Maintenance code violations
534 West 187 Street, Manhattan • Block 02156 • Lot 0072
387 records
HPD grades a violation A for non-hazardous through C for immediately hazardous.
| Issued | Class | Status | Violation | Apartment | Correct by |
|---|---|---|---|---|---|
| Mar 26, 2018 | B | FIRST NO ACCESS TO RE- INSPECT VIOLATION | § 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE .. IN THE 1s... | 7 | Apr 30, 2018 |
| Mar 26, 2018 | B | VIOLATION CLOSED | § 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES OUTLET AT WEST WALL LOCAT... | 7 | Apr 30, 2018 |
| Mar 26, 2018 | C | VIOLATION CLOSED | § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING AT NORTH CLOSET, ... | 7 | Apr 3, 2018 |
| Mar 26, 2018 | B | VIOLATION CLOSED | § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT B-ROOM 7, 1st STORY, 1st B-ROOM FROM EAST ... | 7 | Apr 30, 2018 |
| Mar 26, 2018 | A | FIRST NO ACCESS TO RE- INSPECT VIOLATION | § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE BASE CABINET AT SINK IN THE KITCHENETTE LOCATED AT B-ROOM... | 7 | Jun 29, 2018 |
| Mar 26, 2018 | C | VIOLATION CLOSED | § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING IN THE KITCHENETT... | 7 | Apr 3, 2018 |
| Mar 26, 2018 | B | VIOLATION CLOSED | § 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES LOCATED AT B-ROOM 7, 1st STORY, 1st B-ROOM FROM EAST ... | 7 | Apr 30, 2018 |
| Mar 26, 2018 | B | VIOLATION CLOSED | § 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT B-ROOM 7, 1st STORY, 1... | 7 | Apr 30, 2018 |
| Mar 6, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE HEAVY DUTY LOCK AT DOOR ENTRANCE TO BUILDING AT PUBLIC HAL... | — | Mar 14, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE REPLACE WITH NEW THE MISSING WIRING GLASS (TOTAL 9 PANEL) AT SKYLIGHT | — | Mar 13, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE COPINGS (TOTAL 5) AT WEST PARAPET WA... | — | Mar 13, 2018 |
| Mar 5, 2018 | A | VIOLATION CLOSED | § 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND T... | — | Jun 8, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE BRICK AND MOTAR AT CHIMNEY , ROOF | — | Mar 13, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. MAKE STATIONARY THE IRON LADDER LEADING TO SCUTTLE OPENING IN ROOF ..... | — | Apr 9, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED WIRING AT... | — | Mar 13, 2018 |
| Mar 5, 2018 | A | VIOLATION CLOSED | § 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING R... | — | Jun 8, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CEMENT STUCCO EXTERIOR WALL AT DUMBW... | — | Mar 13, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY SECURE THE LOOSE BALUSTER(TOTAL 1) AT BALUSTRADE , AT PUBLIC HALL STAIRS, 1st STORY | — | Apr 9, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR AT PUBLIC HALL, 2nd STORY | — | Apr 9, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR AT PUBLIC HALL, 3rd STORY | — | Apr 9, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2050 ADM CODE PROVIDE 3 EXTRA SPRINKLER HEADS AND SUITABLE WRENCH FOR EMERGENCY PURPOSES AT O.S.Y. VALVE OF SPRI... | — | Apr 9, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY SECURE THE LOOSE BALUSTER (TOTAL 2) AT BALUSTRADE AT PUBLIC HALL STAIRS, 2nd STORY | — | Mar 13, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2050 ADM CODE SEAL IN OPEN POSITION THE O.S.Y. VALVE OF THE SPRINKLER SYSTEM IN ACCORDANCE WITH THE RULES AND RE... | — | Apr 9, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CEMENT STUCCO CHEEK WALL, FRONT WEST... | — | Mar 13, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED WIRING AT... | — | Mar 13, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE REPLACE WITH NEW THE MISSING VALVE AT SPRINKLER SUPPLY LINE , AT EAST CLOSET AT CELLAR | — | Mar 13, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED WIRING AT... | — | Mar 13, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE CERAMIC TILE AT WEST WALL, SOUTH WALL AT COMMUNITY BATHRO... | — | Apr 9, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE THE 1ST, 2ND , 3RD , 4TH , AND 5TH B... | — | Apr 9, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE CERAMIC TILE FLOOR AT PUBLIC HALL, 1st STORY | — | Mar 13, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY SECURE THE LOOSE LIGHT FIXTURE AT CEILING AT PUBLIC HALL, 1st STORY | — | Apr 9, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CONCRETE FLOOR AT PUBLIC HALL, 1st S... | — | Mar 13, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE CERAMIC TILE FLOOR AT VESTIBULE AT PUBLIC HALL, 1st STORY | — | Mar 13, 2018 |
| Mar 5, 2018 | B | VIOLATION CLOSED | § 27-2005, 2007 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS DOOR TO BASEMENT AT PUBLIC HALL, 1st STORY | — | Apr 9, 2018 |
| Mar 5, 2018 | A | VIOLATION CLOSED | § 27-2026 ADM CODE RESET, SO AS TO SECURE A PROPER AND TIGHT CONNECTION, THE WATER CLOSET BOWL .. AT COMMUNITY BATHRO... | — | Jun 8, 2018 |
| Mar 5, 2018 | C | VIOLATION CLOSED | § 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED WIRING AT... | — | Mar 13, 2018 |
| Feb 23, 2018 | B | FIRST NO ACCESS TO RE- INSPECT VIOLATION | § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE LOWER BASE CABINET IN THE KITCHEN LOCATED AT APT 7, 1st S... | 7 | Mar 30, 2018 |
| Feb 23, 2018 | B | VIOLATION CLOSED | § 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 7, 1st STORY, 1st... | 7 | Mar 30, 2018 |
| Feb 23, 2018 | B | VIOLATION CLOSED | § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE CERAMIC TILE AT THE WEST WALL IN THE BATHROOM LOCATED AT ... | 7 | Mar 30, 2018 |
| Feb 23, 2018 | B | VIOLATION DISMISSED | § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE SOUTH WALL IN T... | 7 | Mar 30, 2018 |
| Feb 23, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT THE SKYLIGHT IN THE KITCHEN LOCATED AT APT 2, 3rd STOR... | 2 | Mar 3, 2018 |
| Feb 23, 2018 | B | VIOLATION CLOSED | § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE ... | 2 | Mar 30, 2018 |
| Feb 23, 2018 | C | VIOLATION CLOSED | § 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING HASP WITH PADLOCK CAPABILITY IN THE ENTRANCE LOCATED AT APT 2, ... | 2 | Mar 3, 2018 |
| Feb 23, 2018 | A | VIOLATION CLOSED | § 27-2027 ADM CODE REPAIR THE BROKEN OR DEFECTIVE RAIN LEADER AT THE REAR YARD 1st YARD FROM EAST | — | May 29, 2018 |
| Feb 23, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE LOOSE BRICKS AND MORTAR AT 3RD STORY... | — | Mar 3, 2018 |
| Feb 23, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE 3 GLASS PANE AT THE SKYLIGHT AT PUBLIC HALL, 3rd STORY | — | Mar 3, 2018 |
| Feb 23, 2018 | C | VIOLATION CLOSED | § 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT THE STOVE IN THE KITCHEN LOCATED AT APT 7, 1s... | 7 | Mar 3, 2018 |
| Feb 23, 2018 | C | VIOLATION CLOSED | § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING AT CELLAR | — | Mar 3, 2018 |
| Feb 23, 2018 | C | VIOLATION CLOSED | § 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT THE STOVE IN THE KITCHEN LOCATED AT APT 2, 3r... | 2 | Mar 3, 2018 |
| Feb 23, 2018 | C | VIOLATION CLOSED | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE UNKEYED PLASTER AT THE CEILING AND S... | — | Mar 3, 2018 |