Skip to content

ECB violations

609-619 West 149 Street, Manhattan • Block 02096 • Lot 0017

75 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Mar 11, 2026 39180112Z ACTIVE CLASS - 1 OBSERVED ON THE 4TH FLOOR: IN APARTMENT 4F, GAS SHUTOFF VALVE BEHIND STOVE IS MISSING HANDLE. IN APARTMENT 4I, PIPE P... $2,500 $2,500 Jan 21, 2027
Mar 11, 2026 39180113K ACTIVE CLASS - 1 OBSERVED IN APARTMENT 6F, NO WATER SUPPLIED TO BATHROOM SINK. IN APTS 6D, SINK IS CRACKED WITH MISSING FAUCET HANDLES... $2,500 $2,500 Jan 21, 2027
Mar 11, 2026 39180812J ACTIVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... $800 $800 May 28, 2026
Mar 11, 2026 39180096H RESOLVE CLASS - 2 CLASS 2 ITEM: CALCULATE THE CORRECT CAR FULL LOAD CAPACITY TO PROPERLY ADJUST ALL FLOOR STOPS IN BOTH DIRECTIONS WITH... $0 $0 May 21, 2026
Mar 11, 2026 39180064N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED IN APT 6D THAT THE LIGHTS WAS NOT WORKING IN THE KITC... $2,500 $2,500 Jan 7, 2027
Mar 11, 2026 39180111R ACTIVE CLASS - 1 OBSERVED ON THE 6TH FLOOR: IN APARTMENT, 6F, A GAS LINE WAS INSTALLED TO SUPPLY A GAS DRYER. IN APARTMENT 6D WASTE PI... $2,500 $2,500 Jan 21, 2027
Mar 5, 2026 39179295M RESOLVE CLASS - 2 CLASS 2 ITEMS: PROVIDE TO INSTALL A PARTITION TO SEPARATE THE DRIVE MACHINE AND ROOM FROM THE HOISTWAY. PROVIDE AN UP... $0 $0 May 14, 2026
Mar 4, 2026 39179167H RESOLVE CLASS - 1 FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED IN MAIN ELECTRICAL RM THAT NO E... $4,800 $4,800 Jan 7, 2027
Mar 4, 2026 39179175H ACTIVE CLASS - 1 OBSERVED IN BASEMENT INSTALLED WASTE LINES FOR WASHING MACHINES ALL WORK COMPLETED100 NO PERMIT, OBTAIN PERMIT $2,500 $2,500 Dec 17, 2026
Mar 4, 2026 39179176J ACTIVE CLASS - 1 OBSERVED ON 7TH FLOOR APARTMENT 7C INSTALLED GAS LINES FOR GAS DRYER AND WASTE LINE FOR WASHING MACHINES ALL WORK COM... $2,500 $2,500 Dec 17, 2026
Mar 4, 2026 39179174X ACTIVE CLASS - 1 OBSERVED IN BASEMENT: CRACKED SEWER PIPING AND LEAKING FROM STEAM LINE ONTO THE FLOOR. SEWAGE BACK UP IN THE BACKYARD... $2,500 $2,500 Dec 17, 2026
Mar 4, 2026 39179173Y ACTIVE CLASS - 1 OBSERVED IN APARTMENT 7C A BUSHING IS BEING USED ON A GAS LINE, PVC INSTALLED ON THE WASHING MACHINE WASTE LINE AND U... $2,500 $2,500 Dec 17, 2026
Mar 4, 2026 39179169L RESOLVE CLASS - 1 ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN MAIN ELECTRICAL ROOM THE STORA... $1,200 $1,200 Jan 7, 2027
Mar 4, 2026 39179170Z RESOLVE CLASS - 1 ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN MAIN ELECTRICAL RM NEW ELECTRICAL DISTRIBUTION INSTALLED ALSO NEW RECEP... $2,500 $2,500 Jan 7, 2027
Mar 4, 2026 39179168J RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... $1,600 $1,600 Jan 7, 2027
Dec 22, 2025 39171123J RESOLVE CLASS - 1 5/L/10 CAR & GATE SWITCH DEFECTIVE REPAIR,55/H/12 DRUM COUNTERWEIGHTS WORN RESHACKLE. $1,250 $1,250 Feb 26, 2026
May 23, 2025 35693875P RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING FACADE AND APPURTENANCES. NOTE: AT THE TIME OF MY INSPECTION I OBSERVED AT EX 4 SOUTH EL... $0 $0 Jul 31, 2025
Jan 8, 2025 39134929X RESOLVE CLASS - 1 CLASS 1: CEASE USE: DOOR RESTRICTOR INOPERATIVE REPAIR (CU). IN CAR STOP SWITCH DAMAGED/INOPERATIVE REPAIR (CU). BRAK... $1,250 $0 Mar 20, 2025
Nov 20, 2024 39130797P RESOLVE CLASS - 1 CLASS 1: PLUNGER REMOVED FROM DOOR RESTRICTOR RENDERING IT INOPERATIVE INSTALL PLUNGER & CALL FOR RETEST (CU). CAR FL... $1,250 $0 Mar 20, 2025
Nov 4, 2024 39129414K ACTIVE CLASS - 2 OBSERVED ON THE THIRD FLOOR IN APARTMENT 3J GAS FLEXES HOSE RUNNING THREW CABINETS WHICH IS CONTRARY TO CODE SECTION ... $625 $0 Feb 6, 2025
Nov 4, 2024 39129413Z RESOLVE CLASS - 2 OBSERVED ON THE THIRD FLOOR IN APARTMENT 3J INSTALLED NEW GAS VALVE FOR STOVE ALL WORK COMPLETED NO PERMITS., OBTAIN ... $1,250 $1,225 Feb 6, 2025
Apr 14, 2023 39083878H RESOLVE CLASS - 2 AT THE TIME OF INSPECTION I OBSERVE LOOSE EXPOSED WIRES HANGING OUT THE CEILING AND SEVERAL OPEN GROUND IN APARTMENT ... $0 $0 Jun 22, 2023
Mar 2, 2023 39080591R RESOLVE CLASS - 2 ADJUST FLOOR STOPS. WORN SADDLE. REPAIR/REPALCE GOVERNOR/WHEELHOUSE DOOR. MACHINE ROOM DOOR HAS A COMPROMISED FIRE RA... $0 $0 May 11, 2023
Apr 12, 2022 39060092Y RESOLVE CLASS - 3 WORK WITHOUT A PERMIT. NOTED: APT 6H ERECTED FULL HEIGHT PARTITION WALL WITH DOOR TO CREATE BEDROOM., OBTAIN PERMIT O... $250 $0 Sep 8, 2022
Apr 5, 2022 39060091M RESOLVE CLASS - 3 OCCUPANCY CONTRARY. NOTED AT APT 6H CONVERTED LIVING RM TO ADDITIONAL BED ROOM WITH BED, CLOTHING AND PERSONAL ITEMS.... $0 $0 Jun 2, 2022
Mar 3, 2022 39057314N RESOLVE CLASS - 1 DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO FIREMANS SERVICE PRESENT IN CONTROLLER. INSTALL FIREMANS SERVICE SO DLM I... $312 $0 Sep 22, 2022
Jun 1, 2020 39023209X RESOLVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER MANDATED AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE NYCBC THIS... $1,250 $0 Feb 18, 2021
Nov 13, 2019 35365802L RESOLVE CLASS - 2 FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE & APPURTENANCES. NOTE: OBSERVED EXP 3 INTERIOR EXP, 6TH FLOOR WHITE BRIC... $620 $0 Jan 23, 2020
Jun 17, 2019 35365583K RESOLVE CLASS - 1 FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES NOTED AT THE TIME OF INSPECTION BUILDING FACADE OBSERV... $2,500 $0 Oct 24, 2019
May 12, 2018 35337770H RESOLVE CLASS - 2 FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION# 35326282P ISSUED ON 4/3/18 & TO FILE A ... $0 $0 Feb 14, 2019
Apr 3, 2018 35326282P RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NO FIRE STOPPINGAS PER BC712.2;27.345 AT CELLAR LEVLE,NUMEROUS ... $2,500 $0 Jul 26, 2018
Apr 3, 2018 35328935M RESOLVE CLASS - 2 28-301.1 MISC VIO FAILURE TO MAINTAIN BILBS @SIDEWALK SHED NOTED (1) LIGH BULBS NOT OPERATIONAL @TIME OF INSP.REM:COM... $0 $0 Jun 7, 2018
Apr 3, 2018 35326283R RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY NOTED AT REAR COURTYARD DIRE ESCAOE DISCHARGE(DROP LADDER)PARTIALLY O... $313 $0 Aug 2, 2018
Mar 26, 2018 35241871K RESOLVE CLASS - 2 OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O ¬ DOB'S RECORDS. WALL ERECTED ILLEGALLY CREATING A ROOM FOR SLEEPING. LO... $0 $0 May 31, 2018
Dec 27, 2017 38260354P RESOLVE CLASS - 2 2X10,8V1,11B7,21D6,26D6,37I10,42B1,52BB12,54M7,55B7,56Y13,58B10,59D6,61M7,68BB7,68B7,70B10. (2X)2WAY COMMUNICATION IN... $0 $0 Feb 15, 2018
Nov 7, 2016 37001481P RESOLVE CLASS - 2 FAILURE TO FILE ACCEPTABLE AMENDED REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL LOCAL LAW 1... $2,000 $0 Feb 23, 2017
Jun 7, 2016 35174467L RESOLVE CLASS - 1 FAILURE TO MAINTAIN EXTERIOR BLDG FACADE AND APPURTENANCES. AT TIME OFINSPECTION OBSERVED AT SOUTH, ELEVATION, EXP4 L... $1,000 $0 Jul 28, 2016
May 20, 2016 35159981Z RESOLVE CLASS - 1 FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN NOV# 35159601H ISSUED ON 3/7/16 & TO FILE A C OF C PURSUAN... $2,400 $0 Sep 22, 2016
Apr 28, 2016 35180710N RESOLVE CLASS - 1 WORK W/O PERMIT. AT TIME OF INSPECTION 11:15AM AT THE ABOVE ADDRESS AND TIME I OBSERVED IN THE MATERIAL/METER ROOM TH... $1,600 $0 Sep 22, 2016
Mar 17, 2016 35159600X RESOLVE CLASS - 1 ELECTRICAL WORK W/O A PERMIT. THE ENTIRE APTS 1B,7A,7E,6L,6J,5K HOUSE PANEL: SUB FEEDERS SUB PANELS,BRANCH CIRCUIT WI... $1,600 $0 Jul 21, 2016
Mar 17, 2016 35159601H RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. BASEMENT M... $8,000 $0 May 5, 2016
Mar 17, 2016 35159602J RESOLVE CLASS - 2 FAILURE TO PROVIDE ARC-FAULT CIRCUIT INTERRUPTER(AFCI)PROTECTION IN DWELLING UNITS. ENTIRE APT 7A BEDROOMS,LIVING ROO... $10,000 $0 May 5, 2016
Mar 10, 2016 35159032R RESOLVE CLASS - 2 ELECTRICAL WORK W/O A PERMIT.I OBSERVED THROUGHOUT THE BLDG NEW ELECTRICAL WORK BEING DONE,IN APT7A I OBSERVED NEW EL... $2,000 $0 Apr 28, 2016
Dec 3, 2015 35154347Z RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. THE NEW FLOORS IN KITCHEN,LIVING ROOM & BEDROOM ARE 5"INCH RAISED(... $500 $0 Feb 18, 2016
Sep 23, 2015 35159240L RESOLVE CLASS - 1 SEC. 240.24 LOCATION ON OR ON PREMISES. ACCESSIBILITY: OVER CURRENT DEVICES SHALL BE READILY ACCESSIBLE & SHALL BE IN... $800 $0 Apr 7, 2016
Sep 23, 2015 35159239Y RESOLVE CLASS - 1 FAILURE TO GROUND ELECTRICAL SYSTEMS. SERVICE GROUND CONDUCTOR: NO WATER MAIN GROUND PROVIDED. PLEASE NOTE-WATER MAIN... $4,800 $0 Apr 7, 2016
Dec 10, 2014 35101084R RESOLVE CLASS - 2 PARTIAL SWO ISSUED FOR SUSPENDED SCAFFOLD PURSUANT 28-207.2 AND POSTEDON PREMISES FAILED TO NOTIFY DEPT PRIOR HOUSE/I... $400 $0 Jan 29, 2015
Dec 10, 2014 35101085Z RESOLVE CLASS - 2 PARTIAL SWO ISSUED FOR SUSPENDED SCAFFOLD PURSUANT 28-207.2 AND POSTEDON PREMISES.WORK W/O PERMIT.NOTEDA:AT TIME OF I... $0 $0 Jan 29, 2015
Dec 10, 2014 35101086K RESOLVE CLASS - 2 PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATION. NOTED:AT TIME OF INSPECTION UNDERSIDE LIGHTS FOR SIDEWALK SHE... $0 $0 Jan 29, 2015
Oct 18, 2011 34915991R RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLAINT MANNER. DEFECTS NOTED: AT TIME OF INSPECTION THE CEILING IN THE 2ND ... $0 $0 May 10, 2012