ECB violations
40-48 Overlook Terrace, Manhattan • Block 02180 • Lot 0178
33 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 29, 2021 | 39040320Z | RESOLVE | CLASS - 2 | FOUND TO HAVE CORRODED COIL PLATE, AND CORRODED MANHOLE, GLASS GAUGE GUARDS MISSING, DISCHARGE PIPE ON RELIEF VALVE N... | $0 | $0 | Jun 17, 2021 |
| Oct 22, 2015 | 35046404H | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN NOV #35153455L ISSUED ON 12/18/14 AND TO FILE A CERTIFIC... | $800 | $0 | Dec 10, 2015 |
| Sep 12, 2015 | 35045212Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35153455L ISSUED ON 12/18/14 & TO FILE A C OF C PURSUANT TO 28... | $2,400 | $0 | Oct 29, 2015 |
| Dec 18, 2014 | 35153455L | RESOLVE | CLASS - 1 | WORK W/O PERMIT. WORK NOTED: NEW CONCRETE PEDESTRIAN (ADA) RAMP INSTALLED AT REAR/SIDE YARD APPROX 48FEET LONG W/LAND... | $1,600 | $0 | Feb 5, 2015 |
| Dec 1, 2011 | 34937707H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT IS VERTICAL AND STEPCRACKS AT VARIOUS LOCATIONS OF C LINE APT EXTER... | $2,500 | $0 | May 24, 2012 |
| Nov 19, 2009 | 34816851L | RESOLVE | CLASS - 1 | FAIL TO MAINTAIN EXTERIOR BLDG WALL. DEFECT IS: EXTERIOR BRICK WALLS & FOUNDATION WALLS OF H LINE APTS HAVE LARGE VER... | $5,000 | $0 | Jan 14, 2010 |
| Sep 17, 2009 | 38206160J | RESOLVE | CLASS - 2 | 32H10 TOP AND BOTTOM CAR GUIDE SHOES ARE WORN 08V10 ADJUST FLSTOPS WERE NEEDED | $250 | $0 | Nov 12, 2009 |
| Sep 11, 2009 | 38205746M | RESOLVE | CLASS - 2 | 97V10,41W06,32H10,05B10.97V10-LEVEL ALL FLOORS SADDLE TO SADDLE.41W06-LOCK M/R DOOR.32H10-GUIDE SHOES(ROCK (L) TO (R)... | $250 | $0 | Oct 29, 2009 |
| Jul 31, 2009 | 34744350N | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE SIDEWALK SHED WHERE REQUIRED. HAZARDOUS FACADE CONDTION WAS FOUND AT WEST OF NORTH ELEVN WHICH WAS... | $0 | $0 | Oct 15, 2009 |
| Jul 8, 2009 | 34789553M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES. DEFECT NOTED: NORTH WEST PART OF BUILDING HAS CRACKED (APPR 2" W... | $1,000 | $0 | Aug 27, 2009 |
| Dec 10, 2008 | 34744152M | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE SIDEWALK SHED AND SAFETY MEASURES ON THE NORTH ELEVATION WHERE SECTION OF THE PARAPET HAD BROKEN O... | $0 | $0 | Jan 29, 2009 |
| Nov 21, 2008 | 38193299Y | RESOLVE | CLASS - 2 | 08U01. 08U01 - ADJUST FLOOR STOPS OFF LEVEL.MORE ON DOWN W/2 TO 3 PEOPLE INSIDE. | $500 | $0 | Apr 30, 2009 |
| Jul 3, 2008 | 34685101P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS AT NORTHWEST SECTION OF BLDG STRUCTURAL CRACKS RUNNING VERTICAL FROM 1ST FLOOR TO PARA... | $500 | $0 | Sep 4, 2008 |
| Jun 20, 2008 | 34662500K | RESOLVE | Hazardous | SEC 27-1009 (A) STOP ALL WORK FAILURE TO SAFEGUARD PUBLIC AND PROPERTY AFFECTED BY CONST. OPERATIONS WORK PERFORMED U... | $0 | $0 | Aug 14, 2008 |
| May 5, 2008 | 34642494P | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN - INTERIOR. NOTED VERTICAL & SETTLEMENT CRACKS OBSERVED IN 6H, 5H AND SUPER'S APT. CRACKS ARE UP ... | $0 | $0 | Oct 2, 2008 |
| Apr 26, 2008 | 34587953X | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG WALL.DEFECTS NOTED:APPROXIMATELY 1/2" TO 1" WIDE CRACK OPEN UP ON EXTERIOR WALL(WES... | $0 | $0 | Jun 12, 2008 |
| Mar 25, 2008 | 38183309J | RESOLVE | Non-Hazardous | *08V0184L10. (08V01) ADJUST FLR STOPS OFF 8 TO 10 INCHES W/ PPL INSIDE(84L10) ELEVATOR STOPS B/W FLR & CAB DOORS OPEN... | $800 | $0 | May 15, 2008 |
| Mar 24, 2008 | 38183304K | RESOLVE | Non-Hazardous | 08V01.40T07.59Q03.86BB05. | $0 | $0 | May 15, 2008 |
| Feb 25, 2008 | 34618734P | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. NOTED: VERTICAL CRACKS ON THE EXTERIOR OF BLDG FROM GROUND TO PARAPET PRIMARILY ON THE WESTERN S... | $180 | $0 | Apr 17, 2008 |
| Jan 18, 2008 | 38181082P | RESOLVE | Non-Hazardous | 8V1,16L10,27H11,39D7,8V LEVELING IS OFF ON ALL FLOORS 16L DOOR CHECK NEED REPAIR 4TH & 1ST FL 27H DOOR HANGERS NEED T... | $0 | $0 | Mar 13, 2008 |
| Oct 3, 2007 | 38178713P | RESOLVE | Non-Hazardous | 25D6/12I10/8V1/31H10/10B7/.25D6-SECURE TOP EMERGENCY EXIT.12I10-REPAIRDAMAGED LIGHTS IN ELEVATOR & INSTALL GUARD.8V-A... | $0 | $0 | Nov 29, 2007 |
| May 11, 2007 | 38166641R | RESOLVE | Non-Hazardous | 8V1/83X10/.CEASE USE:8-V-1-ADJUST FL STOPS 4TH & 5TH FL OFF LEVEL BY 2FT.83-X-10-RETURN TO SERVICE,AS PER RULE 11-02,... | $500 | $0 | Jun 28, 2007 |
| Mar 4, 2007 | 34558086Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG WALLS. DEFECTS NOTED: AT REAR OF BLDG NORTH EAST ELEVATION CORNER EXIST STRUCTURAL ... | $800 | $0 | Apr 26, 2007 |
| Jan 16, 2007 | 38163297N | RESOLVE | Non-Hazardous | 08J01,16J01,33I10. 08- ADJUST 16- ADJUST 4TH FL, ELEVATOR STOP WHEN DOOR IS PULLED 33- REPAIR FL 4TH FL HOISTWAY DOOR. | $180 | $0 | Jun 14, 2007 |
| May 26, 2006 | 38159085J | RESOLVE | Non-Hazardous | 55Y10/58Y10/38Y02. 58-BRAKE SHOE LONINGSAND DRUM. | $0 | $0 | Jul 13, 2006 |
| Mar 12, 2004 | 38145986J | RESOLVE | Non-Hazardous | 16T07/08V01/64X10 16-FLOOR # DESIGNATIONS | $0 | $0 | Apr 29, 2004 |
| Jun 25, 2003 | 38140301P | RESOLVE | Non-Hazardous | 16,J,01 38,O,02 55,F,01 64,M,07 39,D,06 16 DOOR STICKS AT BASEMENT LEVEL 38 CLEAN 55 ADJUST 64 PROVIDE 39 SECURE | $180 | $0 | Aug 14, 2003 |
| Apr 10, 2003 | 38137436P | RESOLVE | Non-Hazardous | 3J11/ 8V1/ 5J11/ 16L11/ 48B15/ 3I11 = TRIPING HAZARD 5J11 = TOO MUCH GAP BETWEEN CAR DOOR AND CAR POST 16L11 = SLAMS ... | $180 | $0 | Oct 23, 2003 |
| Apr 16, 2002 | 38122952J | RESOLVE | Non-Hazardous | 5J11/ 22D6/ 5J11 = TOO MUCH GAP BETWEEN CAR DOOR AND CAR POST | $0 | $0 | Jun 6, 2002 |
| Dec 22, 2000 | 38110651H | RESOLVE | Non-Hazardous | 08V11. 08-ADJ FLOOR LEVELS AS REQUIRED. | $0 | $0 | Feb 8, 2001 |
| Nov 21, 2000 | 38109374K | RESOLVE | Non-Hazardous | 35P17,30O02,08V11. | $0 | $0 | Jan 11, 2001 |
| Jul 3, 2000 | 38106717J | RESOLVE | Non-Hazardous | 03D11,37D11,21I12,03B07,46B12,30O02,47#12,10J11,75R05,36O12.03-PUT NEWWIRING ON CAR IN METAL CONDUIT AS REQURIED.37-P... | $180 | $0 | Dec 14, 2000 |
| May 17, 1997 | 38060030M | RESOLVE | Non-Hazardous | 46M74D35M08V37I28B 46-PROVIDE SPIN OUT FOR CAR & CWT SHACKLES 74- PROPERLY SECURE COVER ON BOX TOP OF CAR 35-PROVIDE ... | $0 | $0 | Sep 18, 1997 |