ECB violations
828 Courtlandt Avenue, Bronx • Block 02406 • Lot 0003
29 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 22, 2026 | 39189672H | ACTIVE | CLASS - 1 | OBSERVED IN BASEMENT GAS LEAK ON REGULATOR FEEDING BOILER,IMPROPER STORAGE OF FLAMMABLE MATERIALS IN MECHANICAL ROOM ... | $2,500 | $2,500 | Aug 21, 2026 |
| Feb 11, 2025 | 37033269Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39104950N ISSUED ON 02/01/2024, AND FAILURE TO FILE... | $1,280 | $0 | May 2, 2025 |
| Mar 18, 2024 | 39109114K | RESOLVE | CLASS - 1 | FOUND AN H/B SMITH 19A-6 FIRED BY A POWER FLAME CR1-30 DO NOT OPERATE BOILER UNTIL ALL HAZARDOUS CONDITIONS ARE IMMED... | $1,250 | $0 | Sep 19, 2024 |
| Mar 18, 2024 | 39109090P | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT OUTSIDE OF THE BOILER ROOM EXCESSIVE MOLD ALONG THE CEILING. THIS IS A MAJOR HEALTH HAZARD... | $0 | $0 | May 31, 2024 |
| Feb 1, 2024 | 39104950N | RESOLVE | CLASS - 2 | OBSERVED LEVEL 3 CORROSION ON THE GAS PIPING LOCATED IN THE BASEMENT/CELLAR. 102.3 MAINTENANCE. INSTALLATIONS, BOTH E... | $0 | $0 | Apr 19, 2024 |
| Feb 1, 2024 | 39104949X | RESOLVE | CLASS - 2 | OBSERVED ACTIVE WATER LEAK IN THE BASEMENT/CELLAR. AS PER 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AN... | $0 | $0 | Apr 19, 2024 |
| Dec 21, 2023 | 39102024P | RESOLVE | CLASS - 2 | HB SMITH 19A-6 BOILER HAS SLIGHT WATER LEAK AT IT'S BASE. CORRECT VIOLATING CONDITION & SUBMIT A CERTIFICATE OF CORRE... | $310 | $0 | Mar 1, 2024 |
| Jul 25, 2022 | 39066560N | RESOLVE | CLASS - 2 | AS PER ONE HB SMITH 19A/S/06, DUAL FUEL BURNING BOILER; CONSTRUCTION AT BASE OF DOOR PREVENTING DOOR FROM CLOSING. | $0 | $0 | Sep 16, 2022 |
| Oct 22, 2019 | 39011573Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE CELLAR, 2 GROUNDING ROD THAT ARE NOT INSTALLED AS PER 250.64 IN THE NATIONAL ELECTRICAL CODE; 250.6... | $0 | $0 | Feb 28, 2020 |
| Oct 22, 2019 | 39011571K | RESOLVE | CLASS - 2 | NOTED: OBSERVED ON THE ROOF, ROOF RAILINGS HAVE BECOME DETACHED AT WELDED POINTS AT NORTH EAST SECTION OF ROOF., REPA... | $0 | $0 | Feb 28, 2020 |
| Jul 17, 2019 | 35340511K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35414833M ISSUED ON 04-30-19 & TO FILE A C OF C PURSUAN... | $625 | $0 | Nov 15, 2019 |
| Apr 30, 2019 | 35414833M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN A BLDG IN CODE COMPLIANT MANNER. OBSERVED IN THE CELLAR 2 DISIMILAR METAL PIPES(GAS PIPE WHICH IS... | $1,250 | $0 | Jul 12, 2019 |
| May 22, 2017 | 35267385K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 5/22/17 AT ABOVE ADDRESS IN BASEMENT PIPES BEING SU... | $500 | $0 | Jun 8, 2018 |
| May 22, 2017 | 35260899X | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIAL,APPARATUS,DEVICE,APPLIANCE OR WIRING IN USE.OBSERVED EMERG... | $800 | $0 | Jun 8, 2018 |
| May 22, 2017 | 35260898Y | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT.OBSERVED EMERGENCY LIGHTING AND NEW CEILING LIGHTS INSTALLED ON ALL FLOORS.REM:COMPL... | $800 | $0 | Jun 8, 2018 |
| May 22, 2017 | 35267319M | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCCE WITH SECTION.OBSERVED GROUNDING CONDUCTOR INSTALLED O... | $4,800 | $0 | Jun 8, 2018 |
| Dec 12, 2016 | 35222505R | RESOLVE | CLASS - 2 | SEC. 401.5 MISC VIOLATION GAS PIPING NOT LABELED OBSERVED ON 12-12-16 NEW GAS PIPING IN CELLAR NOT LABELED. REMEDY: C... | $400 | $0 | Feb 3, 2017 |
| Aug 27, 2014 | 35038530Z | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/O A PERMIT.ON 8/27/14 @ 11:25AM I OBSERV:NEW 6/3 BX RISER TO 16 APT 16 ELECT PANEL INSTALLED.BRANCH... | $0 | $0 | Oct 17, 2014 |
| Aug 27, 2014 | 35066877X | RESOLVE | CLASS - 1 | WORK W/O PERMIT.NOTE:INSTALLATION OF LAVATORY AND WATER CLOSET W/WATER & SANITARY PIPING IN CELLAR.NO PERMIT ON FILE ... | $1,600 | $0 | Oct 17, 2014 |
| Aug 27, 2014 | 35026232M | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED: OBSERVED AT TIME OF INSPECTION AT APT #A3 THE REAR EXIT WINDO... | $1,200 | $0 | Oct 17, 2014 |
| Aug 27, 2014 | 35066876Y | RESOLVE | CLASS - 2 | 301.1 FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTE:STOVE DEFECTIVE IN APT #A1.TENANT HAS TO USE A MATCH TO IGN... | $400 | $0 | Oct 17, 2014 |
| Aug 27, 2014 | 35026233Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NOTED: OBSERVED AT TIME OF I... | $1,000 | $0 | Oct 17, 2014 |
| Aug 27, 2014 | 35066878H | RESOLVE | CLASS - 2 | 301.1 FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTE:EXTERIOR STORM LITER DRAIN NOT CONNECTED TO STORM SEWER SYS... | $400 | $0 | Oct 17, 2014 |
| Mar 28, 2013 | 34957287Z | RESOLVE | CLASS - 3 | WORK W/O A PERMIT. WORK NOTED: REMOVAL & REPLACEMENT OF FIRE RATED MATERIAL,WALLS,CEILINGS & PLUMBING WORK THROUGHOUT... | $0 | $0 | May 17, 2013 |
| Apr 5, 2011 | 34812585J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALLS. DEFECTS ARE: 1) AT THE NORTH AND SOUTHELEVATION T/O VARIOUS LOCATIONS THE STUCCO WALL... | $5,000 | $0 | May 20, 2011 |
| Dec 28, 2009 | 34827767M | RESOLVE | CLASS - 2 | FAIL TO FILE A CERT OF CORRECTION FOR VIO#34787077L REM: CERT OF CORRECTION | $4,000 | $0 | Mar 5, 2010 |
| Aug 6, 2009 | 34787077L | RESOLVE | CLASS - 1 | FAIL TO MAINTAIN BLDG WALLS OR APPURTENANCES. DEFECT NOTED: NORTH PARAPET WALL OUT OF PLUMB,LEANING INWARD APPROX 3",... | $5,000 | $0 | Oct 2, 2009 |
| Jun 16, 2009 | 34791589R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: THERE ARE MISSING BRICKS AT THE NORTH WEST CORNER (CORNER OF ... | $5,000 | $0 | Aug 7, 2009 |
| Dec 12, 2008 | 34735862M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BLDG WALLS. DEFECT NOTED: ON NW SIDE OF BLDG THERE IS MISSING BRICK WORK IN VARIOUS LOCA... | $1,000 | $0 | Feb 6, 2009 |