ECB violations
103-105 East 146 Street, Bronx • Block 02351 • Lot 0021
26 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 9, 2026 | 39183928P | RESOLVE | CLASS - 1 | CLASS 1 CEASE USE: DOOR ZONE RESTRICTOR DEVICE FOUND INOPERATIVE AS PER CODE ASME A17.1/CSA B44 - SECTION 2.26.5. ELE... | $1,280 | $1,280 | Jul 17, 2026 |
| Apr 9, 2026 | 39183927N | RESOLVE | CLASS - 2 | CLASS 2: IN-CAR ALARM BELL INOPERATIVE AS PER CODE ASME A17.1/CSA B44 2.27.1.1.1, REPAIR. | $0 | $0 | Jul 17, 2026 |
| Apr 8, 2025 | 37034992H | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9C REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $2,530 | $0 | Jul 18, 2025 |
| Nov 19, 2024 | 39130685K | RESOLVE | CLASS - 2 | OBSERVED WIFI SYSTEM INSTALLED IN ROOM WITH THREE GAS FIRED APPLIANCES( WATER HEATERS) AS WELL AS GAS PIPING. THIS RO... | $0 | $0 | Jan 31, 2025 |
| Nov 19, 2024 | 39130690P | RESOLVE | CLASS - 2 | MISSING CONDENSATE NEUTRALIZERS ON WATER HEATERS &, MAINTAIN BOILER; MIDDLE WATER HEATERÝSERIAL#1638M000958¨ IS INOPE... | $312 | $0 | Jan 31, 2025 |
| Nov 19, 2024 | 39130689H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED 2 PLASTIC ACCESS PANELS LOCATED ON 1ST FLOOR IN PANTR... | $1,250 | $0 | Jan 31, 2025 |
| Nov 19, 2024 | 39130687Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Jan 31, 2025 |
| Nov 19, 2024 | 39130688X | RESOLVE | CLASS - 2 | OB, REPAIR/REPLACE DOOR | $0 | $0 | Jan 31, 2025 |
| Nov 19, 2024 | 39130684Z | RESOLVE | CLASS - 2 | NO NEUTRALIZATION KITS INSTALLED AT ANY OF THE WATER HEATERS. AS PER 102.3 OF THE PLUMBING CODE MAINTENANCE. INSTALLA... | $0 | $0 | Jan 31, 2025 |
| Oct 1, 2024 | 37029811N | RESOLVE | CLASS - 1 | FAILURE TO SUBMIT THE REQUIRED PARKING STRUCTURE INITIAL OBSERVATION REPORT FOR AN EXISTING PARKING STRUCTURE DOCUMEN... | $2,500 | $0 | Oct 6, 2025 |
| Aug 7, 2023 | 39092130M | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP BOILER THE FAILURE TO SUPPLY A REMOTE SHUT-DOWN AS REQUIRED FOR FUEL BURNING SYSTEMS. AS PE... | $625 | $0 | Sep 6, 2024 |
| Aug 7, 2023 | 39092132X | RESOLVE | CLASS - 1 | I OBSERVED IN THE ROOFTOP BOILER ROOM, THE INSTALLATION OF BRANCH CIRCUIT WIRING TO A EQUIPMENT DISCONNECT TO SUPPLY ... | $800 | $0 | Jun 4, 2024 |
| Aug 7, 2023 | 39092131Y | RESOLVE | CLASS - 1 | I OBSERVED EXPOSED AND ENERGIZED CONDUCTORS UNPROTECTED AND IMPROPERLY SUPPORTED. THE WIRING WAS SECURED TO METAL RAC... | $1,600 | $0 | Nov 12, 2024 |
| Sep 29, 2021 | 39048416J | RESOLVE | CLASS - 2 | I OBSERVED RESIDENTIAL GAS FLEX INSTALLED ON COMMERCIAL APPLIANCE. AS PER FGC 411.1 ALL COMMERCIAL APPLIANCES SHALL B... | $0 | $0 | Nov 19, 2021 |
| Sep 29, 2021 | 39048404M | RESOLVE | CLASS - 1 | I OBSERVED AT EXPOSURE #2 A FUSED DISCONNECT SWITCH BELOW A WOODEN PLYWOOD DECK NEXT TO THE GENERATOR. NO ELECTRICAL ... | $1,630 | $0 | Nov 19, 2021 |
| Sep 29, 2021 | 39048417L | RESOLVE | CLASS - 1 | I OBSERVED GAS LEAK ON NIPPLE TO THE GAS BOOSTER PUMP. CON-ED CALLED AND CONFIRMED THE LEAK. THE CON-ED TECH SHUT AND... | $1,280 | $0 | Nov 19, 2021 |
| Dec 1, 2018 | 35368570P | RESOLVE | CLASS - 1 | BC3304.1.1/FAILURE TO MAINTAIN SIDEWALK.NOTE:AT TIME OF INSPECTION I OBSERVED ACTIVE SITE WITH THE SIDEWALK NOT MAINT... | $0 | $0 | May 10, 2019 |
| Dec 1, 2018 | 35368571R | RESOLVE | CLASS - 1 | FAILURE TO DESIGNATE AND OR HAVE CONSTRUCTION SUPERINTENDENT AT SITE WHEN REQUIRED.NOTE:AT TIME OF INSPECTION I OBSER... | $10,000 | $0 | May 10, 2019 |
| Sep 18, 2017 | 35284945Y | RESOLVE | CLASS - 2 | ELECTRICAL ROOM NOT DEICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLYBASEMENT ELECTRICAL ROOM:USED ELECTRICAL ROOM A... | $600 | $0 | Mar 23, 2018 |
| Sep 18, 2017 | 35284944M | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. BASEMENT PUMP ROOM: SUB FEEDER,30MP DISCONNECT,5PH PUMP FOR NATURAL GAS."NO NA FILE... | $400 | $0 | Mar 27, 2018 |
| Jul 7, 2015 | 35146529J | RESOLVE | CLASS - 1 | 3303.4.5 AN EXCESSIVE AMOUNT OF MATERIALS (RE-BARS) WERE OBSERVED ON OUTRIGGER PLATFORM ON 8TH FL.NO ACTION HAS BEEN ... | $1,600 | $0 | Sep 9, 2015 |
| Aug 12, 2013 | 35028608K | RESOLVE | CLASS - 1 | SEC. 3303.4.1 FAILURE TO MAINTAIN AT TIME OF INSPECTION I OBSERVED GARAGE & DEBRIS BLOCKING PEDESTIAN SIDEWALK,ALSO U... | $4,000 | -$4,000 | Oct 4, 2013 |
| Aug 12, 2013 | 35028607Z | RESOLVE | CLASS - 2 | FAILURE TO POST PERMIT. AT TIME OF INSPECTION JOB SITE FENCE ERECTED. AS PER DOB RECORDS THERE IS ACTIVE & UP TO DATE... | $2,000 | -$2,000 | Oct 4, 2013 |
| Apr 10, 2012 | 34953620P | RESOLVE | CLASS - 1 | EXPIRED PERMIT:UPON INSPECTION AS NOTED ON 3RD OCCURRENCE THE N.B. PERMIT #210107677-01-NB POSTED AT PREMISES HAS BEE... | $1,600 | $0 | Jun 1, 2012 |
| Mar 31, 2012 | 34953600H | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS: WATER ACCUMULATION: UPON INSPECTION ... | $2,400 | $0 | May 18, 2012 |
| Mar 31, 2012 | 34942199R | RESOLVE | CLASS - 1 | EXPIRED PERMIT: UPON INSPECTION AS NOTED THE NB PERMIT #210107677-01-NB POSTED AT JOB SITE HAS EXPIRED SINCE 12/31/11... | $1,600 | $0 | May 18, 2012 |