Issued Violation Status Severity Description Penalty Balance due Hearing
Jun 10, 2021 39042588Z ACTIVE CLASS - 1 FOUND DLM IS NOT WORKING. NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2... $1,250 $0 Jul 29, 2021
Sep 9, 2020 39028346P ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $1,250 $0 Oct 29, 2020
Feb 1, 2017 38253056L RESOLVE CLASS - 2 02L10,41M10,70O02,59U15/02-6-10;REPAIR IN CAR PHONE-REPAIR MACHINE ROOM DOOR-CLEAN PA.PROVIDE BRAKE TAG. $500 $0 Mar 23, 2017
Jun 17, 2011 34902949K RESOLVE CLASS - 3 OCCUPANCY CONTRRY TO THAT ALLOWED BY THE COFO. NOTED:CELLAR OBSERVED TO BE OCCUPIED AS STORAGE FACILITY FOR 1ST FLR. ... $400 $0 Dec 13, 2012
Feb 23, 2010 38209305P RESOLVE CLASS - 2 97V10.52B14.53B14.98B5.99B5.64B7 97V B LEVEL SADDLE TO SADDLE NOT LEVEL 52B CWT TO SPRING MINIUM 6" 53B TENTION WEIGH... $500 $0 Apr 15, 2010
Jan 27, 2010 38208594X RESOLVE CLASS - 2 9H10.68M7.69M7.52H14.77K11.5K11.10M7.70O2.73O2.74O2.77O2 $1,250 -$1,250 Mar 18, 2010
Aug 21, 2009 38205826M RESOLVE CLASS - 2 08V1.21Q3.81M7 21Q3 INSTALL COVER FOR BSMT HOISTWAY DOOR INTERLOCK 39Q3 INSTALL GUARD FOR LIGHT ON TOP O FCAR 64M7 PR... $1,250 -$1,250 Oct 8, 2009
Aug 7, 2009 38205311N RESOLVE CLASS - 2 16B10.21B10.16,21 B-10 CHECK ALL DOORS PULL SWING DOO RAND ELEVATOR WILL STOP IN FLIGHT ALL ITEMS FROM PAST ECB'S STI... $500 $0 Sep 25, 2009
Jun 17, 2009 38203669Z RESOLVE CLASS - 2 100I10,21Q3,16B10,37M7,40B16,10D6,98BB5. 100I100 BASEMENT SADDLE DAMAGED 21Q3 DOOR LOCK COVER MISSING. 16B10 WHILE EL... $500 $0 Apr 8, 2010
May 26, 2009 38203145H RESOLVE CLASS - 2 52B14,78B14,16B10,32H10,37M7,20I11,21Q3,100I10,40M7,10D6,64M7,100R10. 52B- CWT TO SPRING SHORTEN. 78B- TENSION WEIGHT... $500 $0 Jul 16, 2009
Mar 11, 2009 32065799X RESOLVE CLASS - 2 18B.48B.50A.50B.15. 50A COMBUSTION GASES FROM DRAFT REGULATOR DUE TO CORRODED FLUE TEE CONNECTION 50B INSTALL GAUGE G... $0 $0 Dec 16, 2010
Feb 18, 2009 38201150N RESOLVE CLASS - 2 98BB5.99BB5.45I11.37T7.100I10.97V1.68M7.39O2.64M7.100I10.45I11 REPLACE GOV ROPE 37T7 SIGNAGE ON DOOR & LOCK 100I10 WH... $500 $0 Apr 9, 2009
Oct 28, 2008 38192267P RESOLVE CLASS - 2 16I11,21B07,44BB10,52K11,59Y02,38O02,08V01,100BB05,98BB05.16I11-REPLACE DAMAGED BASEMENT HATCH DOOR SADDLE.21B07-PROV... $1,250 -$1,250 Jan 28, 2010
Aug 27, 2007 32052363M ACTIVE Non-Hazardous B4A, 18A,B,44A,48B.NOTE: 44A NEED STEAM GAUGE 300 PSI CALIBRATED OR MORE. $2,500 $0 Oct 18, 2007
Jul 24, 2006 38160365M RESOLVE Non-Hazardous 08J01,16J01,25D06,66Z13-08-ADJUST 16-ADJUST 5TH FL & WHEREVER NECESSARY ELEVATOR STOPS WHEN DOOR IS PULLED 25-SECURE ... $0 $0 Sep 7, 2006
Jun 19, 2006 38159909N RESOLVE Non-Hazardous 8-V-1,40-T-7,59-B-7,63-U-15,39-O-02,38-O-02,66-O-02,84-O-02,84-W-07,84-T-07,84-D-06,34-D-06,43-H-08/08-V-01-ADJUST FL... $350 $0 Oct 5, 2006
Jan 27, 2006 32048269Y ACTIVE Hazardous B4B/3C/51/50/48B/44A/50A/18A/50B. B4B-#3C HAZARDOUS NB # 67678 FULTON HP BOILER. FUMES BACKING INTO BOILER ROOM FROM ... $400 $0 Nov 9, 2006
Apr 14, 2004 32044399Y ACTIVE Non-Hazardous CEASE USE.B4B,48A,48B,44C,3A,50A.51.FULTON V.T. BLR 15 HP,NB 67678,GAS-FIRED,1993,50A-SECONDARY BLOWDOWN VALVE NOT SC... $400 $0 Jun 3, 2004
Aug 19, 2003 34409169K RESOLVE Hazardous FAILURE TO MAINTAIN (EXTERIOR BLDG WALL)NOTED DEFECT:FACADE:CRACKED DETACHED BROKEN OPEN W/MISSING MORTAR FROM MASONA... $800 $0 Jul 8, 2004
Aug 21, 2001 32025962K ACTIVE Non-Hazardous 16-49-3A/REPLACE CORRODED SECTION OF THE PIPE BY NEW ONE. 2-PUT SECONDVALVE IN BLOW DOW AND WATER COLUMN DRAIN. 3 WAT... $2,500 $0 Oct 11, 2001
Aug 21, 2000 34257837R ACTIVE Non-Hazardous EXHAUST TERMINATES WITHIN 10FT OF RESIDENTIAL WINDOW OR DOOR. NOTED: REAR ALLEY WAY OF BUILDING EXHAUST FAN TERMINATE... $2,500 $0 Apr 5, 2001
Aug 11, 1997 38062322N RESOLVE Non-Hazardous 22D6,3M7,31Q7,23U16,74X11,5A12,17M12,8V1,62Q7,57O2,35P17,33P17. PROVIDE CAPACITY PLATE. TOP OF CAR. LIGHT TOP OF CAR.... $0 $0 Dec 18, 1997
Apr 28, 1997 38058196J RESOLVE Non-Hazardous 14M35I47H 35-DAMAGE MOTOR ROOM FLOOR NEED REPAIR $0 $0 Jul 10, 1997
Nov 9, 1993 38038110L RESOLVE Non-Hazardous 11Q,22D,74Q,74R,17I,33W,75U,35P,74X,73O,57Z. 74 PLANK SWITCH. 74 WORK LIGHT TOP CAR. 17 WITH WIRE GLASS. 74 HAVE ELEV... $100 $0 Aug 4, 1994
Jan 15, 1991 38005278Y RESOLVE Non-Hazardous 02L11, 17I12, 57O02, 14M07, 74I12, 73O02 74 SADDLE, IN CAR. $200 $0 Jul 3, 1997
Jan 3, 1990 32005144K ACTIVE Unknown FLUE PIPE CORRODED. HANDHOLES LEAKING. $150 $0 Feb 15, 1990