ECB violations
Maj Wm Deegan Boulevard, Bronx • Block 02527 • Lot 0014
32 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 17, 2025 | 39163908J | RESOLVE | CLASS - 2 | FTM BOILER FOUND A WEIL MCLAIN #1088 BOILER ON GAS RATED AT 3082000 BTUS TO HAVE ITS RELIEF VALVE LEAKING. CORRECT AL... | $1,250 | $0 | Oct 24, 2025 |
| Oct 17, 2025 | 39163932J | ACTIVE | CLASS - 2 | OBSERVED OUTSIDE IN THE STREET FIRE DEPARTMENT CONNECTION LACKING REQUIRED CLEARANCE. OPEN ENDED GAS LINES BEHIND DRY... | $1,250 | $0 | Oct 24, 2025 |
| Nov 25, 2024 | 39131193Z | RESOLVE | CLASS - 2 | FOUND A WEIL MCLAIN 1088 HOT WATER BOILER AIR SEPARATOR WITH A CRACK LEAKING WATER/CORRECT ALL VIOLATING CONDITIONS/S... | $625 | $0 | Dec 13, 2024 |
| Nov 25, 2024 | 39131211N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Dec 13, 2024 |
| Nov 25, 2024 | 39131212P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED EXCESSIVE LEAK IN BOILER ROOM. POTENTIAL FALL HAZARD.... | $1,250 | $0 | Dec 13, 2024 |
| Apr 11, 2024 | 37027261Z | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $1,250 | $0 | May 10, 2024 |
| Mar 10, 2023 | 39081244R | RESOLVE | CLASS - 2 | OBSERVED IN THE BASEMENT/CELLAR WATER IS LEAKING FROM REAR OF THE BOILER ( DEFECTIVE BOILER). AS PER PC 102.3 MAINTEN... | $625 | $0 | Mar 27, 2023 |
| Aug 1, 2018 | 37012037M | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8B REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INTIAL FAC... | $0 | $0 | Jan 4, 2019 |
| Jun 4, 2018 | 32096814R | RESOLVE | CLASS - 2 | 36. FOUND WEIL MCLAIN BOILER MODEL# 88 NOT REGISTER. REGISTER BOILER & SUBMIT C OF C. | $0 | $0 | Aug 17, 2018 |
| Dec 13, 2017 | 35297438M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: OBSERVED THROUGH... | $0 | $0 | Apr 6, 2018 |
| Nov 8, 2017 | 35297176L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED ON 11/08/2017 AT ABOVE ADDRESS NO INSPECTIORS TEST GA... | $0 | $0 | Mar 2, 2018 |
| Apr 26, 2017 | 35260252P | RESOLVE | CLASS - 1 | FGC408.2/DRIPS FUTURE CONNECTIONS DOWN STREAM OF APPLIANCE.OBSERVED ON4/26/17 AT ABOVE ADDRESS FUTURE GAS CONNECTIONS... | $0 | $0 | Jun 30, 2017 |
| Apr 26, 2017 | 35260251N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 4/26/17 AT ABOVE ADDRESS JIM CAPS LOCATED THROUGHOU... | $0 | $0 | Jun 30, 2017 |
| Apr 26, 2017 | 35260250L | RESOLVE | CLASS - 1 | FGC401.1/GAS PIPING NOT LABELED.OBSERVED ON 4/26/17 GAS PIPING IN BASEMENT/CELLAR NOT LABELED.REM:COMPLY WITH SUMMONS. | $0 | $0 | Jun 30, 2017 |
| Nov 17, 2016 | 35208063H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 11/17/16 AT 11 AM IN SUB BASEMENT- BASEMENT, FDNY ... | $0 | $0 | Jan 20, 2017 |
| Nov 17, 2016 | 35208061Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBWERVED ON 11/17/16 AT 11 AM IN GAS METER ROOM IN BASEMENT EX... | $0 | $0 | Jan 20, 2017 |
| Nov 17, 2016 | 35221532H | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. NOTED: EXIT DOOR AT 1ST FLOOR BLG "A"NEAR MAINTENANCE SHOP ROOM AND EXIT DOOR AT 2ND FLOO... | $0 | $0 | Jan 20, 2017 |
| Nov 17, 2016 | 35221533J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBL... | $0 | $0 | Jan 20, 2017 |
| Nov 10, 2016 | 35208062X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBERED ON 11/17/16 AT 11 AM IN BST SUB BST- DE() SPRINKLER/STA... | $0 | $0 | Jan 20, 2017 |
| Nov 7, 2016 | 37001542J | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL LOCAL LAW 1... | $0 | $0 | Jan 20, 2017 |
| Mar 29, 2016 | 35133670X | RESOLVE | CLASS - 1 | FAILURE TO TAKE & PROVIDE SAFETY MEASURES WHERE REQUIRED TO PROTECT & SECURE PUBLIC SAFETY FROM DOCUMENTED UNSAFE FAC... | $0 | $0 | Jul 15, 2016 |
| Feb 18, 2016 | 35171348P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:LACK OF EMERGENCY LIGHTING FOR EXITS, EXIST DISCHARGES AND PUBLIC C... | $0 | $0 | Apr 1, 2016 |
| Oct 21, 2015 | 36023448Y | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE TECHNICAL REPORT IN COMPLIANCE WITH CODEPROVISIONS:PERIODIC INSPECTION OF EXTERIOR WALL... | $0 | $0 | Jan 8, 2016 |
| Oct 3, 2014 | 36019828Y | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXT... | $0 | $0 | Dec 19, 2014 |
| Jan 30, 2009 | 36007981M | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE SIXTH ROUND TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS:PERIODIC INSPECTION OF E... | $0 | $0 | Apr 17, 2009 |
| Oct 17, 2008 | 36000543K | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE 5TH RD TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS: PERIODIC INSPECTION OF EXTER... | $0 | $0 | Dec 19, 2008 |
| Jun 12, 2008 | 34647291H | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. DEFECT NOTED. ON EXPOSER SIDE ONE BRICHS ARE LOOSE AND FELL ON 1 FLOOR SI... | $2,500 | $0 | Aug 1, 2008 |
| Jan 25, 2008 | 34685423H | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A 5TH ROUND TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS: PERIODIC INSPECTION OF EXTERIOR WALLS... | $0 | $0 | Mar 21, 2008 |
| Aug 11, 2006 | 34550362P | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A 5TH ROUND TECHNICAL REPORT IN COMPLIANCE W/ CODE PROVISIONS:PERIODIC INSPECTION OF EXTERIOR WALLS... | $0 | $0 | Oct 6, 2006 |
| May 19, 2006 | 34549794K | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS:PERIODIC INSP OF EXTERIOR WALLS &... | $0 | $0 | Jul 7, 2006 |
| Jul 29, 2005 | 34459036M | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXTERIOR ... | $0 | $0 | Sep 2, 2005 |
| Jan 14, 2005 | 34460938J | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXTERIOR ... | $0 | $0 | Mar 18, 2005 |