| May 26, 2026 | 39189769Y | RESOLVE | CLASS - 2 | FOUND FEDERAL FST -175 DUAL FUEL BOILER WITH EXPOSED WIRING, DISCHARGE PIPE MISSING ON COIL RELIEF VALVE, SAFETY RELI... | $0 | $0 | Aug 21, 2026 |
| May 26, 2026 | 39189803Z | RESOLVE | CLASS - 2 | CLASS 2: 1) MAINTENANCE PROGRAM MISSING AS PER ASME A17.1/CSA B44 8.6. REMEDY: PROVIDE REQUIRED PROGRAM. 2) MAINTENAN... | $0 | $0 | Aug 21, 2026 |
| May 26, 2026 | 39189810R | ACTIVE | CLASS - 2 | FAILURE TO PROPERLY SECURE/SUPPORT ELECTRICAL METALLIC TUBING (EMT). OBSERVED IN THE LOBBY ON THE A/B SIDE OF BUILDIN... | $500 | $500 | Aug 21, 2026 |
| May 26, 2026 | 39189804K | RESOLVE | CLASS - 2 | CLASS 2: 1) INSUFFICIENT ILLUMINATION IN THE MOTOR ROOM; LIGHT LEVELS BELOW ACCEPTABLE WORKING CONDITIONS AS PER ASME... | $0 | $0 | Aug 21, 2026 |
| May 26, 2026 | 39189811Z | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN BASEMENT EXIT SIGNS / EMERGENCY LIGHTS INSTALLED THRU OUT WITH NEW BX C... | $2,500 | $2,500 | Aug 21, 2026 |
| May 26, 2026 | 39189812K | ACTIVE | CLASS - 1 | FAILURE TO PROPERLY GROUP/LABEL DISCONNECTS. OBSERVED IN THE BASEMENT THAT THE TWO MAIN HOUSE 400 AMP SERVICE SWITCHE... | $1,000 | $1,000 | Aug 21, 2026 |
| May 14, 2026 | 39188581H | ACTIVE | CLASS - 2 | FAILURE TO CERTIFY CORRECTIONS 39073449K, FILE A CERTIFICATE OF CORRECTION | $1,250 | $1,250 | Aug 7, 2026 |
| Jul 8, 2025 | 35693842Z | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING WALLS AND APPURTENANCES. AS NOTED AT THE TIME OF INSPECTION I OBSERVED ON EXPOSURE #1 EA... | $5,000 | $5,000 | Jul 27, 2026 |
| May 29, 2025 | 39149291H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED FIRE ESCAPES OBSTRUCTED BY GARDEN FENCES AND HANDRAIL... | $2,500 | $2,500 | Aug 15, 2025 |
| May 29, 2025 | 39149325R | ACTIVE | CLASS - 2 | I FOUND A FEDRAL FST175 STEAM BOILER WITH BAROMETRIC DAMPER BROKEN/ SPILL SWITCH BROKEN/MECHANICAL FAN ON ALL THE TIM... | $6,250 | $6,250 | Sep 3, 2026 |
| May 27, 2025 | 39149000Z | ACTIVE | CLASS - 2 | CLASS ITEMS: IN-CAR COMMUNICATION INOPERATIVE. PROVIDE LABELING FOR MAIN LINE DISCONNECT. FIRE EXTINGUISHER IN MACHIN... | $3,125 | $3,125 | Jan 19, 2027 |
| May 27, 2025 | 39148999Z | ACTIVE | CLASS - 2 | CLASS 2 ITEMS: PROVIDE LABELING FOR MAIN LINE DISCONNECT. CATEGORY 1 TEST TAG MISSING. REPAIR BASEMENT AND FIRST FLOO... | $625 | $625 | Mar 19, 2026 |
| Feb 10, 2025 | 35689864H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 EAST-CRACK... | $2,500 | $2,500 | Jun 6, 2025 |
| Feb 10, 2025 | 35689863X | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTE: AT TIME OF INSPECTION I OBSERVED OBJECTS ON FIRE ESCAPES MULTI... | $1,250 | $1,250 | Jul 17, 2026 |
| Jun 3, 2024 | 39115847Z | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39073449K ISSUED ON 10/31/2022 AND TO ... | $1,250 | $1,250 | Aug 16, 2024 |
| Feb 2, 2024 | 39105084K | RESOLVE | CLASS - 2 | OBSERVED ACTIVE WATER LEAK ON OVERHEAD HOT WATER PIPING LOCATED IN THE BOILER ROOM IN THE BASEMENT/CELLAR. AS PER 102... | $310 | $0 | Apr 19, 2024 |
| Jan 2, 2024 | 39102550P | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS PER ECB# 39073449K ISSUED ON 10/31/2022 AND FILE A CER... | $2,500 | $2,500 | Aug 2, 2024 |
| Dec 28, 2023 | 39102387Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. MAINTENANCE LOG NOT FILLED OUT, PERFORM ROUTINE MAINTENANCE AN... | $312 | -$340 | Mar 29, 2024 |
| May 25, 2023 | 39087155M | RESOLVE | CLASS - 2 | AT THE TIME OF MY INSPECTION, I OBSERVED IN THE BASEMENT. OPEN DEFECTIVE WIRING ARE IN USED, DEFECTIVE FLUORESCENT LI... | $2,000 | $2,000 | Mar 26, 2024 |
| Nov 4, 2022 | 39073465K | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT ELEVATOR DISCONNECT SWITCHES THE IMPROPER FUSING OF THE CONDUCTORS I NOTED 100 AMP FUSES I... | $4,800 | $0 | Jan 27, 2023 |
| Nov 4, 2022 | 39073443J | RESOLVE | CLASS - 2 | OBSERVED PIPING THROUGHOUT BASEMENT EITHER SUPPORTED INCORRECTLY OR NOT AT ALL. AS PER PC 308.4HANGERS AND ANCHORS SH... | $1,562 | $1,562 | Dec 30, 2022 |
| Nov 4, 2022 | 39073466M | RESOLVE | CLASS - 2 | I OBSERVED IN THE APT 1D IN OFFICE #3 THE INSTALLATION OF A PLASTIC COVERING OVER ENERGIZED CONDUCTORS. AS NOTED IN E... | $1,250 | $1,250 | Jan 27, 2023 |
| Nov 4, 2022 | 39073464Z | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT ROOM MARKED WATER METER THE CONDUIT SUPPLYING POWER TO THE METER, APT 1D OFFICE #3, BASEME... | $1,600 | $1,600 | Jan 27, 2023 |
| Nov 4, 2022 | 39073442H | RESOLVE | CLASS - 2 | OBSERVED ACTIVE WATER LEAK IN THE BOILER ROOM LOCATED IN CELLAR. AS PER PC 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXI... | $0 | $0 | Dec 30, 2022 |
| Nov 4, 2022 | 39073467Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE ELEVATOR MOTOR ROOM FAILURE TO PROPERLY TERMINATE CABLE RACEWAYS IN THE CIRCUIT BREAKER PANEL AND T... | $600 | $600 | Jan 27, 2023 |
| Oct 31, 2022 | 39073451J | RESOLVE | CLASS - 2 | OBSERVED: AT CELLAR LEVEL, EXPOSURE # 2,3,4 EXIT DOORS DO NOT CLOSE PROPERLY WHEN INSPECTED, EXPOSURE # 3 EXTERIOR EX... | $312 | $0 | Dec 30, 2022 |
| Oct 31, 2022 | 39073447R | RESOLVE | CLASS - 2 | OBSERVED: -AT EXPOSURE #3, FIRST FL, WINDOWS SPLIT/BROKEN WOOD FRAME, WINDOWS ARE BEING COVERED BY SHEETS OF FLAMMABL... | $1,562 | $1,562 | Jun 16, 2023 |
| Oct 31, 2022 | 39073455R | RESOLVE | CLASS - 2 | OBSERVED: AT STAIRCASE A&C, SEVERAL OPENING DUE PIPE PENETRATION THROUGH FIREPROOF WALLS, ALSO, CELLAR LEVEL, UTILITI... | $0 | $0 | May 8, 2023 |
| Oct 31, 2022 | 39073448Z | RESOLVE | CLASS - 2 | AT ROOF LEVEL, WATERPROOFING COVER MEMBRANE HAS EXPANSION/PEELING JOINTS IN DIFFERENT LOCATIONS, DAMAGE THAT CAN CAUS... | $0 | $0 | Dec 30, 2022 |
| Oct 31, 2022 | 39073452L | RESOLVE | CLASS - 2 | OBSERVED. AT BUB CELLAR LEVEL, BOILER ROOM, METAL STRUCTURE (BEAMS, COLUMNS AND DECK) IS BEING INSTALLED TO CREATE A ... | $1,250 | $0 | Apr 28, 2023 |
| Oct 31, 2022 | 39073051K | RESOLVE | CLASS - 2 | IN CAR PHONE NOT WORKING. | $312 | $312 | Mar 3, 2023 |
| Oct 31, 2022 | 39073449K | ACTIVE | CLASS - 1 | AT EXP # 2,3, 4, FIRE SCAPE STAIRS, CELLAR LEVEL EXIT CORRIDORS & EXP #1,2,3 EXIT PASSAGEWAY, ARE BEING OBSTRUCTED BY... | $1,250 | $1,250 | Dec 30, 2022 |
| Oct 31, 2022 | 39073457K | RESOLVE | CLASS - 2 | OBSERVED: AT CELLAR LEVEL, WATER METER ROOMS, STORAGE OF MATERIAL, DEBRIS, WOODEN STAIRS, GARBAGE, CONSTRUCTION EQUIP... | $0 | $0 | Dec 30, 2022 |
| Oct 31, 2022 | 39073453N | RESOLVE | CLASS - 2 | OBSERVED:-AT EXPOSURE #3, OUTSIDE AREA TO EMERGENCY EXIT CRACKED RETAINING WALL,ALSO, FLOOR SLAB AND RETAINING WALL A... | $0 | $0 | Dec 30, 2022 |
| Oct 31, 2022 | 39073454P | RESOLVE | CLASS - 2 | OBSERVED: AT FIRST FLOOR LOBBY, CEILING DAMAGES, AT CELLAR LEVEL, CORRIDORS, ELECTRICAL ROOM, STORAGE ROOMS, WALLS/CE... | $0 | $0 | Dec 30, 2022 |
| Oct 31, 2022 | 39073456Z | ACTIVE | CLASS - 2 | OBSERVED: AT CELLAR LEVEL, CORRIDORS, COMMON AREAS, UTILITY ROOMS. EMERGENCY LIGHTING IS REQUIRED TO ILLUMINATE AND I... | $1,250 | $1,250 | Dec 30, 2022 |
| Oct 31, 2022 | 39073050Z | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). TOP OF CAR FAN NOT WORKING. | $1,250 | $1,250 | Mar 3, 2023 |
| Oct 31, 2022 | 39073450H | RESOLVE | CLASS - 2 | OBSERVED: -AT B&C BUILDINGS, FROM SECOND FL TO ROOF, STAIR CASE A&C WALLS CRACKED, OPENING (PIPES PENETRATION) AND DE... | $0 | $0 | Dec 30, 2022 |
| Feb 2, 2022 | 39055421J | RESOLVE | CLASS - 2 | I OBSERVED ON THE 1ST FLOOR IN OFFICE #3 OF APT 1D THE IMPROPER TERMINATION OF A RACEWAY SUPPLYING POWER TO THE OVERH... | $600 | $600 | May 6, 2022 |
| Feb 2, 2022 | 39055420H | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT ROOM OPPOSITE THE METER BANK A TO J INSIDE THE SHEETROCK COLUMN THE IMPROPER TERMINATION A... | $400 | $400 | May 6, 2022 |
| Feb 2, 2022 | 39055419K | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT ABOVE THE ELECTRIC METERS THE INSTALLATION OF RECESSED LIGHTING WITH THE USE OF LAMP WIRIN... | $800 | $800 | May 6, 2022 |
| Jan 7, 2020 | 38272511H | RESOLVE | CLASS - 1 | 97X10-ENTIRE DEVICE INOPERATIVE REMEDY:RESTORE SERVICE | $312 | $0 | Jan 22, 2021 |
| Apr 10, 2019 | 38269204K | RESOLVE | CLASS - 2 | 32H10,37M7,40M7,70M7. 32H10-TOO MUCH PLAY IN CAR SHOES; 37M7-NO ACCESS TO OVERHEAD MISSING KEYS; 40M7-NO ACCESS TO MA... | $625 | $0 | Sep 14, 2020 |
| Apr 10, 2019 | 38269203Z | RESOLVE | CLASS - 2 | 32H10,40M7,37M7. 32H10-TOO MUCH PLAY IN CARSHOES; 40M7-NO ACCESS TO MACHINE ROOM MISSING KEYS; 37M7-NO ACCESS TO OVER... | $625 | $0 | Sep 14, 2020 |
| Nov 14, 2018 | 38264665K | RESOLVE | CLASS - 2 | 39X10,11M07,34E10,05K10,10H11,56Y13,70O02. 39-FAN NOT WORKING;11-PROVIDE MISSING SCREWS ON CAR STATION; 34-BANGING GO... | $310 | $0 | Jan 4, 2019 |
| Nov 14, 2018 | 38264666M | RESOLVE | CLASS - 2 | 39X10,09I10,05J01,05K10,10H11,043D06,42I10,70O02,1M07. 39-FAN NOT WORKING; 09-CAR FLOOR DAMAGED/REPAIR; 05-CAB DOOR B... | $312 | $0 | Feb 22, 2019 |
| Sep 28, 2018 | 38265487L | RESOLVE | CLASS - 2 | 06I11,26B11,67B10,08V01,16T07,60Q03,68M07,68M07,70O02,80B07,26D06. 06-CAR DOOR IS RUSTED AND DAMAGE, REPLACE DOOR; 26... | $625 | $0 | Nov 16, 2018 |
| Sep 26, 2018 | 38265758Y | RESOLVE | CLASS - 1 | (C/U)5.A.10,5.B.1,59.BB.5,68.M.7,68.M.7-(5,A,10)DOOR ZONE RESTRICTOR NOT WORKING WIRED INCORRECTLY.CAR DOOR IN THE CL... | $1,250 | $0 | Nov 16, 2018 |
| Sep 26, 2018 | 38265757M | RESOLVE | CLASS - 1 | (C/U)5.A.10,(C/U)44.B.10,59.BB.5,68.M.7,68.M.7,(C/U)78.L.10-(5,A,10)DOOR ZONE RESTRICTOR NOT WORKING TAKEN A PART.(44... | $1,250 | $0 | Nov 16, 2018 |
| Aug 8, 2018 | 38264778R | RESOLVE | CLASS - 2 | 05E01,32I10,97V01,100M07,40P16. 05E01-CAR DOOR IS RUBBING ADJUST; 32I10-CAR GUIDESHOES SLIGHTLY DAMAGE REPAIR; 97V01-... | $310 | $0 | Oct 5, 2018 |