ECB violations

138 West 143 Street, Manhattan • Block 02011 • Lot 0053

44 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Apr 17, 2026 39185016L ACTIVE CLASS - 2 ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED THRU OUT BUILDING NEW EMERGENCY LIGHTS INSTALLED. ALSO IN THE BASEMENT TWO... $1,280 $1,280 Jun 25, 2026
Apr 17, 2026 39185017N RESOLVE CLASS - 2 FAILURE TO PROVIDE ADEQUATE GROUNDING OF ELECTRICAL SYSTEMS. OBSERVED IN THE MAIN ELECTRICAL THAT THE MAIN HOUSE WATE... $2,430 $2,430 Jun 25, 2026
Mar 12, 2025 39141295Z RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $2,500 $0 Mar 30, 2026
Mar 12, 2025 39141294R RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING.NON SELF CLOSING DOOR AT SPRINKLER VALUE CONTROL ROOM. LOCATED AT BASEMENT LEVEL. POTENTIA... $312 $0 Mar 30, 2026
Apr 15, 2024 39111750Y RESOLVE CLASS - 1 RAZOR WIRE INSTALLED ON PERIMETER FENCE BLOCKING FIRE ESCAPE EXIT TO GROUND LEVEL, THROUGHOUT BUILDING. RAZOR WIRE CA... $1,280 $0 Aug 1, 2024
Apr 15, 2024 39111728H RESOLVE CLASS - 2 OBSERVED NEWLY INSTALLED PIPING TO BASEBOARDS HEATERS AND IN BOILER ROOM NO PERMITS ON FILE AT THE TIME OF MY INSPECT... $0 $0 Mar 13, 2025
Apr 15, 2024 39111729J RESOLVE CLASS - 2 OBSERVED IN THE COURTYARD EXCESSIVE PONDING OF BLACK WATER. WORKERS ARE FORCED TO WALK ON PALLETS TO AVOID GOING THRO... $655 $0 Aug 1, 2024
Oct 3, 2022 39071301P RESOLVE CLASS - 2 -AT ROOF LEVEL, PARAPET WALLS/ FACADES EXPOSURE # 1,2,3& 4, SEVERAL CRACKS, LIFTING AND LOSS MORTAR, AT CELLAR LEVEL,... $3,155 $0 Nov 17, 2022
Oct 3, 2022 39071289L RESOLVE CLASS - 2 I OBSERVED IN THE FIRST FLOOR BATHROOM, THE BASEMENT BOILER ROOM DEFECTIVE GFCI RECEPTACLE OUTLETS. THE RECEPTACLES F... $6,030 $0 Nov 17, 2022
Oct 3, 2022 39071303Z RESOLVE CLASS - 2 AT CELLAR LEVEL, EXIT DOORS EXPOSURE # 2, 3, &4 DO NOT CLOSE PROPERLY WHEN INSPECTED. ALSO, METAL STAIR FROM FIRST FL... $1,592 $0 Nov 17, 2022
Oct 3, 2022 39071302R RESOLVE CLASS - 2 CELLAR LEVEL, UTILITIES/STORAGE ROOMS, CORRIDORS, SEVERAL OPENING, DUE PIPES PENETRATION, THROUGH FIRE PROOF WALLS/CE... $3,155 $0 Nov 17, 2022
Oct 3, 2022 39071293Y RESOLVE CLASS - 2 I OBSERVED THE CONSTRUCTION OF A ROOM AT THE BASEMENT LEVEL WITH CONDUITS, JUNCTION BOXES, WIRING AND DEVICES INSTALL... $830 $0 Nov 17, 2022
Oct 3, 2022 39071291K RESOLVE CLASS - 2 I OBSERVED IN THE BASEMENT GAS METER ROOM EMT CONDUIT INSTALLED FROM THE EXTERIOR SWITCH BOX TO A JUNCTION BOX INSIDE... $1,280 $0 Nov 17, 2022
Oct 3, 2022 39071292M RESOLVE CLASS - 2 I OBSERVED IN THE OUTSIDE PASSAGEWAY THE UNPERMITTED USE OF EMT OUTDOORS. ALSO NOTED THE LIGHTING ALONG THE PASSAGEWA... $530 $0 Nov 17, 2022
Oct 3, 2022 39071290Z RESOLVE CLASS - 2 I OBSERVED ON THE FIRST FLOOR EXPOSED AND ENERGIZED CONDUCTORS IN A METAL RACEWAY IN THE CORRIDOR NEAR THE VENDING MA... $830 $0 Nov 17, 2022
May 26, 2022 39062969K RESOLVE CLASS - 2 AT CELLAR LEVEL, EXIT DOORS WITHOUT A SELF-CLOSING SYSTEM AND DOORS DO NOT MEET TECHNICAL AND SAFETY STANDARDS. ALSO,... $1,562 $0 Jul 14, 2022
May 26, 2022 39062968Z RESOLVE CLASS - 2 AT CELLAR LEVEL, ELECTRICAL RM,CORRIDORS, STORAGES RM & BOILER RM SEVERAL OPENING DUE PIPES PENETRATION THROUGH THE F... $3,125 $0 Jul 14, 2022
May 26, 2022 39062970H RESOLVE CLASS - 2 AT PARAPET WALLS, FACADE WALLS, SEVERAL CRACKS, STUCCO LIFTING AND LOSS OF MORTAR IN DIFFERENT LOCATIONS, ALSO, AT CE... $5,000 $0 Jul 14, 2022
Oct 28, 2021 39050186X RESOLVE CLASS - 2 NOTED: OBSERVED AT CELLAR, STONE WALL NEAR EXIT DOOR THAT LEADS TO EXPOSURE #2 HAS APPROXIMATELY 1.5 INCH CRACKS THRO... $1,562 -$1,562 Dec 16, 2021
Sep 23, 2021 39048008K RESOLVE CLASS - 2 MISSING DISCHARGE PIPE ON RELIEF VALVE ON HOT WATER STORAGE TANK,LEAK ON PIPE AT BOTTOM OF TANK,CORRECT VIOLATION AND... $1,562 -$1,562 Nov 18, 2021
Sep 23, 2021 39048009M RESOLVE CLASS - 2 HARD PIPE GAS LINE TO REGULATOR REMOVE STOPPER ON BAROMETRIC,LEAK ON RETURN CORRECT VIOLATION AND SEND IN CERTIFICATE... $1,562 -$1,562 Nov 18, 2021
Dec 19, 2019 35514039N RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35386220Y ISSUED ON 03/20/19 & TO FILE A C OF C PURSUAN... $6,250 $0 Feb 27, 2020
Nov 21, 2019 35512776Y RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35386220Y ISSUED ON 03/20/19 & TO FILE A C OF C PURSUAN... $12,500 $0 Apr 2, 2020
Oct 16, 2019 35511847H RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35386220Y ISSUED ON 03/20/19 & TO FILE A C OF C PURSUAN... $6,250 $0 Jan 7, 2021
Oct 16, 2019 35430931X RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35386220Y ISSUED ON 03/20/19 & TO FILE A C OF C PURSUAN... $2,500 $0 Aug 13, 2020
Sep 9, 2019 39009152N RESOLVE CLASS - 2 I OBSERVED IN THE GAS METER THE INSTALLATION OF CONDUITS BRANCH CIRCUIT WIRING AND RECEPTACLE OUTLETS. NO ELECTRICAL ... $2,000 -$2,000 Apr 8, 2021
Sep 9, 2019 39009153P RESOLVE CLASS - 2 I OBSERVED IN THE GAS METER ROOM THE INSTALLATION OF RECEPTACLE OUTLETS NOT OF THE GFCI TYPE. PHOTOS TAKEN., INSTALL ... $5,000 -$5,000 Apr 8, 2021
Sep 9, 2019 39009154R RESOLVE CLASS - 2 I OBSERVED IN THE GAS METER ROOM EMT CONDUITS ON THE CEILING UNSUPPORTED. PHOTOS TAKEN., PROPERLY SECURE/SUPPORT EMT $1,250 -$1,250 Apr 8, 2021
Aug 14, 2019 35427490M RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35386220Y ISSUED ON 03/20/19 & TO FILE A C OF C PURSUAN... $6,250 $0 Oct 17, 2019
Jun 6, 2019 35400336Y RESOLVE CLASS - 1 FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35386220Y ISSUED ON 03/20/19 AND TO FI... $6,250 $0 Aug 8, 2019
Mar 20, 2019 35386220Y RESOLVE CLASS - 2 WORK WITHOUT A PERMIT.OBSERVED ON 03/20/19 AT ABOVE ADDRESS NEWLY INSTALLED WATER HEATER IN BASEMENT/CELLAR.EMERGENCY... $625 $0 May 30, 2019
Nov 26, 2018 32098029K RESOLVE CLASS - 1 B101 AS PER CLAS 1 B101, 28-105.1 VIOLATING CONDITION FOUND LOCHINVARCWN 399 GAS FIRED BOILER INSTALLED W/O PERMIT OB... $6,250 -$6,250 Jan 17, 2019
Jul 9, 2018 32097186J RESOLVE CLASS - 1 B154,3C,4A,10A,50A,51. B154 LOCHINVAR BOILER MODEL #RWN399PM399,000BUT3C,4A,10A,51 HOLES IN FLUE PIPE AND LOW CUT OFF... $1,250 $0 Aug 28, 2018
Aug 23, 2017 35290281L RESOLVE CLASS - 1 ELECTRICAL WORK W/O PERMIT.OBSERVED IN ELECTRICAL ROOM LOCATED IN BSMTTHE INSTALLATION OF 4-400AMP,1-200AMP AND 1-100... $4,000 $0 Mar 22, 2018
Aug 23, 2017 35290282N RESOLVE CLASS - 1 FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE W/SECTION.OBSERVED IN BSMT AT WATER MAIN;MAIN GROUNDIN... $12,000 -$12,000 Mar 22, 2018
May 11, 2017 35271439Z RESOLVE CLASS - 1 FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED.OBSERVED IN BASEMENT/CELLAR OF 138 BUILDING REPLACED GAS PIPING... $250 $0 Dec 14, 2017
Apr 27, 2017 35231519M RESOLVE CLASS - 2 FAILURE TO COMPLY W/COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35226504N ISSUED ON 09/21/16 AND TO FILE A C... $0 $0 Jun 4, 2020
Feb 4, 2017 35229131N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER;LACK OF SYSTEM OF AUTOMATIC SPRINKLERS.WHERE REQUIRED-PER BC 9203.2... $500 -$43 Feb 16, 2018
Sep 21, 2016 35226505P RESOLVE CLASS - 1 FGC401.5/OBSERVED IN BST/CELLAR NEW GAS PIPING & FITTING NO HAVING PROPER IDENTIFICATIONS LABELS AND GAS FLOOR PIPING... $400 $0 Feb 16, 2018
Sep 21, 2016 35226504N RESOLVE CLASS - 1 FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEMS TESTED OBSERVED IN BASE/CELLAR OF 138 BLDG REPLACED GAS PIPING VALUE ... $0 $0 Feb 8, 2018
Sep 21, 2016 35226503L RESOLVE CLASS - 1 FGC403.10.1/MISC VIOLATION-OBSERVED IN CELLAR/BST OF 138 BLDG ILLEGAL DRESSER COUPLING & RUNNING THREAD COUPLING ON H... $1,600 $0 Feb 16, 2018
Mar 9, 2016 35177266Z RESOLVE CLASS - 2 WORK W/O A PERMIT. WORK NOTED: AT BUILDING 138, 2ND FLOOR APT #2H AND 2F REMOVED GAS STOVES, RESIDENTIAL SINKS AT KIT... $2,000 $0 May 26, 2016
Mar 9, 2016 35177265R RESOLVE CLASS - 3 OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS CERTIFICATE OF OCCUPANCY ... $250 -$250 May 26, 2016
Oct 18, 2006 32051438N RESOLVE Hazardous 51/50A: 50A-BOILER EMITTING CARBON MONOXIDE FROM BURNER MOUNT GASKETS@228PPM'S-HAZARDOUS-REPAIR IMMEDIATELY -CEASE USE $400 $0 Dec 7, 2006