ECB violations
578-590 Fort Washington Avenue, Manhattan • Block 02180 • Lot 0039
35 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 27, 2023 | 39089239Z | ACTIVE | CLASS - 2 | FOUND WATER LEAKING OUT OF REAR CHAMBER DOOR, BOLTS AND LATCHES MISSING ON BOILER DOORS, OIL BURNER NEEDS SERVICING A... | $312 | -$312 | Aug 31, 2023 |
| Jan 8, 2018 | 35274518K | ACTIVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS ,DEVICES,APPLIANCES OR WIRING IN USE.APT #27:OP... | $400 | $0 | Jul 5, 2018 |
| Jan 8, 2018 | 35274519M | RESOLVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT.THE ENTIRE BUILDING HALLWAYS:REFLECTING FLOURSCENT LIGHTING FIXTURES.THIS IS NOT A F... | $400 | $0 | Jul 5, 2018 |
| Dec 23, 2015 | 35142184P | RESOLVE | CLASS - 1 | WORK W/O A PERMIT.INSTALLATION SPRINKLER SYSTEM.TIME OF INSPECTION 1120AM.ON 12/23/15 I OBSERVED A NEW AUTOMATIC SPRI... | $1,600 | $0 | Mar 24, 2016 |
| Nov 5, 2015 | 38239220N | RESOLVE | CLASS - 2 | 20I11,70M07,70O02.12Q03. 20I11-VISION PANEL BROKEN REPLACE; 70M02-PIT MISSING LADDER PROVIDE;70O02-PIT DIRTY CLEAN; 2... | $2,500 | $0 | Dec 24, 2015 |
| Jul 21, 2015 | 35115909J | ACTIVE | CLASS - 2 | BC 903.2.10.6. FAILURE TO PROVIDE SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED. AT 3:00PM FOUND THAT ADDRESS ABOVE H... | $800 | $0 | Mar 31, 2016 |
| Jan 29, 2015 | 35122893J | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIAL, DEVICES, APPLIANCES OR WIRING IN USE. THE ENT... | $1,600 | $0 | May 7, 2015 |
| Jan 29, 2015 | 35122892H | RESOLVE | CLASS - 2 | FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS. BASEMENT SERVICE EQUIPMENT: ONE OF THE SERVICE SWITCH NEUTRAL BAR NOT BO... | $750 | $0 | May 7, 2015 |
| Jan 29, 2015 | 35122891X | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. BASEMENT SERVICE EQUIPMENT: NO WATER MAIN GROUND PROVIDED FOR THE TWO SERVICE S... | $4,800 | $0 | May 7, 2015 |
| Jan 15, 2015 | 35041663J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER TO FILE C OF C W/THE DOB'S FOR NOTICE OF VIO #35111487K ISSUED ON 11/9/14 PURSUA... | $800 | $0 | Jun 18, 2015 |
| Nov 10, 2014 | 35117556M | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS AND PROPERTY AFFECTED BY CONSTRUCTIONOPERATIONS . | $0 | $0 | Jan 8, 2015 |
| Nov 9, 2014 | 35111487K | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN IN A CODE COMPLIANT MANNER.NOTED:@ CELLAR LEVEL IN A FEW DIFFERENT LOCATIONS (METER & POWER AREA)... | $1,000 | $0 | Mar 26, 2015 |
| Apr 10, 2012 | 35049989X | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOTICE OF VIOLATION #34947553N ISSUED ON 2/9/12. NOTED: FLO... | $0 | $0 | Sep 6, 2012 |
| Apr 10, 2012 | 34973678X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMS ORDER TO FILE A CERT OF CORRECTION W/ THE DOB FOR NOV#34947553N ISSUED ON 2/9/12 PURSU... | $800 | $0 | Sep 6, 2012 |
| Apr 10, 2012 | 34950014L | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/ THE COMMS ORDER CONTAINED IN NOV#34947553N ISSUED ON 2/9/12.NOTED:FLOOR TO CLG CRACKS,SOME UP TO... | $0 | $0 | May 31, 2012 |
| Apr 10, 2012 | 34971630H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMS ORDER TO FILE A CERT OF CORRECTION W/ DOB FOR NOV#34947553N ISSUED ON 02/09/12 PURSUAN... | $0 | $0 | May 31, 2012 |
| Feb 9, 2012 | 34947553N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER NOTED DEFECTS AT INTERIOR HALLWAY IN FRONT OF C APT & N APT AT 2 ... | $1,000 | $0 | Mar 29, 2012 |
| Jun 22, 2005 | 38152944R | RESOLVE | Non-Hazardous | 51H11/43H10/84L10/85M07 84-L-10 REPAIR INTERCOM SYSTEM TO WORK PROPERLY | $350 | $0 | Dec 8, 2005 |
| Jun 16, 2003 | 38139679Z | RESOLVE | Non-Hazardous | 3M7,10H12,16L1,20Q3 3MT=CAPACITY PLATE 16L1=ADJUST CHECK 4TH F. 20Q3=CAR | $0 | $0 | Jul 31, 2003 |
| May 13, 2003 | 34381694R | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY 10111 IN THAT AN APARTMENT HAS BEEN CREATED AT BASEMEN... | $0 | $0 | Mar 25, 2004 |
| Apr 21, 2003 | 38136728M | RESOLVE | Non-Hazardous | 37I11/ 34D06/ 37/I - LARGE HOLE IN MOTOR RM FLOOR 34/D - PROPERLY SECURE OVERHEAD GRATING | $0 | $0 | Jun 5, 2003 |
| Nov 8, 2002 | 38125495R | RESOLVE | Non-Hazardous | (5)J11/ (11)X11/ (15)L11/ (22)L6/ (23)U16/ (33)O2/ 50Y14/ (75)U55J11 = TOO MUCH GAP BETWEEN CAR DOOR AND CAR POST 11X... | $440 | $0 | Dec 26, 2002 |
| Oct 31, 2002 | 38124998Y | RESOLVE | Non-Hazardous | 9H08-51F11. 39-REGROOVE MACHINE SHEAVE 51-REPAIR WORM WORM AND GEARS. | $350 | $0 | Jul 24, 2003 |
| Jul 8, 2002 | 38124216K | RESOLVE | Non-Hazardous | 11X11/ 15L11/ 22L6/ 23U16/ 15E11/ 33O2/ 5J11/ 37G12/ 37T16/ 975)U5/ 15L11 = SLAMS B TO 5 FLS 11X11 = CAR TOP 22L6 = S... | $880 | $0 | Nov 14, 2002 |
| Apr 5, 2002 | 38122519Z | RESOLVE | Non-Hazardous | 50F11/ 31Q07/ 13D01/ <<< SECOND OFFENSE 38L11/ 17M07/ 75B05/ 50 - ELIMINATE EXCESSIVE LOST MOTION IN MACHINE GEARING ... | $880 | $0 | May 23, 2002 |
| Dec 13, 2001 | 38120164J | RESOLVE | Non-Hazardous | 57O2/ 50F11/ 47H12/ 33O2/ 50Y14/ | $350 | $0 | Jan 31, 2002 |
| Jul 23, 2001 | 34299928H | RESOLVE | Hazardous | FAILURE TO MAINTAIN DEFECT NOTED: SECTIONS OF THE UNDERSIDE OF THE EXTENDED REAR YARD ELEVATED CONCRETE FLOOR ARE MIS... | $800 | $0 | Jan 31, 2002 |
| Dec 13, 2000 | 38108604M | RESOLVE | Non-Hazardous | 37G12-09B11-31Q07 13D01 - CONTROLLER OVERFUSED ALL FUSE BLOCKS, BEND FIRE GIBB & PROVIDE SECOND DOOR GIBB, THROUGHOUT... | $350 | $0 | Mar 1, 2001 |
| Aug 2, 2000 | 38106969X | RESOLVE | Non-Hazardous | 03D11/28F11/50F11/03B07/74B07 - 07 REPAIR CAR FAN 28 SECURE CAR SHOES 50 ELEIMINATE EXCESSIVE LOST MOTION IN GEARING ... | $0 | $0 | Sep 21, 2000 |
| Aug 1, 2000 | 32018520H | RESOLVE | Non-Hazardous | 49A/49B -(49A) OIL LEAKING AT PUMP. (49B) INSTALL A TEMPERTURE COIL RELEIF VALUE ON DOMESTIC | $0 | $0 | Sep 21, 2000 |
| Jul 31, 1998 | 38077608K | RESOLVE | Non-Hazardous | 46-#15-. HOIST CABLES NEED SHORTING. | $0 | $0 | Sep 24, 1998 |
| Apr 1, 1992 | 38023978Y | RESOLVE | Non-Hazardous | 11R,03#,35I,53X,57O,35O,30O, 03#-12: CAR ENCLOSURE CEILING ILLEGAL REMOVE AND REPLACE. 35-I-12: OVER HEAD MACHINE ROO... | $150 | $0 | May 14, 1992 |
| Jul 13, 1988 | 34010953J | RESOLVE | Non-Hazardous | FALIURE TO MAINTAIN: FIRE DAMAGE 6TH FLOOR APT 6E KITCHEN FIRE RATING OF CEILING. REMEDY; MAKE ALL NECESSARY REPAIRS ... | $1,000 | $0 | Sep 1, 1988 |
| Jul 13, 1988 | 34010954L | RESOLVE | Non-Hazardous | FALIURE TO MAINTAIN. REINFORCED CONCRETE WLAKWAY CRACKED, BROKEN AND DEFECTIVE. REMEDY: OBTAIN A PERMIT AND APPROVALS... | $250 | $0 | Dec 22, 1988 |
| Jun 1, 1988 | 34007529N | RESOLVE | Hazardous | FAILURE TO MAINTAIN: EXTERIOR. REMEDY: OBTAIN A PERMIT AND APPROVALS FROM THIS DEPARTMENT. | $1,000 | $0 | Sep 1, 1988 |