Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jun 13, 2014 35099845M ACTIVE CLASS - 2 RE-ISSUE # 34987444K. WATER PENETRATION. AT CELLAR BOILER ROOM BEHIND BOILERS, THE FOUNDATION & FLOOR SLAB HAVE BECOM... $0 $0 Aug 28, 2014
Jun 13, 2014 35099848H RESOLVE CLASS - 2 27-371(B). PLEXI VISION PANELS. THERMOPLASTIC VISION PANELS INSTALLED AT 2C,4A,3B,2B,2C & 1C. REMEDY: REPLACE WITH CO... $0 $0 Aug 28, 2014
Jun 13, 2014 35099849J RESOLVE CLASS - 2 MISSING EMEGENCY SIGN. AT ALL FLOORS, NO EMERGENCY SIGNS AT ELEVATOR CALL STATIONS. REMEDY: PROVIDE SIGNS WITH DIAGRA... $0 $0 Aug 28, 2014
Jun 13, 2014 35099846Y RESOLVE CLASS - 2 EXIT DOORS NOT SELF CLOSING. AT 4B,3A,2B,2C,2A, & GYM, DOORS ARE RACKED TO FRAME WITH BROKEN TOP HINGE & NOT CLOSING.... $0 $0 Aug 28, 2014
Jun 13, 2014 35099976M RESOLVE CLASS - 2 DEFECTIVE EXTERIOR LIGHTING. AT ROOF LEFT & RIGHT, 4 AREA LIGHTING FIXTURES ARE LOOSE WITH DEFECTIVE POWER CORDS & EX... $0 $0 Aug 28, 2014
Mar 4, 2013 34987444K ACTIVE CLASS - 2 REISSUE: 349092104 - THE FOUNDATION WALL HAS BECOME POROUS AND ALLOWING RAIN WATER INTO THE BOILER ROOM CAUSING INTER... $0 $0 Apr 18, 2013
Mar 4, 2013 34987441P RESOLVE CLASS - 2 GYMNASIUM EXIT PASSAGEWAY IS PARTIALLY OBSTRUCTED BY GYM EQUIPMENT & CHAIRS ON THE 2ND FLOOR LEVEL. REMEDY: REMOVE AN... $0 $0 Apr 18, 2013
Mar 4, 2013 34987443Z RESOLVE CLASS - 2 REISSUE: 34909207N THE CEILING IS SPALLNG LOCATED AT STAIRWAY B&C 5TH FLOOR LEVEL ADJACENT TO THE SKYLIGHT. REMEDY: R... $0 $0 Apr 18, 2013
Mar 4, 2013 34987442R RESOLVE CLASS - 2 REISSUE: 34862101J EXTERIOR BRICK FACADE HAS BECOME POROUS AND ALLOWING RAIN INTO ROOM 428 (4TH FLOOR) CAUSING INTERI... $0 $0 Apr 18, 2013
Jun 19, 2012 34982049H RESOLVE CLASS - 2 2ND FLOOR GYM 7 METAL VENT COVERS ARE HANGING FROM CEILING VENTS W/CHAIN. REMEDY: REPAIR/REPLACE VENT COVERS. $0 $0 Sep 20, 2012
Jun 19, 2012 34982048X RESOLVE CLASS - 2 4TH FLOOR STWY "A & B" DOORS ARE RACKED. 3RD FLOOR STWY 'A' DOOR RACKED. 2ND FLOOR STWY "A,B & C" DOORS ARE RACKED. G... $0 $0 Sep 20, 2012
Jun 19, 2012 34982044Z RESOLVE CLASS - 2 SEC. 27-369 REISSUE: 34909208P COMBUSTIBLE MATERIAL IN CORRIDORS AT 3,4,5 FLOORS,BOOK CASES W/BOOKS FURNITURE ETC. RE... $0 $0 Sep 20, 2012
Jun 19, 2012 34982043R RESOLVE CLASS - 2 REISSUE: 34909206L AT 3,4,5 FLOORS ADJACENT TO ELEVATOR THE CORRIDORS SET UP AS CLASS ROOMS W/TABLES,CHAIRS,BOOK CASE... $0 $0 Sep 20, 2012
Jun 19, 2012 34982047Y RESOLVE CLASS - 2 SEC. 27-369 REISSUE: 34909205J VARIOUS CLASS ROOMS W/2 EXIT DOORS HAVE1 OF THE 2 DOORS PARTIALLY BLOCKED W/CABINETS,R... $0 $0 Sep 20, 2012
Jun 19, 2012 34982046M RESOLVE CLASS - 2 SEC. 27-766 REISSUE: 34909201M GAS METER ROOM AT CELLAR LEVEL HAS NO FRESH AIR VENT. REMEDY: PROVIDE FRESH AIR VENTIL... $0 $0 Sep 20, 2012
Jun 19, 2012 34982045K RESOLVE CLASS - 3 REISSUE: 34909200K 3RD FLOOR MECHANICAL ROOM ADJACENT TO ROOM 324 & GAS METER & ELECTRICAL ROOMS AT CELLAR LEVEL ARE ... $0 $0 Sep 20, 2012
May 11, 2011 34909210Y RESOLVE CLASS - 2 WATER PENETRATION.@ CELLAR BOILER ROOM BEHIND BOILERS,THE EXTERIOR FOUNDATION & FLR SLAB HAVE BECOME POROUS ALLOWING ... $0 $0 Jun 16, 2011
May 11, 2011 34909203X RESOLVE CLASS - 2 REISSUE#34862100H.DEFECTIVE PLASTER.@ 4 FLR ROOM 428,THE PLASTER IS SPLALLING & CRUMBLING ON THE EXTERIOR WALL.REM:RE... $0 $0 Jun 16, 2011
May 11, 2011 34909207N RESOLVE CLASS - 2 DEFECTIVE PLASTER.@ 5 FLR BULKHEAD STAIRWAY B,C SPALLING & CRUMBLING PLASTER @ SKYLIGHTS.REM:REPAIR PLASTER SURFACE. $0 $0 Jun 16, 2011
May 11, 2011 34909204H RESOLVE CLASS - 2 DEFECTIVE DOORS.THE FIRE PROOF SELF CLOSING DOORS ARE RACKED TO FRAME & JAM @ STAIRWAY C(1 &4 FLR),STAIRWAY A(2 FLR),... $0 $0 Jun 16, 2011
May 11, 2011 34909208P RESOLVE CLASS - 2 NON COMPLIANT STORAGE.@ CELLAR LEVEL AUDITORIUM EXIT 2 ,3,4,5 FLR CORRIDORS W/ VARIOUS COMBUSTIBLE ITEMS IE:FURNITURE... $0 $0 Jun 16, 2011
May 11, 2011 34909201M RESOLVE CLASS - 2 27-766)REISSUE#34862172R.NO GAS METER ROOM VENT.@ CELLAR LEVEL,GAS METER ROOM HAS NO FRESH AIR VENT OR MECHANICAL VEN... $0 $0 Jun 16, 2011
May 11, 2011 34909206L RESOLVE CLASS - 2 OCCUPANCY CONTRARY @ 3,4,5, FLRS ADJACENT TO ELEVATOR,CORRIDOR SET UP FOR STUDENT INSTRUCTION W/ TABLES,CHAIRS,BOOK C... $0 $0 Jun 16, 2011
May 11, 2011 34909205J RESOLVE CLASS - 2 OBSTRUCTED DOORS THROUGH OUT,CLASS ROOMS HAVE 1 OF 2 DOORS OBSTRUCTED W/ FILE CABINETS,ROLLING CARTS,BOOK CASES,SCHOO... $0 $0 Jun 16, 2011
May 11, 2011 34909209R RESOLVE CLASS - 2 DEFECTIVE CONCRETE STEPS.@ WEST 196 ST ENTRY,THE CONCRETE ENTRANCE STEPS ARE CHIPPED & CRUMBLING W/ PIECES MISSING.RE... $0 $0 Jun 16, 2011
May 11, 2011 34909202Y RESOLVE CLASS - 2 REISSUE#34862101J.MOISTURE PENETRATION.@ 4 FLR ROOM 428,THE EXTERIOR WALL HAS BECOME POROUS ALLOWING MOISTURE TO PENE... $0 $0 Jun 16, 2011
May 11, 2011 34909200K RESOLVE CLASS - 3 REISSUE#34862173Z.NON COMPLIANT STORAGE.@ 3 FLR MECHANICAL ROOM ADJACENT TO ROOM 324,STORAGE OF SCHOOL SUPPLIES,FILES... $0 $0 Jun 16, 2011
Jul 21, 2010 34862174K RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER NOTED:EXIT SIGN THROUGHOUT, SCHOOL VARIOUS AREAS ARE DAMAGE OR MISS... $0 $0 Sep 16, 2010
Jul 21, 2010 34862173Z RESOLVE CLASS - 3 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NOTED:REISSUE NOV 34646181M, 34777309M STORAGE IN 3RD FLR MECHANICA... $0 $0 Sep 16, 2010
Jul 21, 2010 34862101J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALLS AND APPURTENANCES NOTED WATER PENETRATIION THROUGH WALL INTO ROOM 428 REM: MAINTAIN BLDG $0 $0 Sep 16, 2010
Jul 21, 2010 34862172R RESOLVE CLASS - 3 FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER.NOTED:REISSUE NOV 34646181M, 34777310J, 34607986H.NO FRESH AIR VENT... $0 $0 Sep 16, 2010
Jul 21, 2010 34862100H RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NOTED SPALDING PLASTER DISLODGE PLASTER IN ROOM 428 REM; MAINTAIN BLDG $0 $0 Sep 16, 2010
May 13, 2009 34777310J RESOLVE CLASS - 3 REISSUE 34646181M GAS METER RM HAS NO FRESH AIR VENT CELLAR LEVEL $0 $0 Aug 13, 2009
May 13, 2009 34777309M RESOLVE CLASS - 3 REISSUE 34646182Y ELECTRICAL RM NEAR RM 324 USED FOR STORAGE, BOOKS, CHAIRS, SCHOOL SUPPLIES REMEDY:KEEP RM CLEAR REM... $0 $0 Aug 13, 2009
May 13, 2009 34777311L RESOLVE CLASS - 3 FAILURE TO MAINTAIN AT FLS 5,4,3,2 CELLAR SOUTH CORRIDORS USED FOR STORAGE OF DESKS CHAIRS, BOOKS, COPIERS, ESPECIALL... $0 $0 Aug 13, 2009
May 13, 2009 34777313P RESOLVE CLASS - 3 FAILURE TO MAINTAIN FIRE DOORS 3 FL STAIR A AND CELLAR STAIR C NOT PROPERLY CLOSING REMAIN PARTIALLY OPEN.REMEDY:REPA... $0 $0 Aug 13, 2009
May 13, 2009 34777312N RESOLVE CLASS - 3 FAILURE TO MAINTAIN IN LIBRARY BOTH EXIT SIGNS UNLIT ONE SIGN MISSING EXIT COVER REMEDY:MAINTAIN AND REPAIR EXIT SIGNS $0 $0 Aug 13, 2009
Jun 5, 2008 34646181M RESOLVE Non-Hazardous REISSUE: 34607986H GAS METER ROOM DOES NOT HAVE ANY FRESH AIR VENTILATION ON CELLAR LEVEL. $0 $0 Aug 28, 2008
Jun 5, 2008 34646182Y RESOLVE Non-Hazardous 3RD FLR ELECTRICAL ROOM IS BEING USED AS A STORAGE ROOM CONSISTING OF CHAIRS, SCHOOL FURNITURE, BOOKS, ADJACENT TO RO... $0 $0 Aug 28, 2008
Sep 19, 2007 34607987J RESOLVE Non-Hazardous FAILURE TO MAINTAIN INTERIOR 1ST FL STAIRWAY E FRONT AUDITORIUM LEFT OF STAGE STAIRRAIL LOOSE & FALLING OFF WALL REME... $0 $0 Nov 15, 2007
Sep 19, 2007 34607986H RESOLVE Non-Hazardous FAILURE TO MAINTAIN-INTERIOR GAS METER ROOM NO FRESH AIR VEN.REMEDY SUPPLY FRESH AIR VENT $0 $0 Nov 15, 2007
May 26, 2006 34526573P RESOLVE Hazardous FAILURE TO MAINTAIN BLDG-INTERIOR SAFTEY RAILING ON THE 1ST FL OF THE AUDITORIUM IN BACK, VERY LOOSE & READY TO BREAK... $0 $0 Aug 17, 2006
May 26, 2006 34526900N RESOLVE Hazardous FAILURE TO MAINTAIN BLDG-INTERIOR 5TH FL STAIRWAY A SKY LIGHT LEAKS ONTO MECHANICAL FL LANDING REMEDY:REPAIR LEAK $0 $0 Aug 17, 2006
May 26, 2006 34526574R RESOLVE Hazardous FAILURE TO MAINTAIN BLDG-INTERIOR 5TH FL STAIR C DOOR CLOSER BROKEN REMEDY:REPAIR DOOR CLOSER $0 $0 Aug 17, 2006
Jun 8, 2005 32048083X RESOLVE Non-Hazardous 50A/29C/50B 50A THE SAFETY VALUES DISCHARGE MUST BE PIPED INDIVIDUALLYTO A SAFE POINT 50B THE RIGHT SIDE MUD LEG S CL... $0 $0 Jul 28, 2005
Jun 8, 2005 32048082Y RESOLVE Non-Hazardous 50A/50B 50A THE SAFETY VALUES DISCHARGE MUST BE PIPED INDIVIDUALLY TO A SAFE POINT 50B THE MANHOLE IS LEAKING STEAM $0 $0 Jul 28, 2005
Jun 8, 2005 32048084H RESOLVE Non-Hazardous 50A 50A THE SAFETY VALUES DISCHARGED MUST BE PIPED FULL SIZE INDIVIDUALLY TO A SAFE POINT $0 $0 Jul 28, 2005
Feb 25, 2005 34466956K RESOLVE Non-Hazardous NOTED: ROOF OF ELEVATOR MACHINE ROOM AT ROOF LEAKING INTO CONTROL AND MOTOR ROOM- LEAKAGE AROUND ROOF HATCH. REMEDY: ... $0 $0 Apr 21, 2005
Feb 25, 2005 34466957M RESOLVE Non-Hazardous NOTED: FIFTH FLOOR BOYS AND GIRLS BATHROOMS (#506 AND 526) MISSING WALL MOUNTED EXHAUST LOUVER COVERS WITHIN H.C. BAT... $0 $0 Apr 21, 2005
Feb 25, 2005 34466958Y RESOLVE Non-Hazardous NOTED: GYMNASIUM (P.A. CAP 360) EXIT "H" RIGHT HAND DOOR SET RIGHT HAND LEAF DOOR PANIC HARDWARE INOPERATIVE. REMEDY:... $0 $0 Apr 21, 2005