ECB violations
30-36 Hamilton Place, Manhattan • Block 02070 • Lot 0008
118 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 10, 2025 | 39163309H | RESOLVE | CLASS - 1 | CLASS 1 CEASE USE: CONTROLLER FUSE BYPASSED WHAT COMPROMISES OVERCURRENT PROTECTION. REMEDY: REMOVE VIOLATING CONDITI... | $1,250 | $0 | Dec 18, 2025 |
| Oct 9, 2025 | 39163270J | RESOLVE | CLASS - 2 | OBSERVED ON THE SIXTH FLOOR IN THE STAIRCASE, THE SPRINKLER SYSTEM LACKS PROPER SUPPORT .IN BASEMENT , THE GAS METER ... | $0 | $0 | Dec 18, 2025 |
| Nov 13, 2024 | 39130124K | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE... | $625 | $0 | Nov 13, 2025 |
| Jul 31, 2023 | 39091378L | RESOLVE | CLASS - 2 | FOUND REAR CHAMBER DOOR MISSING BOLTS AND LATCHES AND SIGHT GLASS. | $312 | $0 | Jul 17, 2025 |
| Apr 4, 2023 | 39082980J | RESOLVE | CLASS - 2 | I OBSERVED ON THE GROUND AN OCCUPIED OFFICE AREA WITH LIGHTING, POWER, EMERGENCY LIGHTING, ALSO NOTED IN THE ELECTRIC... | $0 | $0 | Jun 8, 2023 |
| Apr 4, 2023 | 39082982N | RESOLVE | CLASS - 1 | I OBSERVED THE INSTALLATION OF THE LIGHTING AND POWER FOR THE SIDEWALK SHED ,AS PER ELECTRIC CODE ALL TEMPORARY WIRIN... | $4,000 | $0 | Jun 8, 2023 |
| Apr 4, 2023 | 39082981L | RESOLVE | CLASS - 1 | I OBSERVED IN THE GROUND FLOOR OFFICE AREA THE ELECTRICAL SERVICE WITH NO GROUNDING CONNECTED TO THE SERVICE DISCONNE... | $12,000 | $0 | Jun 8, 2023 |
| Dec 30, 2021 | 35636707P | RESOLVE | CLASS - 2 | SEC. BC3307.6.4.8 PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECOFICATIONS-NO LIGHTS AT NIGHT. AT 5:40AM WHILE IT WAS ... | $2,400 | $0 | Mar 31, 2022 |
| Nov 15, 2021 | 39051235H | RESOLVE | CLASS - 2 | PHONE NOT WORKING | $1,562 | $0 | Mar 17, 2022 |
| Nov 1, 2021 | 35577945N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE/WALLS AND APPURTENANCES.NOTE:AT TIME OF INSPECTION OBSERVED AT EXP #1 EA... | $3,125 | $0 | Oct 22, 2026 |
| Sep 21, 2021 | 39047833X | RESOLVE | CLASS - 2 | WATER PIPING FROM COIL CORRODED AND LEAKING-LUGZ MISSING FROM FIRE DOOR AT BACK OF BOILER AND GASKET NOT PROPERLY SEA... | $0 | -$312 | Nov 18, 2021 |
| Sep 17, 2021 | 35589066P | RESOLVE | CLASS - 1 | FAILURE TO TAKE AND PROVIDE SAFETY MEASURES WHERE REQUIRED.AT TIME OF INSPECTION VIEW AT EXP #2 SOUTH ELEVATION CRACK... | $12,500 | $12,500 | Oct 8, 2026 |
| Aug 4, 2021 | 35588777R | RESOLVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY WITH COMMISSIONERS ORDER NOTE AT THE TIME OF MY INSEPCTION OBSERVED THAT RESPONDENT F... | $6,250 | $0 | Oct 21, 2021 |
| Aug 4, 2021 | 35588778Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS OR APPURTENANCES NOTE AT THE TIME OF MY INSPECTION OBSERVED VERTICAL CRAC... | $3,125 | $0 | Oct 21, 2021 |
| Jun 30, 2021 | 35559810R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING EXTEIROR WALL/FACADE AND APPURTENANCES AT THE TIME OF MY INSPECTION OBSERVED VERTICAL CR... | $6,250 | $0 | Feb 26, 2026 |
| Jun 30, 2021 | 35559809J | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE SAFETY MEASURES WHERE REQUIRED AT THE TIME OF MY INSEPCTION OBSERVED (DEFACED) CONDITIONAT THE EXT... | $10,000 | $0 | Feb 26, 2026 |
| May 15, 2021 | 35577676Y | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE SIDEWALK SHED WHERE REQUIRE. NOTE: AT THE TIME OF INSPECTION OBSERVED DEFECTED FACADE CRACK DETERI... | $0 | $0 | Mar 10, 2022 |
| May 15, 2021 | 35559924P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG EXTERIOR WALLS/FACADE & APPURTENANCES. NOTE: AT THE TIME OF INSPECTION VIEW EXP#1 EAST ELEVA... | $2,500 | $0 | Mar 10, 2022 |
| May 15, 2021 | 35577681Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMM'S ORDER TO FILE A CERT OF CORRECTION W/THE DEPT OF BLDGS. NOTE: AT THE TIME OF INSPECTION RE... | $1,250 | $0 | Mar 10, 2022 |
| Jan 29, 2021 | 35549518K | RESOLVE | CLASS - 1 | 1RCNY 103-04 OWNER FAILED TO MAKE NECESSARY REPAIRS IN TIME FRAME RECOMMENDED BY QEWI. AS NOTED A SWARMP REPORT WAS S... | $2,500 | $0 | Oct 7, 2021 |
| Feb 19, 2019 | 38268268P | RESOLVE | CLASS - 2 | 5B1,59B1. 5B1-ADJUST LARGE GAP BETWEEN THE TWO CAR DOORS. 59B1-BRAKE SHOE NEEDS TO BE ADJUSTED NO TENSION ON THE BRAK... | $0 | $0 | Apr 18, 2019 |
| Jun 4, 2018 | 35342484N | RESOLVE | CLASS - 2 | EC400.8 FLEXIBLE CORD USED AS PERMANENT WIRING. OBSERVED ALONG ROOFTOP THE INSTALLATION OF A RUBBER SJ TYPE CORD FROM... | $400 | $0 | Oct 11, 2018 |
| Jun 4, 2018 | 35342485P | RESOLVE | CLASS - 2 | FAILURE TO SECURE/SUPPORT ELECTRICAL METALLIC TUBING. OBSERVED IN ELECTRICAL DISTRIBUTION ROOM EMT CONDUITS LEANING W... | $250 | $0 | Oct 11, 2018 |
| Jun 4, 2018 | 35335432X | RESOLVE | CLASS - 3 | OBSERVED ROOF WATER PONDING IN SEVERAL LOCATIONS DUE TO THE LACK OF ROOF DRAINS. THE ROOF DRAINS ARE REQUIRED TO PREV... | $500 | $0 | Dec 6, 2018 |
| Jun 4, 2018 | 35335433H | RESOLVE | CLASS - 3 | OBSERVED @ EXP#1 OF BLDG THREE 90 DEDREE ELBOWS USED TO TERMINATE VENTS FOR GAS PRESSURE REGULATORS THAT ARE NOT EQUI... | $250 | $0 | Dec 6, 2018 |
| Jun 4, 2018 | 35342483L | RESOLVE | CLASS - 2 | EC 342.30 FAILURE TO PROPERLY SECURE/SUPPORT INTERMEDIATE CONDUIT (IMC) OBSERVED ON ROOF TOP ALONG PARAPET WALL IMC R... | $400 | $0 | Oct 11, 2018 |
| Mar 20, 2018 | 38261667K | RESOLVE | CLASS - 2 | 35B7,26I10,26I6,2X10. 26I11-TOP EMERGENCY EXIT COVER IS DAMAGED AND HAS NO MICROSWITCH,PROVIDE; 35B-EXPOSED ELECTRICA... | $625 | $0 | Sep 13, 2018 |
| Mar 19, 2018 | 35325482P | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED SUMMONS/VIOLATION #35290009M ISSUED ON 08/24/17 & TO FILE A CER... | $0 | $0 | May 29, 2018 |
| Feb 11, 2018 | 35284077N | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35281946M ISSUED ON 08/24/17 & TO FILE A C OF C PURSUAN... | $0 | $0 | May 8, 2018 |
| Dec 28, 2017 | 35281946M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35290009M ISSUED ON 08/24/17 AND TO FI... | $0 | $0 | May 8, 2018 |
| Dec 15, 2017 | 35297196Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 12/15/2017 @ ABOVE ADDRESS NO INSP TEST PRESSURE GAUGE... | $2,500 | $0 | Feb 1, 2018 |
| Nov 29, 2017 | 38259541M | RESOLVE | CLASS - 2 | 40P16)PROVIDE LADDER TO OVERHEAD WHEEL HOUSE. | $250 | $0 | Apr 19, 2018 |
| Nov 15, 2017 | 35280601M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35290009M ISSUED ON 08/24/17 & TO FILE A C OF C PURSUAN... | $0 | $0 | May 8, 2018 |
| Sep 27, 2017 | 35278799Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35290009M ISSUED ON 08/24/17 & TO FILE A C OF C PURSUAN... | $0 | $0 | May 8, 2018 |
| Aug 24, 2017 | 35290010J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: OBSERVED AT ROOF LEVEL,PARAPET WALL IS EXCESSIVELY TILTING AP... | $0 | $0 | May 8, 2018 |
| Aug 24, 2017 | 35290009M | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. NOTED: OBSERVED THAT CLADDING HAS BEEN INSTALLED THROUGHOUT THE ENTIRE EXTERIOR OF A POTENTIALLY H... | $0 | $0 | May 8, 2018 |
| Aug 24, 2017 | 35290011L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: OBSERVED AT STAIR'A'ROOF BULKHEAD,SPALLING PLASTER DUE TO W... | $500 | $0 | May 8, 2018 |
| Aug 11, 2016 | 37001083J | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 7TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS & APPUR... | $10,000 | $0 | Dec 29, 2016 |
| Oct 26, 2015 | 35133767M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG GENERAL NOTED:DECORATIVE MINI BALCONIES RUSTING,UNDERSIDE CRACKED-PARAPET & 3RD FL ... | $2,500 | $0 | Dec 24, 2015 |
| Oct 21, 2015 | 36023412M | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS: PERIODIC INSPECTION PF EXTERIOR WALLS... | $8,000 | $0 | Mar 3, 2016 |
| Jul 25, 2015 | 35129448N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. NOTE: AT BASEMENT LEVEL OF ABOVE PREMISES GAS METER ROOM IS BEING ... | $1,250 | $0 | Sep 17, 2015 |
| Jun 23, 2015 | 32075360Z | RESOLVE | CLASS - 2 | B254,6A,16,36,50,50A,50B,50C,50D. 50-POOR FLAME ON SHUT DOWN; 50A-CON DENSATE TANK VENT REDUCED AND NOT PIPED DOWN; 5... | $500 | $0 | Oct 15, 2015 |
| Jun 17, 2015 | 38236611R | RESOLVE | CLASS - 2 | 02X10,08V01,10D06,16D06,39X10,15M07,45D06,70Y02,71X10. 02X-2WAY COMMUNICATION INOPERABLE; 08V-LOBBY LANDING; 45D-SECU... | $500 | $0 | Aug 6, 2015 |
| Mar 9, 2015 | 35120344H | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.CO #49446 INDICATES LEGAL PENTHOUSE TO BE OCCUP... | $1,200 | $0 | Jul 16, 2015 |
| Mar 9, 2015 | 35120342Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: INCORRECT LABELING OF FLOOR LEVELS CONTRARY TO THE C OF O. ... | $0 | $0 | Jun 18, 2015 |
| Mar 9, 2015 | 35120341M | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. WORK NOTED: PENTHOUSE LEGAL 2 APTS NOW CREATED 5 APTS. REMEDY: OBTAIN PERMITS. | $800 | $0 | Jul 23, 2015 |
| Mar 9, 2015 | 35120343X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: BSMT LEVEL GAS METER ROOM NOT UP TO CODE: MISSING FIRE STOP... | $0 | $0 | Jun 18, 2015 |
| Mar 6, 2015 | 35115097N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION.I OBSERVED AT 12:20PM AT GROUND FLOOR IN... | $800 | $0 | May 28, 2015 |
| Mar 6, 2015 | 35115096L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF COR RECTION WITH THE DOB.I OBSERVED AT 12:20PM AT G... | $800 | $0 | May 28, 2015 |
| Sep 19, 2014 | 36019759J | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXT... | $4,000 | $0 | Jan 8, 2015 |