ECB violations
141-145 West 144 Street, Manhattan • Block 02013 • Lot 0009
52 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 16, 2025 | 39170621H | ACTIVE | CLASS - 2 | OBSERVED IN THE BASEMENT OPEN ENDED WASTE LINES, A DAMAGE SPRINKLER HEAD, BUSHING FITTING ON GAS LINE AND GAS DRYER V... | $1,250 | $1,250 | Oct 1, 2026 |
| Dec 16, 2025 | 39170593J | ACTIVE | CLASS - 2 | FOUND HB SMITH OIL FIRED BOILER MODEL# 28A-10, WITH LEAKING CONDENSATE PUMP, GLASS GAUGE AT CONDENSATE TANK DIRTY, CO... | $6,250 | $6,250 | Mar 19, 2026 |
| Dec 16, 2025 | 39170724K | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBL... | $1,250 | $1,250 | Feb 26, 2026 |
| Mar 14, 2025 | 39141606R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED GAS METER WITH NO FRESH AIR VENTILATION FOR GAS PIPIN... | $0 | $0 | May 22, 2025 |
| Mar 14, 2025 | 39141607Z | RESOLVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED UNSAFE STOREAGE UNDERNEATH BOTH STAIRCASES. (BOXES, WO... | $2,500 | $2,500 | Nov 7, 2025 |
| Mar 14, 2025 | 39141605P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $2,500 | Nov 7, 2025 |
| Mar 12, 2025 | 39141275L | RESOLVE | CLASS - 2 | CLASS 2 ITEMS: REPAIR OIL LEAK AND CLEAN HOIST MACHINE. IN-CAR COMMUNICATION INOPERATIVE. PROVIDE AN UPDATED MAINTENA... | $312 | $312 | May 22, 2025 |
| Jun 17, 2024 | 39117033Z | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR BYPASSED. REMEDY: REPAIR / REPLACE. CALL THE D.O.B. FOR REINSPECTION. | $1,250 | $1,250 | Jan 16, 2025 |
| Apr 15, 2024 | 39111658L | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB# 39071367H ISSUED ON 10/04/2022 AND CORR... | $625 | $625 | Jun 20, 2024 |
| Apr 15, 2024 | 39111661M | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT ELECTRICAL ROOM THE INSTALLATION OF A FULL HEIGHT ERECTED WALL THAT BLOCKS ACCESS TO THE A... | $1,250 | $0 | Jun 26, 2025 |
| Apr 15, 2024 | 39111659N | RESOLVE | CLASS - 2 | I OBSERVED THE INSTALLATION OF CONDUIT RACEWAYS, OUTDOOR EXIT SIGNS ALONG THE EXTERIOR OF PROPERTY, AND EQUIPMENT SWI... | $0 | $0 | Nov 14, 2024 |
| Apr 15, 2024 | 39111660K | RESOLVE | CLASS - 1 | I OBSERVED IN THE WATER METER ROOM THE DETERIORATED CONDITION OF THE JUMPER WIRE DUE TO EXCESSIVE HEAT, THIS WAS VERI... | $1,600 | $1,600 | Jun 26, 2025 |
| Apr 10, 2024 | 39111283Y | RESOLVE | CLASS - 2 | IN CAR PHONE OR INTERCOM NOT WORKING. PROVIDE ELECTRICAL SWITCH FOR THE GOVERNOR , CONTROLLER HAS A DRIVE. PROVIDE LA... | $0 | $0 | Nov 14, 2024 |
| Dec 20, 2023 | 39101853H | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 35657507N ISSUED ON 07/... | $625 | $625 | Jan 2, 2025 |
| Jul 20, 2023 | 35657507N | RESOLVE | CLASS - 1 | PERFORMING UNLICENSED PLUMBING WORK WITHOUT PERMIT RESPONDENT ENGAGED IN THE BUSINESS, TRADE, OCCUPATION OF PLUMBING ... | $5,000 | $0 | Aug 5, 2024 |
| Oct 4, 2022 | 39071364M | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT STORAGE AREA A CONVENIENCE RECEPTACLE NOT OF THE GFCI TYPE NOR GFCI PROTECTED AS REQUIRED ... | $1,200 | $0 | Apr 10, 2023 |
| Oct 4, 2022 | 39071365Y | RESOLVE | CLASS - 3 | I OBSERVED IN THE PANELS ON ALL FLOORS IMPROPERLY OR NOT LABELED AS REQUIRED., PROVIDE CIRCUIT DIRECTORY/ID; PROVIDE ... | $100 | $0 | Apr 10, 2023 |
| Oct 4, 2022 | 39071367H | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT ELECTRICAL ROOM WALLS ERECTED TO CREATE A NEW ROOM PRIOR TO ENTERING THE MAIN ELECTRICAL A... | $500 | $0 | Jan 5, 2023 |
| Oct 4, 2022 | 39071329R | RESOLVE | CLASS - 2 | AS PER ONE FUEL OIL BURNING SMITH 28A-10 STEAM BOILER. CLEANOUT AT CHIMNEY BASE W/O REMOVABLE CAP OR CLEANOUT DOOR TO... | $0 | $0 | Dec 1, 2022 |
| Oct 4, 2022 | 39071366X | RESOLVE | CLASS - 2 | I OBSERVED IN THE REAR COURTYARD THE INSTALLATION OF BRANCH CIRCUIT WIRING TO OUTDOOR SPLIT UNIT CONDENSOR . NO DOB P... | $800 | $0 | Apr 10, 2023 |
| Sep 24, 2019 | 39009971R | RESOLVE | CLASS - 2 | I OBSERVED AN ELECTRICAL OUTLET TAPPED FROM THE EXIT LIGHT SPLICE BOX WITH EXPOSED ENERGIZED CONDUCTORS. , COMPLY WIT... | $830 | $0 | Jan 30, 2020 |
| Apr 8, 2019 | 39001984J | RESOLVE | CLASS - 2 | FOUND CORRODED PIPING ON HART FORD LOOP, AT DHW COIL AND AT WATER COLUMN,. REPLACE ALL CORRODED PIPING. HOLES IN WALL... | $312 | $0 | Jun 27, 2019 |
| Feb 19, 2019 | 38268267N | RESOLVE | CLASS - 2 | 37D6,59BB7,59B2,67X10. 27D6-PROPERLY SECURE OVERHEAD LADDER; 59BB7-BRAKE MAINTENANCE TAG EXPIRED; 59B2-CLEAN BRAKE SH... | $0 | $0 | Jun 6, 2019 |
| Oct 9, 2018 | 32097850Z | RESOLVE | CLASS - 2 | B254,40,50,50A,50B,50C,50D 50-NEED TO ADJUST BURNER 50A NEET TO SEAL AROUND SUPPORTING FLUE PIPE.50C NEED TO REMOVE A... | $1,562 | $0 | Dec 6, 2018 |
| Oct 5, 2018 | 35361396R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: AT EXP#1 PARAPET WALL,AT SOUTH-WEST CORNER,THERES A VERTICLE ... | $0 | $0 | Nov 29, 2018 |
| May 25, 2018 | 35313420L | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. IN 12/22/17;4/26/18. 2 ELECTRICAL VIOLATIONS WAS ISS... | $2,500 | $0 | Oct 18, 2018 |
| Mar 26, 2018 | 35313088Z | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY W/ORDER OF THE COMMISSIONER.ON AUGUST 23,2017 AN ELECTRICAL VIOLATION WAS ISSUED TO T... | $625 | $0 | Sep 13, 2018 |
| Feb 16, 2018 | 38261320L | RESOLVE | CLASS - 1 | C/U 05A10,R/C 02X16,68M07,68B07,52M07,53M07,26D07,39X10,56Y13,39P16. 05A10 CEASE USE ITEM.DOOR ZONE RESTRICTOR HAS BE... | $2,500 | $0 | Apr 5, 2018 |
| Aug 23, 2017 | 35293677L | RESOLVE | CLASS - 1 | FAILUR ETO GROUND ELECTRICAL SYSTEMS.OBSERVED IN BSMT @WATER MAIN PIPE:MAIN GROUNDING CONDUCTOR FOR BLDGS ELECTRICAL ... | $4,800 | $0 | Jul 12, 2018 |
| Aug 23, 2017 | 35290280J | RESOLVE | CLASS - 1 | SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL. OBSERVED IN ELECTRICAL ROOM LOCATED IN BASEMENT. | $0 | $0 | Oct 12, 2017 |
| Aug 23, 2017 | 35290006R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NOTED:OBSERVED AT STAIR "B"ROOF BULK-HEAD SPALLING PLASTER AROU... | $250 | $0 | Oct 12, 2017 |
| Mar 17, 2017 | 35235147Z | RESOLVE | CLASS - 1 | SEC: FGC 411.1. RESIDENTIAL GAS FLEX USED IN COMMERCIAL EQUIPMENT. OBSERVED ON 3/17/17 @ ABOVE ADDRESS RESIDENTIAL GA... | $1,600 | $0 | Aug 17, 2017 |
| Mar 17, 2017 | 35235148K | RESOLVE | CLASS - 1 | SEC: FGC 408.2. DRIPS-FUTURE CONNECTIONS EXIST DOWN STREAM OF APPLIANCE. OBSERVED ON 3/17/17 IN LAUNDRY ROOM FUTURE C... | $0 | $0 | Aug 23, 2017 |
| Jan 18, 2017 | 38252700Z | RESOLVE | CLASS - 2 | 59V15,68B7. 59-PROVIDE BRAKE MAINTENANCE TAG AS PER A17.1 2003 AND APPENDIX K3 8.6.4.6; 68-MAINENANCE LOG BOOK NOT UP... | $0 | $0 | Mar 9, 2017 |
| Sep 23, 2016 | 35212782X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:LACK OF A SYSTEMOF AUTOMATIC SPRINKLERS WHERE REQURIED OR ALTER... | $0 | $0 | Jan 24, 2017 |
| Apr 18, 2016 | 35177274Z | RESOLVE | CLASS - 3 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.CO#92253 INDICATES BASEMENT TO BE 2 CLASS'A'APT... | $0 | $0 | Jan 10, 2017 |
| Apr 18, 2016 | 35177273R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: EXCESSIVE STORAGE OF BOXES AND OTHER ITEMS IN GAS METER... | $250 | $0 | Jun 2, 2016 |
| Jun 18, 2015 | 38236612Z | RESOLVE | CLASS - 2 | 13-L-10,10-B-01,16-B-01,42-G-07,56-Y-13,59-O-02,61-B-07:10-B-ADJUST DOOR GIBS INTO TRACK.16-B-ADJUST SWING DOORS (VAR... | $0 | $0 | Aug 6, 2015 |
| Dec 18, 2012 | 38224830Z | RESOLVE | CLASS - 2 | 13M7,1009M7,71M7. 100-PHONE IN CAR NEED ALSO EMERGENCY LIGHT. | $0 | $0 | Feb 7, 2013 |
| Nov 19, 2002 | 38134170N | RESOLVE | Non-Hazardous | 33M07-26Q07-39G12-80B12. 33-MISSING COVERS SHAFT RISER, 80-RASETTE MUST COMPLY WITH RULE 212.9F ANSI A17.1 1987. | $0 | $0 | Jan 9, 2003 |
| Jan 16, 2002 | 38120758R | RESOLVE | Non-Hazardous | 15L11-17A12-18L11-22O2-23U16-37G12-46B15-50U16-37U16-53B7-73O2-74M7-3M7. 15-L-11 SLAMS BSMT FLOOR 17-A-12 MUST BE WIR... | $0 | $0 | Mar 7, 2002 |
| Jul 9, 2001 | 38114541P | RESOLVE | Non-Hazardous | 60I11/ 60- REPAIR DAMAGE CUT BUFFER | $0 | $0 | Aug 23, 2001 |
| Jul 26, 2000 | 38106217N | RESOLVE | Non-Hazardous | 47B15 02I12 47-SHORTEN GOVERNOR CABLE 02-REPLACE DAMAGED BUTTON ON FIRE STATION IN CAR. | $0 | $0 | Sep 14, 2000 |
| Jul 16, 1999 | 38087337R | RESOLVE | Non-Hazardous | 75U, 15B. | $180 | $0 | Sep 2, 1999 |
| Feb 3, 1999 | 38083668N | RESOLVE | Non-Hazardous | 75U5,9H12,46U16,3O2. | $0 | $0 | Mar 25, 1999 |
| Jan 14, 1998 | 38069071J | RESOLVE | Non-Hazardous | 30O30O18U3233P50Y57O62K62K 30-CLEAN CAR TOP 18-SECURE ALL INTERLOCK COVER 32-PUT THE RIGHT DUCT WORK COVER. | $180 | $0 | Mar 5, 1998 |
| Aug 26, 1997 | 34158043L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL VERTICAL CRACKS BETWEEN 2ND AND 3RD FLOOR BATHRROM WINDOWS WEST COURT YARD... | $0 | $0 | Dec 18, 1997 |
| Aug 11, 1997 | 38062733H | RESOLVE | Non-Hazardous | 1A18D314774R74I 1 EMS STOP SWITCH LOW SOUND 18-5TH FLOOR INERLOCK NOT SECURE 31-COVER OFF ELECTRIC BOX TOP OF CAR 74-... | $0 | $0 | Oct 2, 1997 |
| Nov 12, 1996 | 38057474X | RESOLVE | Non-Hazardous | 15L,28L,31L,37#,46L,30O,57M,73#,. 15L-WAKE ALL DOORS TO BE SELF CLOSING 46L-TENSION 57M-LADDER AND PIT STOP SWITCH 73... | $500 | $0 | Mar 13, 1997 |
| Sep 7, 1993 | 38036668L | RESOLVE | Non-Hazardous | 17R,17Q,22D,25Q,18L,37R,46L,47H,73U,75T, 17R-FOR WIRE-GLASS 17Q-CAR DOOR 37R- JUMPED FUSE | $0 | $0 | Oct 21, 1993 |