ECB violations
690 Fort Washington Avenue, Manhattan • Block 02180 • Lot 0605
139 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 29, 2025 | 39146413N | RESOLVE | CLASS - 2 | CLASS 2: NO CHAIN ON ESCAPE HATCH, INSTALL CHAIN ON ESCAPE HATCH. TOP OF CAR LIGHT DAMAGED, REPAIR TOP OF CAR LIGHT. ... | $625 | -$310 | Jul 31, 2025 |
| Dec 19, 2024 | 39133286R | RESOLVE | CLASS - 2 | CLASS 2: PHONE MISSING INSTALL & CONNECT SERVICE TO EMERGENCY OPERATOR. CAR FLOOR NOT LEVEL TO LANDING SILL ADJUST TO... | $312 | $0 | Aug 14, 2025 |
| Dec 19, 2024 | 39133285P | RESOLVE | CLASS - 1 | CLASS 1: DOOR LOCK MONITORING INOPERATIVE REAPIR & TEST (CU). WORM BEARING WORN ON MOTOR REPAIR (CU). CLASS 2: PHONE ... | $1,250 | $0 | Feb 27, 2025 |
| Apr 23, 2024 | 39112360N | RESOLVE | CLASS - 2 | CAR SADDLE TO HALL SADDLE IS NOT LEVEL AT THE LOBBY LEVEL CREATING A TRIPPING HAZARD, NEED TO ADJUST FLOOR STOPS. BRA... | $312 | $0 | Jul 25, 2024 |
| Nov 14, 2023 | 39099291P | RESOLVE | CLASS - 2 | FTM B254 FOUND A FEDERAL BOILER FST250 DUEL FUEL TO HAVE THESE VIOLATING CONMDITIONS/TUBES LEAKING/COMBUSTION AIR FAN... | $310 | $0 | Jan 18, 2024 |
| Feb 13, 2023 | 39079605K | RESOLVE | CLASS - 2 | CLASS 2: PHONE MISSSING FROM INSIDE CAB. INSTALL PHONE & PROGRAM TO 24 HR EMERGENCY OPERATOR. CAR FLOOR NOT LEVEL TO ... | $0 | $0 | Apr 20, 2023 |
| Feb 13, 2023 | 39079604Z | RESOLVE | CLASS - 2 | CLASS 2: PHONE MISSSING FROM INSIDE CAB. INSTALL PHONE & PROGRAM TO 24 HR EMERGENCY OPERATOR. CAR FLOOR NOT LEVEL TO ... | $625 | $0 | Apr 20, 2023 |
| Dec 29, 2020 | 39034012X | RESOLVE | CLASS - 1 | CAR CEASE USE CLASS 1 CAR DOOR RESTRICTOR IS NOT WORKING MISSING PARTS REPAIR OR REPLACE.OUT SIDE COMM MISSING PROVIDE. | $1,280 | $0 | Feb 18, 2021 |
| Aug 10, 2020 | 35538808P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING EXTERIOR WALLS/FACADE AND APPURTENANCES. OBSERVED AT EXPOSURE 1:CRACK AT 4 FL UNDER WIND... | $625 | $0 | Oct 15, 2020 |
| Jan 21, 2020 | 38273045Y | RESOLVE | CLASS - 1 | 42M05: NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. ... | $1,250 | $0 | Sep 24, 2020 |
| Jan 21, 2020 | 38273044M | RESOLVE | CLASS - 1 | 42M05: NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. ... | $1,250 | $0 | Sep 24, 2020 |
| Nov 7, 2019 | 38272215N | RESOLVE | CLASS - 2 | 02-M-7,39-M-07=02-M-07 PROVIDE EMERGENCY COMMMUNICATION(PHONE) INSIDE ELEVATOR CAR SO INCASE OF EMERGENCY THE PASSANG... | $0 | $0 | Jan 16, 2020 |
| Nov 15, 2018 | 38266514M | RESOLVE | CLASS - 2 | 2M7,8V10. 2M7-NO EMERGENCY OUTSIDE COMM, PROVIDE; 8V10-CAR FLOOR TO LANDING SILL NOT LEVEL, REPAIR. | $655 | $0 | Jan 10, 2019 |
| Oct 10, 2018 | 35365103M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTE: EXP1 SOUTH ELEVATION CRACK/MISSING/DAMAGE BRICK... | $2,500 | $0 | Jan 31, 2019 |
| May 9, 2018 | 35318821P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTE: AT THE TIME OF INSPECTION, FACADE OBSERVE RECUR... | $1,563 | $0 | Jun 28, 2018 |
| Dec 12, 2017 | 38260039P | RESOLVE | CLASS - 2 | 30B10. 30B BOTTOM SLOW DOWN ROLLER WRAPPED WITH FRICTION TAPE. | $0 | $0 | Feb 1, 2018 |
| Dec 11, 2017 | 38260036J | RESOLVE | CLASS - 1 | CEASE USE. 72H11,2M7,42B9,56Y13,59Y2. (72H)PIT/RUN- STOP SWITCH- WHEN CHECKED UNABLE TO CHECK IN STOP POSITION (SWITC... | $1,000 | $0 | Jan 25, 2018 |
| Dec 2, 2017 | 35264920J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS AND APPURTENANCES.NOTE:SOUTH ELEVATION EXPOSURE #1 (W-190ST)OBSERVE CRACK... | $1,000 | $0 | Jan 18, 2018 |
| Apr 7, 2017 | 35250876Y | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. I OBSERVED ON ROOFTOP ON SIDE OF BLDG AND IN CELLARAREA NEWLY INSALLED GAS PIPING AND FITTINGS, EX... | $1,600 | $0 | May 25, 2017 |
| Feb 14, 2017 | 38253671N | RESOLVE | CLASS - 2 | 02M7,68M7,59B7.02M7 PROVIDE MISSING PHONE IN CAB;68M7 PROVIDE CONTROLLER PRINTS;59B7 WRONG DATE IN BRAKE MAINTENANCE ... | $0 | $0 | Jun 15, 2017 |
| Sep 9, 2015 | 38238586N | RESOLVE | CLASS - 2 | 67M07 COMMUNICATION MISSING PROVIDE IN CAR PHONE. | $0 | $0 | Oct 29, 2015 |
| Sep 9, 2015 | 38238585L | RESOLVE | CLASS - 2 | 67M07,20I11,41M07,40P07. 67M07-COMMUNICATION MISSING IN CAR PROVIDE; 20I11-VISION PANEL DAMAGED REPLACE BROKEN 6TH FL... | $0 | $0 | Oct 29, 2015 |
| Apr 8, 2015 | 38235736X | RESOLVE | CLASS - 2 | 08V01,03B10,40O02,41I10,56Y13,58Y02,70#01. 70#-COMPLY W/8.1 (SECTION) (PIT AREA); 41I- LOCK DAMAGED REPAIR; 58Y-FRONT... | $0 | $0 | May 28, 2015 |
| Jul 15, 2014 | 38231717M | RESOLVE | CLASS - 2 | 05M07;08J01,70O02,52Q07,41L10,41L06,45M07,61L11 #05 ZONE RESTRICTOR(CODE 84)NEW OPERATOR GATE SW #09 ADJUST FLOOR STO... | $250 | $0 | Sep 4, 2014 |
| Jul 15, 2014 | 38231716K | RESOLVE | CLASS - 2 | 56M07,56Y10,56O02,40O02,41L11,64M07,70O02,61L11.#56 GEAR OIL.#56 CLEAN #40CLEAN OIL OFF FL,#41 M/ROOM DOOR & FRAME,#6... | $250 | $0 | Sep 4, 2014 |
| Dec 24, 2013 | 38229677Y | RESOLVE | CLASS - 1 | 21J10,08B01,16D10,97M07. 21J10-HATCH DOOR ELECTRICAL INTERLOCK CONTACTS STOPS CAR WHEN PULL DOOR ON THE 6TH FLOOR AND... | $5,000 | $0 | Feb 13, 2014 |
| Dec 7, 2012 | 38224713J | RESOLVE | CLASS - 2 | 100M7,01B11,02B11,13M7. 100-PHONE IN CAR ALSO FIRE SERVICE PHASE ONE AND TWO NEEDED (1)STOP SWITCH IN CAR MUST BE PUS... | $0 | $0 | Jan 24, 2013 |
| Dec 7, 2012 | 38224712H | RESOLVE | CLASS - 2 | 100M7,01B11,02B11,13M7. 100-PHONE IN CAR NEED ALSO FIRE SERVICE PHASE ONE OF TWO NEEDED (1)STOP SWITCH IN CAR MUST BE... | $0 | $0 | Jan 24, 2013 |
| Nov 30, 2011 | 38219061R | RESOLVE | CLASS - 2 | 32H11,08V06,100BB10,72M07,16B01-(08V)ADJUST LEVELING ON ALL FLOORS.(100BB)SERVICE FIRE EXTINGUISHER.(16B)ADJUST ALL H... | $0 | $0 | Jan 19, 2012 |
| Jan 25, 2011 | 34879557Z | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE APPROVED PLANS JOB #120558789 DURING CONSTRUCTION IN APT 2G. REMEDY: STOP ALL WORK PROVIDE APPROVE... | $250 | $0 | Jul 7, 2011 |
| Sep 21, 2010 | 38213020N | RESOLVE | CLASS - 2 | 42/D/06,42/G/11,57/Q/03/42-D-06SECURE PDT RELAY ON CONTROLLER/42-G-11-REPLACE BRIDGED FUSES ON CONTROLLER/57-Q-03-INS... | $0 | $0 | Nov 18, 2010 |
| May 13, 2010 | 34820091J | RESOLVE | CLASS - 2 | FAILURE TO SAFEGUARD ALL PERSONS AND PROPERTY AFFECTED BY CONSTRUCTIONOPERATIONS. OBSERVED RECENT SMOKING REFUSE W/I ... | $1,200 | $0 | Dec 16, 2010 |
| May 13, 2010 | 34820092L | RESOLVE | CLASS - 2 | FAILURE TO SAFEGUARD ALL PERSONS AND PROPERTY AFFECTED BY CONSTRUCTIONOPERATIONS NOTED AT TIME OF INSPECTION. EXCESSI... | $800 | $0 | Dec 16, 2010 |
| Mar 31, 2010 | 34835952Y | RESOLVE | CLASS - 2 | PERFORMING UNLICENSED PLUMBING WORK W/O A MASTER PLUMBERR LICENSE. NOTED: MR GRISHA ADMITTED TO ME UPON INSPECTION TH... | $0 | $0 | Sep 23, 2010 |
| Mar 31, 2010 | 34835953X | RESOLVE | CLASS - 2 | SEC. 27-3017(A). PERFORMING UNLICENSED ELECTRICAL W/O THE REQUIRED LICENSE. NOTED: MR. GRISHA ADMITTED TO ME UPON INS... | $0 | $0 | Sep 23, 2010 |
| Dec 21, 2009 | 32067764P | RESOLVE | CLASS - 3 | B354,15,50A,B,C.50A-OIL BURNER SMOKE.50B-PIPE SAFETY OR RELIEF VALVE DOWN NO THREADED END.50C-REMOVE WASTE OIL FROM B... | $200 | $0 | Aug 3, 2010 |
| Sep 23, 2009 | 34804543L | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. NOTE: RESPONDENT FAILED TO CORRECT THE CONDITIONS... | $2,400 | $0 | Jun 17, 2010 |
| Aug 14, 2009 | 34804203P | RESOLVE | CLASS - 1 | FAIL TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. DEFECTS NOTED: AT FIRE ESCAPE BALCONIES ON FT WASHINGTON AVE ELEVATION ... | $1,200 | $0 | Jul 8, 2010 |
| Aug 14, 2009 | 34804206K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS. AT REAR YARD SETBACK FOUND WITH THE STORAGE OF NU... | $0 | $0 | Jul 8, 2010 |
| Aug 14, 2009 | 34804202N | RESOLVE | CLASS - 2 | WORK W.O PERMIT. ILLEGAL WORK NOTED: AT REAR YARD SETBACK FOUND W.AN IRON FENCE W/DOOR INSTALLED @ 9'-0" ADJACENT TO ... | $800 | $0 | Jul 9, 2010 |
| Aug 14, 2009 | 34804205Z | ACTIVE | CLASS - 1 | FAIL TO MAINTAIN EXTERIOR BLDG WALLS OR APPURTENANCES. DEFECTS NOTED: AT BLDG REAR YARD SETBACK FOUND W.A RAMP & RAIL... | $200 | $0 | Jul 8, 2010 |
| Aug 14, 2009 | 34804204R | RESOLVE | CLASS - 3 | FENCE EXCEEDS PERMITTED HEIGHT. NOTED: AT REAR YARD SETBACK ACCESS AT LEFT OF FT WASHINGTON AVE ELEVATION FOUND W/THE... | $200 | $0 | Jul 9, 2010 |
| Jul 15, 2009 | 32066519R | RESOLVE | CLASS - 2 | 50A,B,51. 50A-CHIMNEY BASE NOT SEALED FOR COMBUSTION FLUE GAS TIGHTNESS MAY CAUSE COMBUSTION FLUE GAS SPILLAGE INTO B... | $500 | $0 | Jul 29, 2010 |
| Apr 22, 2009 | 34775410H | RESOLVE | CLASS - 2 | SEC. 28-201.1 UNLAWFUL ACTS FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER NOTED: RESPONDENT HAS FAILED TO COMPL... | $0 | $0 | Jun 11, 2009 |
| Apr 22, 2009 | 34775408Z | RESOLVE | CLASS - 2 | SEC. 28-201.1 UNLAWFUL ACTS FAILURE TO COMPLY WITH AN ORDER OF THE CO MMISIONER NOTED: RESPONDENT HAS FAILED TO COMPL... | $0 | $0 | Jun 11, 2009 |
| Apr 22, 2009 | 34775409K | RESOLVE | CLASS - 2 | SEC. 28-201.1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH AN ORDER OF THE COMMISIONER NOTED: RESPONDENT HAS FAILED TO COMPL... | $0 | $0 | Jun 11, 2009 |
| Apr 22, 2009 | 34775407R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILL A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS ... | $0 | $0 | Nov 5, 2009 |
| Apr 8, 2009 | 34766066N | RESOLVE | CLASS - 1 | STOP ALL WORK. WORK W/O A PERMIT. NOTED: IN APT 1D CONVERTED 1BR APT INTO 3 BR REMOVED KITCHEN AND CREATED BR, ERECTE... | $1,600 | $0 | Jun 17, 2010 |
| Feb 19, 2009 | 34758173Z | RESOLVE | CLASS - 1 | FAILURE SAFEGUARD ALL PERSONS AND PROPERTY AFFECTED BY CONST OPERATIONS NOTED THE BATHROOM CEILING OF APT 5I HAS BEEN... | $0 | $0 | Nov 5, 2009 |
| Dec 22, 2008 | 38199560X | RESOLVE | CLASS - 1 | CU1D10,CU5D10,61M7,56Y/O10/12,100BB5,75M7,97#10. 1D70 CEASE USE: STOP SW IS NOT SECURE WHEN TRYING TO ACTIVATE. 5D10 ... | $1,000 | $0 | Sep 10, 2009 |