| Jul 29, 2026 | 39198223R | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSP... | $3,125 | $3,125 | Oct 8, 2026 |
| Jul 22, 2026 | 39197170H | ACTIVE | CLASS - 1 | RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-9... | $1,250 | $1,250 | Oct 1, 2026 |
| Jun 16, 2026 | 39192763K | ACTIVE | CLASS - 1 | CLASS1 ITEM: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, SERVICE ELEVATOR EQUIPMENT AS PER CODE BC3001.2 &... | $1,250 | $1,250 | Aug 20, 2026 |
| May 4, 2026 | 39553760X | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION OF 7 STORY BUILDING OBSERVED SIDEWALK SHED IN PLACE NOT COVERING THE FULL WIDTH OF SIDEWALK CAU... | $0 | $0 | Jul 9, 2026 |
| Apr 20, 2026 | 37036520Z | ACTIVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 9A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $3,125 | $3,125 | Sep 17, 2026 |
| Apr 10, 2026 | 39184117X | ACTIVE | CLASS - 1 | UPON INSPECTION, IT WAS FOUND THAT THE BUILDINGS ONLY ELEVATOR HAS BEEN OUT OF SERVICE FOR A PERIOD OF SEVERAL MONTHS... | $25,000 | $25,000 | Jun 18, 2026 |
| Mar 16, 2026 | 39180520H | ACTIVE | CLASS - 1 | CLASS 1 (RTS): FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27... | $25,000 | $25,000 | May 21, 2026 |
| Dec 23, 2025 | 39171318J | ACTIVE | CLASS - 1 | RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-9... | $25,000 | $25,000 | Feb 26, 2026 |
| Nov 18, 2025 | 39167336L | ACTIVE | CLASS - 2 | I FOUND A BEST 5B-80 BOILER WITH BACKFLOW AIR GAP/DRAIN PIPE MISSING AND LEAKING/LIGHTS NEED TO BE FIX/SAFETY VALVE O... | $1,250 | $1,250 | Feb 19, 2026 |
| Sep 19, 2025 | 35718578R | ACTIVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY ON FIRE ESCAPE.AS PER NOTED AT TIME OF INSPECTION OBSERVED NUMEROUS O... | $1,250 | $1,250 | Jan 15, 2026 |
| Aug 26, 2025 | 39544136H | ACTIVE | CLASS - 2 | AT TIME OF INSPECTION OF 7 STORY MIXED USE BUILDING OBSERVED SIDEWALK SHED IN PLACE NOT MAINTAINED PER CODE 1. ROTTIN... | $2,430 | $0 | May 1, 2026 |
| Aug 13, 2025 | 39543599J | ACTIVE | CLASS - 2 | AT TIME OF INSPECTION OF 6 STORY MIXED USED BUILDING OBSERVED SIDEWALK SHED IN PLACE NOT MAINTAINED PER CODE SPECIFIC... | $2,430 | $0 | Oct 30, 2025 |
| Jul 10, 2025 | 39153267J | ACTIVE | CLASS - 1 | CLASS 1: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS IS A RECURRING CONDITION CREATING SAFETY HAZZARDS FO... | $25,000 | $25,000 | Sep 18, 2025 |
| Nov 4, 2024 | 39129433X | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSP... | $6,250 | $6,250 | Feb 5, 2026 |
| Sep 19, 2024 | 39125357P | ACTIVE | CLASS - 1 | : FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON IN... | $12,500 | $12,500 | Dec 5, 2024 |
| Jul 26, 2024 | 39119958J | ACTIVE | CLASS - 1 | CEASE USE ITEMS: CAR IS JUMPING DURING TRAVEL UP AND DOWN. ONE OF THE HOIST CABLES HAS DROPPED DOWN IN THE SHEAVE. AP... | $6,250 | $0 | Oct 3, 2024 |
| Apr 29, 2024 | 39528074L | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION OF 7 STORY MIXED USE BUILDING OBSERVED SIDEWALK SHED IN PLACE NOT TO CODE SPECIFICATIONS NOT FU... | $2,400 | $0 | Nov 14, 2024 |
| Mar 13, 2024 | 39108616X | ACTIVE | CLASS - 1 | CLASS 1: CEASE USE: DOOR RESTRICTOR MISSING INSTALL & CALL NYCDOB TO REINSPECT (CU). CAR DOOR MALFUNCTIONING. 2 SPEED... | $6,250 | $6,250 | May 23, 2024 |
| Jan 16, 2024 | 37026286K | ACTIVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 9A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $1,250 | $1,250 | Jun 6, 2024 |
| Dec 20, 2023 | 39101949M | RESOLVE | CLASS - 2 | FOUND BEST( MODEL# 5B 80) DUAL FUEL BOILER IN CELLAR NOT REGISTERED CORRECT VIOLATING CONDITION SUBMIT CERTIFICATE OF... | $0 | $0 | Apr 4, 2024 |
| Nov 29, 2023 | 39100296J | ACTIVE | CLASS - 2 | CLASS 2: PHONE INOPERATIVE REPAIR & PROGRAM TO 24 HR EMERGENCY OPERATOR. UNMARKED SWITCHES ON CAR BUTTON STATION MARK... | $3,125 | $3,125 | Feb 8, 2024 |
| Jul 19, 2023 | 39090536N | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION OBSERVED SIDEWALK SHED ON SITE ALONG EXPOSURE # 01, 02 & 04. SIDEWALK SHED PERMIT # M00437229-I... | $0 | $0 | Sep 28, 2023 |
| Dec 20, 2022 | 39076045H | ACTIVE | CLASS - 2 | PHONE NOT WORKING;REPAIR, PROVIDE CITY ID IN ELEVATOR CAB, DAMAGED ENCODER ON MACHINERY, PROVIDE MOTOR ROOM SIGN | $3,125 | $0 | Feb 23, 2023 |
| Aug 3, 2022 | 35664031M | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE/TAKE REQUIRED SAFETY MEASURES SUCH AS SHED,NETTING,FENCE,CONTROLLED ACCESS ZONE ETC.WHERE REQUIRED... | $0 | $0 | Jul 10, 2023 |
| Jul 25, 2022 | 39504069K | RESOLVE | CLASS - 2 | SIDEWALK SHED NOT MAINTAINED BOLT CAPS MISSING, FIRE ESCAPE NOT ENCLOSED PROPERLY AND DAMAGED PARAPET PANEL.MAINTAIN | $2,400 | $0 | Mar 13, 2023 |
| May 23, 2022 | 35651388M | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE/TAKE REQUIRED SAFETY MEASURES SUCH AS SHED NETTING FENCE CONTROLLED ACCESS ZONE ETC WHERE REQUIRED... | $0 | $0 | Aug 18, 2022 |
| Apr 5, 2022 | 35651125K | RESOLVE | CLASS - 1 | FAILURE TO TAKE AND PROVIDE ADEQUATE SAFETY MEASURES TO PROTECT AND SECURE PUBLIC SAFETY FROM DOCUMENTED UNSAFE FACAD... | $10,000 | $0 | Jan 12, 2023 |
| Mar 14, 2022 | 39058021Y | ACTIVE | CLASS - 1 | FOUND NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014NYBC. THI... | $3,125 | $0 | Apr 28, 2022 |
| Feb 10, 2022 | 35243636J | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY C/O&DOB RECORDS ILLEGAL CELLAR APT CREATED W/STUDS&SHEETROCK INCREASING OCCUPAN... | $0 | $0 | Mar 21, 2023 |
| Dec 21, 2021 | 39053230H | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Mar 31, 2022 |
| Nov 4, 2021 | 35635543N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES.AS NOTED BUILDING FAILED TO CORRECT CONDITIONS IN SUMM... | $3,125 | $0 | Sep 1, 2022 |
| Jul 7, 2021 | 39044046N | ACTIVE | CLASS - 1 | FOUND DOOR RESTRICTOR'S PLUNGER TIED UP BY ZIP TIE. DOOR RESTRICTOR IS NOT WORKING. CEASE USE. REMOVE ZIP TIE AND REP... | $1,250 | $0 | Aug 26, 2021 |
| May 13, 2021 | 35529615Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMMISSIONER'S ORDER CONTAINED IN SUMMONS/V35540557M ISSUED11/13/20&TO FILE C/C PURSUANT TO28-201... | $0 | $0 | Oct 14, 2021 |
| Apr 9, 2021 | 39039097R | ACTIVE | CLASS - 1 | DLM IS NOT WORKING. NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NY... | $3,125 | $0 | Mar 24, 2022 |
| Mar 24, 2021 | 35528638M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35540557M ISSUED ON 11/13/2020 AND TO ... | $0 | $0 | Apr 7, 2022 |
| Jan 12, 2021 | 35526056N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35540557M ISSUED ON 11/13/20 AND TO FI... | $0 | $0 | Apr 7, 2022 |
| Jan 12, 2021 | 39034785H | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY : INSTAL... | $1,250 | $0 | Dec 16, 2021 |
| Nov 28, 2020 | 39032624H | ACTIVE | CLASS - 1 | CEASE USE ITEM, ALTERED CAR DOOR RESTRICTOR AND NOT WORKING REMEDY; REPAIR AND THEN CONTACT NYCDOB FOR RESTORE TO SER... | $6,250 | $0 | Jan 14, 2021 |
| Nov 13, 2020 | 39032075Y | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY : INSTAL... | $12,500 | $12,500 | Oct 10, 2024 |
| Nov 13, 2020 | 35540557M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BBLDG IN CODE COMPLIANT MANNER. NOTE: AT APT#6 OBSERVED WSTER PENETRATION TO CEILING & WALLS THRO... | $0 | $0 | Apr 7, 2022 |
| Sep 4, 2020 | 35519835R | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #39014462L ISSUED ON 12-16/2019 AND TO FILE... | $6,250 | $0 | Nov 12, 2020 |
| Aug 13, 2020 | 39026934M | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; INSTALL... | $6,250 | -$2,073 | Oct 1, 2020 |
| Jun 29, 2020 | 37019285N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35319267L ISSUED ON 07-10-2018, AND TO FIL... | $3,125 | -$3,125 | Sep 24, 2020 |
| Jun 28, 2020 | 35475283X | RESOLVE | CLASS - 2 | RESIDENTIAL CONVORTED MAINTAINED OR OCCUPIED AS A DWELLING FOR MORE THAN THE LEGALLY APPROVED NUMBER OF FAMILIES AUTH... | $0 | $0 | Feb 11, 2021 |
| Jun 28, 2020 | 35475284H | RESOLVE | CLASS - 1 | WORK WITHOUT PERMITS:WORK NOTED:AT BASEMENT LEVEL INSTALLED WATER&WASTE LINE FOR 2PC BATHROOM-TOILET-SHINK-& RESIDENT... | $0 | $0 | Jan 6, 2022 |
| Jun 25, 2020 | 39024512N | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Jan 14, 2021 |
| Jun 8, 2020 | 39023610M | ACTIVE | CLASS - 1 | CLASS 1, RETURN TO SERVICE FOR PROPER INSPECTION BY DOB. | $6,250 | $0 | Jul 23, 2020 |
| May 26, 2020 | 39022751L | ACTIVE | CLASS - 1 | CAT FIVE EXPIRED 10/15/2008.CAT ONE EXPIRED ON 9/24/2018.PIT DIRTY CLEAN. | $1,250 | $0 | Nov 19, 2020 |
| Apr 16, 2020 | 39021199M | RESOLVE | CLASS - 2 | HOT WATER COIL LEAK-NO FLAME GLASS AT BACK OF BOILER-RATING PLATE FOR STEAM BOILER NOT AFFIXED TO BOILER-BODY DRAIN N... | $312 | $0 | Oct 15, 2020 |
| Feb 12, 2020 | 39017425J | RESOLVE | CLASS - 2 | FRONT PLATE OF BOILER FOR HOT WATER LEAKING. NO RELIEF VALVE ON COLD WATER SIDE OF PIPING. NO BLOW DOWN FAILURE TO MA... | $625 | $0 | Jan 14, 2021 |