ECB violations
370 Willis Avenue, Bronx • Block 02287 • Lot 0007
26 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 23, 2021 | 35645903R | RESOLVE | CLASS - 2 | JOBSITE FENCE NOT MAINTAINED TO CODE SUBSECTION.AT TIME OF INSPECTION OBSERVED 4 STORY BUILDING UNDER CONSTRUCTION CO... | $0 | $0 | May 20, 2022 |
| Dec 29, 2020 | 35545248L | RESOLVE | CLASS - 2 | JOBSITE FENCE NOT CONSTRUCTED OR MAINTAINED PURSUANT TO SUBSECTION NOTED AT THE TIME OF INSPECTION OF A 4 STORY ALT 2... | $500 | $500 | Apr 16, 2021 |
| Mar 2, 2020 | 35470245M | RESOLVE | CLASS - 1 | BC33103-NO SITE SAFETY PLAN.AT TIME OF MY INSPECTION,AT A 4 STORY BUILDING UNDER ALTERATION I OBSERVED CONSTRUCTION O... | $2,500 | $2,500 | Apr 9, 2021 |
| Mar 2, 2020 | 35470247X | RESOLVE | CLASS - 1 | OVERHEAD PROTECTION.AT THE TIME OF MY INSPECTION OF A 4 STORY BUILDINGUNDER ALTERATION,I OBSERVED NO OVERHEAD PROTECT... | $10,000 | $10,000 | Apr 9, 2021 |
| Mar 2, 2020 | 35470246Y | RESOLVE | CLASS - 1 | INADEQUATE LOG BOOK.AT THE TIME OF MY INSPECTION AT 4 STORY BUILDING UNDER ALTERATION,I OBSERVED COMPETENT PERSON AND... | $10,000 | $10,000 | Apr 9, 2021 |
| Mar 2, 2020 | 35470249J | RESOLVE | CLASS - 1 | BC330744-AT TIME OF MY INSPECTION AT A 4 STORY BULIDING UNDER ALTERATION I OBSERVED 3 LABORERS CARVING 2X4 FROM THE S... | $2,500 | $2,500 | Apr 9, 2021 |
| Mar 2, 2020 | 35470248H | RESOLVE | CLASS - 1 | SIDEWALK SHED WHERE REQUIRED.AT THE TIME OF MY INSPECTION AT A 4 STORYBUILDING UNDER ALTERATION I OBSERVED THAT THE S... | $10,000 | $10,000 | Apr 9, 2021 |
| Jan 9, 2018 | 35255808P | RESOLVE | CLASS - 1 | REMOVED OR DEFACED A WRITTEN POSTED VACATE ORDER. NOTED: AT THE TIME OF INSPECTION,VACATE STICKER WAS OBSERVED TO HAV... | $2,500 | $0 | Mar 2, 2018 |
| Dec 19, 2011 | 34895699Y | RESOLVE | CLASS - 1 | RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN THE LEGALLY APPROVED # OF FAMILIES, DOB HPD RECORDS INDIC... | $57,000 | $57,000 | Feb 3, 2012 |
| Sep 2, 2011 | 34866796N | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C/O OR BLDG DEPT RECORDS 2ND STORY CLASS A APT BEEN SUBDIVIDED INTO 2APTS W... | $6,000 | $0 | Dec 30, 2011 |
| May 24, 2011 | 34891772N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLAINT MANNER NOTED: STAIR RAILING BETWEEN 2ND & 3RD FL DANGEROUS(BALLISTERS)... | $5,000 | $0 | Aug 12, 2011 |
| May 24, 2011 | 34891770J | RESOLVE | CLASS - 1 | WORK W/O PERMIT NOTED: AT REAR OF BUILDING BASEMENT LEVEL REMOVE 6'WIDE SECTION OF BRICK EXTERIOR WALL (STRUCTURAL) &... | $11,000 | -$6,000 | Jul 15, 2011 |
| May 24, 2011 | 34891771L | RESOLVE | CLASS - 1 | RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN THE LEGALLY APPROVED # OF FAMILIES NOTED: HPD RECORDS SHO... | $6,000 | -$6,000 | Aug 12, 2011 |
| May 18, 2011 | 34832897R | RESOLVE | CLASS - 2 | WORK W/O A PERMIT FOUND IN CELLAR & 1ST FL "J & J DRY CLEANERS" GAS PIPING INSTALLED & BY PASS (ILLEGAL PIPING) REMOV... | $2,000 | -$2,000 | Jul 15, 2011 |
| May 18, 2011 | 34832898Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLAINT MANNER FOUND ON GROUND FLOOR OF LOCATION "J & J DRY CLEANERS" WATER LE... | $2,500 | $0 | Jul 15, 2011 |
| Aug 4, 2010 | 32068818X | RESOLVE | CLASS - 3 | 50A/B.(FULTON V.J BOILER GHP,NB 50676,OIL FIRED,1986.(50A)LOWER HANDHOLE PORTS FULLY COVERED W/ FURNACE CEMENT.REMOVE... | $200 | $0 | Oct 1, 2010 |
| Aug 4, 2010 | 32068817Y | RESOLVE | CLASS - 3 | 6A,50.CAST IRON LP BOILER OIL FIRED.(6A)SAFETY VALVE CORRODED NOT OPERABLE.REPLACE SAFETY VALVE.(50)OIL SPILL FROM FU... | $200 | $0 | Oct 1, 2010 |
| Oct 21, 2009 | 32067304Y | RESOLVE | CLASS - 1 | CEASE USE. 50A,51,50B.FULTON VT BOILER,HP STEAM,OIL FIRED.50A SECTIONSOF THE BOILER EXTERIOR CASING CORRODED REPLACE ... | $5,000 | $0 | Dec 18, 2009 |
| Dec 23, 2008 | 32065068M | RESOLVE | CLASS - 1 | XA.50A CAST IRON LOW PRESSURE STEAM HEATINGS OIL 6A SAFETY VALVE CORRODED NOT OPERABLE REPLACE DEFECTIVE SAFETY VALVE... | $2,500 | -$2,500 | Apr 17, 2009 |
| Dec 23, 2008 | 32065067K | RESOLVE | CLASS - 1 | 36.50A.50B.50C.51 FULTON VT BOILER HP STEAM OIL FIRED 36 FLUE PIPE DISLOCATED AT ELBOW JOINT 50A CONTROL INSTRUMENTS ... | $5,000 | $0 | Apr 17, 2009 |
| Jul 17, 2007 | 32054443L | RESOLVE | Hazardous | B4B/3B/3D/11A/18A/18B/30A/48A/48B/51/25A/25B/. | $2,500 | $0 | Sep 7, 2007 |
| Jan 23, 2004 | 32043596Z | RESOLVE | Non-Hazardous | 18A,B,44C,50A,38,48A,B,50B. FULTON VERT TBS BOILER 6HP,NB50676 OIL-FIRED 1986 50(A) SECONDARY LOW WATER CUT OFF RESET... | $350 | $0 | Oct 22, 2004 |
| Aug 7, 2001 | 32025844J | RESOLVE | Non-Hazardous | 2ND VALVE IN BLOWDOWN AND WATER COLUMN AND WATER COLUMN DRAIN TO INSTALL LOW WATER MANUAL RESET SWITCH TO RECONNECT I... | $350 | $0 | Sep 21, 2001 |
| Mar 3, 2000 | 32018595M | RESOLVE | Non-Hazardous | 49, YOU WERE NOTIFIED THIS INSPECTION THRU OFFICIAL NOTICE BUT BOILER WAS NOT ARRANGED FOR INTERNAL INSPECTION WHEN I... | $2,500 | $0 | Apr 14, 2000 |
| Jun 10, 1997 | 32014872N | RESOLVE | Hazardous | 16,18A,18B,48C,49, BLOW DOWN LINE VALVE HANDLE MISSING-BOILER WATER FEED LINE NEXT TO BOILER CORRODED. | $1,000 | $0 | Feb 13, 1998 |
| Dec 13, 1989 | 32003740H | RESOLVE | Unknown | MUST SUBMIT FILING APPLICATION NUNBER FOR HP BOILER INSTALLATION AT 370 WILLIS AVENUE. | $75 | $0 | Feb 23, 1990 |