ECB violations

Bx Learning Institute For Girls, Bronx • Block 02443 • Lot 0079

36 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Mar 26, 2026 35722418J ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FIRE-PROOF DOORS DO NOT SELF-CLOSE PROPERLY AT 3RD FLR-... $1,250 $0 Apr 10, 2026
Mar 26, 2026 35722419L ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371... $1,250 $0 Apr 10, 2026
May 20, 2025 35720006Y RESOLVE CLASS - 2 EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION WHEN TESTED.AT THE TIME OF INSPECTION OBSERVED AND NOTE... $625 $0 Aug 15, 2025
Mar 17, 2022 35591613H RESOLVE CLASS - 2 REISSUE#35548230R.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:ILLUMINATION FOR EXIT,EXIT DISCHARGES AND PUB... $1,562 $0 Jun 17, 2022
Feb 9, 2021 35548230R RESOLVE CLASS - 2 REISSUE#35495367L FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC COR... $1,562 $0 May 21, 2021
May 8, 2020 35495367L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS ,EXIT DISCHARGES AND PUBLIC CORRIDORS PE... $625 $0 Aug 7, 2020
May 8, 2020 35495368N RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUIDLING IN CODE COMPLIANT MANNER USE OF PROHIBITED DOOR AND OR HARDWARE PER BC 1008.1.8;27-381(J... $625 $0 Aug 7, 2020
Jan 31, 2018 35291040P RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR &/OR HARDWARE PER BC 1008.1.8; 27-371(J). N... $0 $0 Apr 20, 2018
Apr 29, 2016 35128409X RESOLVE CLASS - 2 REISSUE #35147096H FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. WATER PENETRATING FROM ROOF DRAIN. WATER DA... $0 $0 Sep 16, 2016
Sep 4, 2015 35147096H RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES.WATER PENETRATING BUILDING ENVELOPE WITH WATER DAMAGE EVIDENT F... $0 $0 Jan 8, 2016
Apr 23, 2014 35093929M RESOLVE CLASS - 3 CROSS CORRIDOR SIGNS &/OR BANNERS. 1ST FLOOR SIGNS HANGING. 2ND FLOOR SIGNS HANGING. REMEDY: REMOVE ALL CROSS CORRIDO... $0 $0 Jun 20, 2014
Apr 23, 2014 35093928K RESOLVE CLASS - 2 DEFECTIVE HARDWARE. MAIN ENTRANCE ROOF BULKHEAD DOOR, DOOR CHECK DEFECTIVE. 2B, BULKHEAD DOOR AT ROOF, DOOR RACKED. R... $0 $0 Jun 20, 2014
Apr 24, 2013 35016423X RESOLVE CLASS - 2 DEFECTIVE EXIT DOORS (4) NOT OPENING & CLOSING PROPERLY. LOCATION: CAFETERIA MAIN ENTRY. REMEDY: MAINTAIN AS PER CODE. $0 $0 Jun 21, 2013
Jun 19, 2012 34981141X RESOLVE CLASS - 2 RUSTED/DETERIORATED STEEL DOORS AND DOOR JAMBS. AT 1ST STY EXIT DISCHARGE DOORS AT ROOMS 133/123,113,110,111/107,101,... $0 $0 Sep 21, 2012
Jun 19, 2012 34981140Y RESOLVE CLASS - 1 EXIT DISCHARGE DOOR JAMMED SHUT/DOES NOT OPEN WHEN PANIC BAR DEPRESSEDAT 1ST STY ROOM 113 EXIT TO YARD EXCESSIVE FORC... $0 $0 Sep 21, 2012
Oct 3, 2011 34927720N RESOLVE CLASS - 2 EXTERIOR CONCRETE UNDER THE BRIDGE IS CRACKED & SPALLING LOCATED AT EXIT 8 ON THE 1ST FLOOR LEVEL. REMEDY: REPAIR &/O... $0 $0 Dec 2, 2011
Oct 3, 2011 34927719X RESOLVE CLASS - 2 REISSUE: 34760965J EXTERIOR BRICK FACADE HAS BECOME POROUS & ALLOWING RAIN INTO THE BUILDING AT STAIR "C" & "D" 2ND F... $0 $0 Dec 2, 2011
Oct 3, 2011 34927721P RESOLVE CLASS - 1 EXIT DOORS AT 6D ON THE 1ST FLOOR LEVEL IS TOTALLY OBSTRUCTED BY METAL WIRES & DUCT TAPE. (HAZARDOUS CONDITION) REMED... $0 $0 Dec 2, 2011
Oct 3, 2011 34927718Y RESOLVE CLASS - 2 REISSUE: 34856019J INTERIOR WALL & CEILING IS SPALLING LOCATED AT STAIR C & D ON THE 2ND FLOOR LEVEL. REMEDY: REPAIR ... $0 $0 Dec 2, 2011
Jun 23, 2010 34856019J RESOLVE CLASS - 2 THE PLASTER IS SPALLING OF THE WALLING LOCATED @ STAIR "C" 2ND FL LEVEL REMEDY: REPAIR / REPLACE PLASTER $0 $0 Sep 17, 2010
Jun 23, 2010 34856020R RESOLVE CLASS - 2 INTERIOR CLASSROOM DOOR EXIT IS DEFECTIVE NOTED: DOOR IS HITTING AGAINST DOOR SADDLE MAKING DOOR NOT PROPERLY OPENING... $0 $0 Sep 17, 2010
Jun 8, 2010 38211257M RESOLVE CLASS - 2 12Q03,39Q03,69M07,77Q03. 39Q- INSTALL GUARD FOR LIGHT TOP OF CAR. 77Q-INSTALL GUARD FOR LIGHT UNDER CAR $0 $0 Jul 30, 2010
Jan 27, 2009 34760965J RESOLVE CLASS - 3 REISSUE #34592826J - 34627874L FAILURE TO MAINTAIN BLDG WALLS OR APPURT NOTE WATER PENETRATION THROUGHOUT FLS # 1 2 3... $0 $0 May 15, 2009
Jan 27, 2009 34760966L RESOLVE CLASS - 3 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NOTE DEFECTIVE JAMMING DOORS NOT OPENING CLOSING PROPERLY & ROTTED ... $0 $0 May 15, 2009
Mar 14, 2008 34627874L RESOLVE Non-Hazardous REISSUE: 34592826J EXTERIOR FACADE HAS BECOME POROUS AND ALLOWING RAIN WATER TO ENTER THE BLDG CAUSING INTERIOR DAMAG... $0 $0 May 16, 2008
Mar 14, 2008 34639622N RESOLVE Non-Hazardous GAS METER ROOM DOES NOT HAVE FRESH AIR INTAKE ON THE SUB-CELLAR LEVEL. REMEDY: SUPPLY FRESH AIR TO GAS METER ROOM. $0 $0 May 16, 2008
Aug 22, 2007 34592826J RESOLVE Hazardous REISSUE # 34513292X FAILURE TO MAINTAIN EXTERIOR THROUGHOUT BLDG WATERPENETRATION THRU THE WALL & WINDOWS.REMEDY:MAKE... $0 $0 Nov 16, 2007
Aug 22, 2007 34592827L RESOLVE Hazardous REISSUE # 34513293H FAILURE TO MAINTAIN INTERIOR THROUGH OUT BLDG PLASTER IS SPALLING & CRACKING AROUND WINDOWS DUE T... $0 $0 Nov 16, 2007
Mar 10, 2006 34513294J RESOLVE Non-Hazardous NOTED: OPEN CRACKS AT WALLS AND CEILING AT GYMNASIUM AND CAFETERIA. (FIRST FLR) REMEDY: REPAIR WALLS AND CEILINGS. $0 $0 May 5, 2006
Mar 10, 2006 34513293H RESOLVE Non-Hazardous NOTED: PLASTER SPALLING, PEELING AT VARIOUS LOCATIONS, CLASSROOM #346,#307,#204, #102, STAIRWAY "C" 1ST FLR, SOUTH FA... $0 $0 May 5, 2006
Mar 10, 2006 34513292X RESOLVE Non-Hazardous NOTED: WATER PENETRATION THROUGH BRICK WALL FACADES AT VARIOUS LOCATIONS IN THE BLDG. REMEDY: MAKE REPAIRS/RE-POINT F... $0 $0 May 5, 2006
Mar 10, 2006 34513291Y RESOLVE Non-Hazardous REISSUE VIO #34466376Y. NOTED: 3RD FLR CORRIDOR SMOKE STOP DOOR IS MISSING NEAR CLASSROOM #347. REMEDY: INSTALL DOOR. $0 $0 May 5, 2006
Jan 28, 2005 34466376Y RESOLVE Non-Hazardous FAILURE TO MAINTAIN BLDG DEFECTS NOTED:THIRD FLOOR CORRIDOR SMOKE STOP DOOR IS MISSING NEAR CLASSROOM 347. REMEDY:MAI... $0 $0 Mar 18, 2005
Mar 27, 2001 34279858N RESOLVE Non-Hazardous FAILURE TO PROVIDE ADEQUATE EMERGENCY POWER EXIT LIGHTS ON ALL FLOORS,CORRIDORS AND STAIRS.FAILURE TO PROVIDE EMERGEN... $0 $0 May 11, 2001
Mar 27, 2001 34279857L RESOLVE Non-Hazardous FAILURE TO PROVIDE 3"LETTER ELEVATOR ID SIGNS ON ALL FLOOR.REMEDY:PROVIDE SIGNAGE AS PER LL-16/84 CODE. $0 $0 May 11, 2001
Jan 23, 1998 38069618Y RESOLVE Non-Hazardous 74M,14M,74L,30O,57O,73U, 79-CITY I.D MISSING 74-REPAIR ELECTRIC EYE 30-CLEAN CAR TOP. $2,500 $0 Mar 13, 1998