ECB violations
212 Willis Avenue, Bronx • Block 02281 • Lot 0004
11 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 31, 2018 | 32097714Y | RESOLVE | CLASS - 2 | 5A,15,38,50,51,21B,40,50A,50B-50)FOUND IN CELLAR FLUE PIPE MISSING ON BOILER. 50A)NEED TO CLEAN THINGS OUT OF BOILER ... | $625 | $625 | Oct 19, 2018 |
| Jan 9, 2018 | 35255845Y | RESOLVE | CLASS - 1 | REMOVED OR DEFACED A WRITTEN POSTED VACATE ORDER. NOTED: AT THE TIME OF INSPECTION VACATE STICKER WAS REMOVED. VACATE... | $1,000 | $0 | Mar 2, 2018 |
| Jul 21, 2017 | 35245295J | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. WORK NOTED: AT TIME OF INSPECTION THERE IS UNPERMITTED WORK ONGOING AT THE 1ST FL W/O A PERMIT. BR... | $4,000 | $0 | Sep 15, 2017 |
| Dec 23, 2008 | 32065069Y | RESOLVE | CLASS - 3 | 18B FULTON VT BOILER 10HP NB66829 GAS 18B SCALE ACCUMULATION & EVIDENCE OF LEAKAGE AT UPPER & LOWERHANDHOLES DESCALE ... | $500 | $0 | Feb 20, 2009 |
| Jul 17, 2007 | 32054442J | RESOLVE | Non-Hazardous | B4A/18A/18B/44A/48B/50A/50B/50C/50D/50E/.50A-STEAM GAUGE TEST PORT MISSING.50B-REVERSE FIXED VENTILATION FAN TO BRING... | $180 | $0 | Sep 7, 2007 |
| Nov 15, 2005 | 32048831M | RESOLVE | Non-Hazardous | 50A/50B/50C. FULTON V.T. BOILER, 10 HP, NB52466, GAS, 50(A) NO SECONDARY SCREW TYPE SHUT OFF VALVE ON THE BLOWDOWN LI... | $180 | $0 | Feb 24, 2006 |
| Nov 15, 2005 | 32048832Y | RESOLVE | Non-Hazardous | 50A/50B/50C. H.B SMITH C.Z- BOILER, LP STEAM, OIL- FIRED. 50 (A) NO ANTI-SIPHON DEVICE IS INSTALLED ON THE HIGH POINT... | $0 | $0 | May 19, 2006 |
| Jan 23, 2004 | 32043594P | RESOLVE | Non-Hazardous | 48A,B50B,50A. FULTON VERT TBS HP BOILER; 10HP, NB 52466 GAS-FD 50(A) STRUCTURE DEFICIENCIES IN BOILER ROOM NOTED. MIN... | $180 | $0 | Mar 5, 2004 |
| Jan 23, 2004 | 32043595R | RESOLVE | Non-Hazardous | 50A,50B,50C. HB SMITH CAST IRON LP STEAM BOILER, OIL-FIRED 50(A) THE STANDARD STEAM PRESSURE GAUGE ON THE BOILER IS I... | $0 | $0 | May 26, 2006 |
| Feb 2, 1999 | 32016993Z | RESOLVE | Non-Hazardous | 8C,9A,9B. 8C-WELDED PATCHES IMPROPERLY INSTALLED. 9A-WELDING UNLICENSED REPAIR. 9B-WELDING POOR QUALITY. | $350 | -$50 | May 5, 1999 |
| Jan 3, 1990 | 34029640Z | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. CELLING BEAMS ARE ROTTING AND CORRODED . THESE DEFECTS ARE LOCATED AT REAR OF STORE ABOVE BATHRO... | $1,000 | $0 | Feb 16, 1990 |