | CU5A10,CU5B1. 5A10-DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED. THIS IS A SAFETY DEVICE TO ENSURE PASSENG... | $1,250 | $0 | May 9, 2019 |
| Dec 6, 2018 | 38266976R | RESOLVE | CLASS - 1 | CU05B10; 40P16; 67X10. 65B10-CAR DOOR IS OFF TRACK AND HANGING IN SHAFTWAY REPAIR. 40P16-NO ACCESS TO MOTOR ROOM, PRO... | $1,250 | $0 | Jan 31, 2019 |
| Sep 27, 2018 | 38265486J | RESOLVE | CLASS - 1 | CU52B12,CU55B12; 39O02,37B10,41B10,72B07,70O02,56Y13,34D06,53U07,53U07,26D06,59B0,25M07. CEASE USE ITEMS (52B12)(55B1... | $1,250 | $0 | Nov 15, 2018 |
| Sep 26, 2018 | 38265215H | RESOLVE | CLASS - 1 | 8V10 CAR FLOOR NOT LEVEL WITH FLOOR STOPS REPAIR. | $1,250 | $0 | Nov 15, 2018 |
| Aug 30, 2018 | 38265132M | RESOLVE | CLASS - 2 | 8J01,10H11,40O02,39O02-8J1)ADJUST CAR LEVELING. 10H11)REPLACE CAR DOOR GIBS(WORN). 40O02)CLEAN AND REMOVE NON-ELEVATO... | $312 | $0 | Oct 18, 2018 |
| Jan 17, 2018 | 38260784P | RESOLVE | CLASS - 2 | 16J01, 11B07,37B07,40B07,54M07,55B07,52B07,70B07. 16J-ADJUST LOBBY DOOR TO CLOSE FULLY; 11B-COMPLY WITH SECTION 8.1 (... | $0 | $0 | Mar 8, 2018 |
| Dec 26, 2017 | 38260325X | RESOLVE | CLASS - 1 | CEASE USE. 5A10,8V1. (5A)DOOR ZONE RESTRICTOR HAS BEEN TAMPERED DISABLED & RENDERED INOPERATIVE. THIS IS A SAFETY DEV... | $1,000 | $0 | Feb 15, 2018 |
| Sep 28, 2017 | 38258172L | RESOLVE | CLASS - 2 | 12M07,08V01,10H10,37B07,54M07,55B07,71I11,99BB05,60B07,52B07-12M)PROVIDE (COVER) FOR LIGHT FIXTURE. 08V)BASEMENT LEVE... | $500 | $0 | Nov 16, 2017 |
| Aug 8, 2017 | 38257275J | RESOLVE | CLASS - 1 | CU-45M07; 40O02,56Y13,57BB07,68BB07,08V01. 45M07-GOVERNOR SEAL MISSING/CALIBRATE AND SEAL IN THE PRESENCE OF A CITY I... | $1,000 | $0 | Sep 28, 2017 |
| May 10, 2017 | 38254395K | RESOLVE | CLASS - 2 | 31V1,47B1. 31-LEVELING UNIT IN BASEMENT NOT LEVEL ADJUST BALANCE FOR MORE WEIGHT IF OVER 700 LBS HITS LIMIT; 47-DRUM ... | $500 | $0 | Aug 24, 2017 |
| Mar 2, 2017 | 38253154P | RESOLVE | CLASS - 1 | 5M78,97X10. 5-CAR DOOR MISSING PROVIDE; 97-ENTIRE DEVICE INOPERATIVE REPAIR. FAILURE TO MAINTAIN EQUIPMENT IN COMPLIA... | $1,000 | $0 | Apr 20, 2017 |
| Feb 16, 2017 | 38253197P | RESOLVE | CLASS - 1 | 97X17 THE ONLY ELEVATOR IN BLDG OUT OF SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A H... | $1,000 | $0 | Apr 6, 2017 |
| Feb 14, 2017 | 38254230M | RESOLVE | CLASS - 2 | 17J01;21J01;52M07;54M07;55M07;56O02;70O02;71X10;45M07;37I04;37D06;41D06:17J-ADJUST SWING DOORS ON 4&5 FLOORS.21J-ADJU... | $0 | $0 | Jun 22, 2017 |
| Jan 17, 2017 | 38252370P | RESOLVE | CLASS - 2 | 40P16,37P16,70P16. 40,37,70P - NO MEANS OF ACCESS; 16-PROVIE MEANS OF ACCESS TO COMPLETE THIS INSPECTION. | $0 | $0 | Mar 9, 2017 |
| Dec 12, 2016 | 38251674J | RESOLVE | CLASS - 1 | 2X10,11B7,21Q3,8V1. (2X)OUTSIDE COMMUNICATION NOT WORKING. (11B)5TH FLR BUTTON NOT WORKING. (21Q)B,L, INTERIOR COVERS... | $1,000 | $0 | Jan 26, 2017 |
| Nov 18, 2016 | 38250322L | RESOLVE | CLASS - 2 | 46Z10 WATER LEAK MACHINE ROOM REPAIR | $500 | $0 | Jan 5, 2017 |
| Oct 26, 2016 | 35201648L | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARTUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE.IN THE BSMT ... | $400 | $0 | Feb 9, 2017 |
| Oct 26, 2016 | 35201647J | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS.FROM THE MAIN ELECTRICAL SERVICE SWITCH TO THE WATER MAIN THERE IS NO ELECTRICAL... | $0 | $0 | Feb 14, 2017 |
| Oct 26, 2016 | 35201649N | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/OUT PERMIT.OBSERVED @11:00 AM IN APTS 40 & 32 NEW ELECTRICAL WORK THROUGHOUT THE ENTIRE APTS (1) NE... | $400 | $0 | Dec 15, 2016 |
| Jun 10, 2016 | 38243315H | RESOLVE | CLASS - 2 | 40P16,37P16,70P16,02B07,52B12. 40,37,70-PROVIDE ACCESS TO COMPLETE THIS COMPLAINT INSPECTION; 02-2WAY COMMUNICATION N... | $500 | $0 | Jul 28, 2016 |
| Apr 4, 2016 | 38242079K | RESOLVE | CLASS - 1 | 97-X-10:FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER,SERVICE EQUIPMENT-ELEVATOR AS PER BC ACTIVE.UPON INSP THE D... | $1,000 | $0 | Sep 1, 2016 |
| Feb 2, 2016 | 38240047R | RESOLVE | CLASS - 1 | 97X10,06I10. FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER SERVICE EQUIPMENT ELEVATORS ER BC 3001.2.1278 98) ... | $0 | $0 | Apr 21, 2016 |
| Dec 16, 2015 | 38239536J | RESOLVE | CLASS - 2 | 42V01,40P16,02B10,71I10,70O02,41B11. 42-CAR IS 4"HIGH AT LOBBY,ADJUSTSELECTOR, 30-NO ACCESS TO OVERHEAD; 02-CAR PHONE... | $1,250 | -$1,250 | Feb 4, 2016 |
| Apr 6, 2015 | 38235499L | RESOLVE | CLASS - 1 | CU-08V01,67L10,100M07. 08-FLOOR STOPS EXCESSIVELY OUT OF LEVEL MUST REPAIR IMMEDIATELY. 6STROY BUILDING ONLY ELEVATOR... | $1,000 | $0 | May 21, 2015 |
| Jul 22, 2014 | 38231724K | RESOLVE | CLASS - 2 | 6-7L10,34M07,16L10,39O02,05L01,61L11,29L10,23L10,22M07,57L10,05AM07,08B01. 67PHONE; 34FACIA UNDER 6TH 3RD BSMT DOOR;1... | $500 | $0 | Oct 30, 2014 |
| Apr 23, 2014 | 38231353K | RESOLVE | CLASS - 2 | 42L10/ 61L11/ 100N07/ 71L10/ 54B12/ 55B12/ 05M07/ 05AL01/ 67L10/ 21L1023M07/ 99M07/ #42 MOUNT OPEN RELAY PROPERLY & D... | $1,250 | -$1,250 | Jun 12, 2014 |
| Jan 27, 2014 | 38229696J | RESOLVE | CLASS - 2 | 05J01,02L10,23L10. 05J01-CAR DOOR LARGE GAP ADJUST; 02L10-IN CAR COMMUNICATIONS NOT WORKING REPAIR;23L10-3RD FLOOR HA... | $500 | $0 | Mar 13, 2014 |
| Dec 18, 2013 | 38229600X | RESOLVE | CLASS - 2 | 08V01,41W07,67B10,57V10,70O02,10H10. 08V01-ADJUST LEVELING; 41W07-OVERHEAD MR DOOR NOT SECURE; 67B10-REPAIR COMMUNICA... | $500 | $0 | Feb 6, 2014 |
| Mar 5, 2013 | 38226028K | RESOLVE | CLASS - 2 | 100M7,13M7,40P16,70O02. OVERHEAD NEEDS LIGHT AND STOP SWITCH, NEED BRAILLE TAGS ON ALL FLOORS; NO PHONE IN CAR,EMERGE... | $0 | -$250 | Apr 25, 2013 |
| Dec 30, 2011 | 38216419Z | RESOLVE | CLASS - 2 | 05B07,23I10,70O02,08J01,43X10,03I10,100B07,29Q03,100M07,11E01: 05-PROVIDE 2 GIBS PER DOOR; 23-SEAL HOLE ON 2ND FLOOR;... | $0 | $0 | Feb 16, 2012 |
| Sep 28, 2011 | 34925456Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE-COMPLIANT MANNER. NOTED: AT WEST WING SOUTH ELEVATION, 6TH FLR FIRE ESCAPE ELEMENT... | $2,500 | -$2,500 | Nov 17, 2011 |
| Sep 28, 2011 | 34925457X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE-COMPLIANT MANNER. NOTED: AT SOUTH ELEVATION, 6TH FLR, MASONRY CRACKED, DISPLACED; ... | $2,500 | -$2,500 | Nov 17, 2011 |
| Feb 7, 2011 | 38215095R | RESOLVE | CLASS - 2 | 10B07,21Q03,99BB05.(10B07)PROVIDE ADDITIONAL GIBBS FOR CAR CAR DOOR.(21Q03)INSTALL COVER FOR BSMNT HOISTWAY DOOR INTE... | $0 | $0 | Mar 24, 2011 |
| Oct 18, 2010 | 38213111Z | RESOLVE | CLASS - 2 | 58B01 16B01 42G09 98BB07 37D06 42I11 58B01-ADJUST FLOOR STOPS B 2-4TH FL 16B01-ADJUST 3RD FL HOISTWAY DOOR 42G09-REMO... | $0 | $0 | Dec 13, 2010 |
| Sep 1, 2010 | 38212822K | RESOLVE | CLASS - 2 | 08V01,20I11,42D06. 20I- REPLACE DAMAGED BASEMENT HOISTWAY DOOR VISION GLASS. 42D- SECURE TIMER RELAY ON CONTROLLER. | $0 | $0 | Oct 21, 2010 |
| Jun 2, 2009 | 38201439Y | RESOLVE | CLASS - 2 | 08B1.56Y13.68M7 08B01 FL STOPS ARE NOT LEVEL NEED TO BE ADJUSTED 06Y13 HOIST MOTOR AND MACHINE ARE LEAKING NEED TO BE... | $500 | $0 | Sep 9, 2010 |