ECB violations
1237 Webster Avenue, Bronx • Block 02427 • Lot 0046
21 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 1, 2025 | 39168812H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED FIRE ESCAPE DROP LADDER OBSTRUCTED WITH STAIRCASE. LO... | $2,500 | $2,500 | Nov 23, 2026 |
| Dec 1, 2025 | 39168811X | RESOLVE | CLASS - 2 | OBSERVED IN THE BASEMENT STORAGE NEXT TO GAS METERS. ALSO UNDER THE SINK USING FERNCO COUPLING ON WASTE LINE AND DECR... | $0 | $0 | May 29, 2026 |
| Feb 4, 2025 | 39137437N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $625 | $0 | Jun 6, 2025 |
| Feb 4, 2025 | 39137553K | ACTIVE | CLASS - 2 | FOUND FEDERAL FST-40 GAS FIRED BOILER WITH EXPOSED WIRING ON SIDE OF BOILER, SIGHT GLASS MISSING AT REAR CHAMBER DOOR. | $312 | $0 | Jun 6, 2025 |
| Apr 5, 2024 | 39110923Z | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT MAINTENANCE STORAGE ROOM THE INSTALLATION OF WIRING, CABLES, AND LIGHTS WITH NO JUNCTION B... | $1,600 | $0 | May 8, 2025 |
| Apr 5, 2024 | 39110924K | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT THE INSTALLATION OF ELECTRICAL WIRING AND LIGHTS AT THE REAR OF THE MAINTENANCE STORAGE RO... | $800 | $0 | May 8, 2025 |
| Feb 6, 2024 | 39105315Z | RESOLVE | CLASS - 2 | OBSERVED ACTIVE WATER LEAK FROM BOTTOM REAR OF THE BOILER LOCATED AT BASEMENT/CELLAR LEVEL. AS PER 102.3 OF THE PLUMB... | $0 | $0 | Apr 19, 2024 |
| Jul 28, 2022 | 39066873Y | RESOLVE | CLASS - 2 | OBSERVED SUMP PUMP INSTALLED IN THE BOILER ROOM WITH 2 INCH CAST IRON PIPING TO SANITARY LINE, NO PERMITS ON FILE FOR... | $0 | $0 | Sep 16, 2022 |
| Jul 28, 2022 | 39066895P | RESOLVE | CLASS - 2 | AS PER ONE FEDERAL FST-40 BOILER; COMBUSTION AIR FAN NOT INTERLOCKED WITH BOILER. FLAME GLASS AT REAR FIRE-DOOR MISSI... | $0 | $0 | Sep 16, 2022 |
| May 3, 2022 | 39061463Z | RESOLVE | CLASS - 2 | AT CELLAR EXIT DOORS DO NOT ALLOW EASY ESCAPE FROM THE BUILDING IN CASE OF EVACUATION, DOORS WITHOUT A SELF-CLOSING S... | $655 | $0 | Jun 17, 2022 |
| Jul 12, 2019 | 39005414X | RESOLVE | CLASS - 2 | SURFACE BLOWDOWN VALVE AND DRAIN NOT INSTALLED-BODY DRAIN MISSING FROM SAFETY VALVE- COIL RELIEF VALVE DRAIN NOT PIPE... | $655 | $0 | Aug 30, 2019 |
| Jul 10, 2019 | 37015401N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOL ATION #35349639K ISSUED ON 10/03/18 AND TO FILE... | $1,280 | $0 | Sep 20, 2019 |
| Oct 3, 2018 | 35349639K | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMETN AND/OR APPROV ED AMENDMENT FOR JOB #220254338 NOTED CELLAR LA... | $1,250 | $0 | Nov 30, 2018 |
| Sep 7, 2018 | 32097760P | RESOLVE | CLASS - 2 | 11A,50A,50B,50C,50D-AS PER CLASS 2(B254)28.301.1 FAILURE TO MAINTAIN.11A:SURFACE BLOWDOWN VALVE NOT INSTALLED DRAIN N... | $655 | $0 | Nov 2, 2018 |
| May 30, 2017 | 35267690R | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/O A PERMIT. OBSERVED NEW LIGHTS THROUGHOUT BLDG HALLS W/EMERGENCY BACK UP. ALSO IN STORAGE AREA IN ... | $400 | $0 | Feb 2, 2018 |
| May 30, 2017 | 35267494J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. ILLUMINATION FOR EXITS;EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1... | $500 | $0 | Feb 2, 2018 |
| May 30, 2017 | 35267688H | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEM OBSERVED BROKEN & CORRODED GROUND PIPE GOING TO WATER SYSTEM PIPE. REMEDY: PROVID... | $2,400 | $0 | Feb 2, 2018 |
| Nov 29, 2016 | 35221110H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NOTED: CELLAR LEVEL AT CEILI... | $530 | $0 | Jan 20, 2017 |
| Jun 20, 2015 | 32075182P | RESOLVE | CLASS - 2 | B254,15,16,32A,50A,50B,50C,50D,50E,50F,50G. 50A-GLASS MISSING IN REAR OF BOILER TO SIGHT FIRE; 50B-MISSING BAROMETRIC... | $500 | $0 | Jan 29, 2016 |
| May 4, 2011 | 32070633M | RESOLVE | CLASS - 2 | B254,5B,15,16,32A,50A,B,C,D,E. 50A- SOOT ON BOILER AND BURNER. 50B- CLEAN OUT DOOR TO CHIMNEY MUST CLOSE TIGHT. 50C- ... | $500 | $0 | Sep 2, 2011 |
| Dec 30, 2008 | 34736080M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL DEFECT NOTED THERE IS CRACK BRICK WORK IN VARIOUS LOCATIONS AND MISSING MORTAR JOINTS O... | $1,200 | $0 | Feb 20, 2009 |