ECB violations

1258-1260 Maj Wm Deegan Boulevard, Bronx • Block 02530 • Lot 0009

63 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Apr 21, 2026 39185380H ACTIVE CLASS - 2 FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39130842P, FILE A CERTIFICATE OF CORRECTION $1,250 $1,250 Jul 31, 2026
Oct 15, 2025 39163631X RESOLVE CLASS - 1 CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. RE... $1,250 $0 Dec 19, 2025
Nov 20, 2024 39130843R ACTIVE CLASS - 2 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE WIRES FROM THE FIRE ALARM SWITCH ENERGIZED AND EXPOSED. THIS IS A MAJOR SH... $800 $0 Jan 31, 2025
Nov 20, 2024 39130842P ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $2,500 $0 Jan 31, 2025
Jul 3, 2024 39118389Y RESOLVE CLASS - 2 REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. MISALIGNED CAB MIRROR. OIL LEAKING INTO TOP OF SHAFT. REPAI... $0 $0 Sep 6, 2024
Mar 9, 2023 39081110L RESOLVE CLASS - 2 -EXPOSURE #1 PARAPET WALL, CRACKS AND BULKHEAD B LOCATED ON ROOF LEVEL., MAINTAIN EXTERIOR BUILDING WALL $1,280 $0 May 19, 2023
Mar 9, 2023 39081111N RESOLVE CLASS - 2 -FIRST FLOOR CAFETERIA, EXIT DOORS, ILLEGAL HARDWARE INSTALLED., PROVIDE LEGAL HARDWARE $0 $0 May 19, 2023
Mar 9, 2023 39081112P RESOLVE CLASS - 2 -FIRST LEVEL BOILER ROOM, WATER PENETRATION THROUGH FOUNDATIONAL WALLS., MAINTAIN EXTERIOR BUILDING WALL $1,280 $0 May 19, 2023
Mar 9, 2023 38274747N RESOLVE CLASS - 2 2X10,59BB5,68B7:2-X-10=INOPERATIVE PHONE REPAIR/59-BB-5=IN COME AT DATE ON TAG DATE IS IN THE FUTURE MUST PERFORM AND... $312 $0 Sep 25, 2023
Jun 8, 2022 39063742K RESOLVE CLASS - 2 OBSERVED RESIDENTIAL GAS FLEX USED ON COMMERCIAL LAUNDRY EQUIPMENT. COMMERCIAL LAUNDRY SHALL BE HARD PIPED., REPAIR A... $655 $0 Jul 29, 2022
Jun 8, 2022 39063740R RESOLVE CLASS - 2 SELF-CLOSING FIREPROOF DOORS AT FIRST FLOOR BACK SIDE EXIT DOOR ,STAIR A EXIT DOOR, CAFETERIA EXIT DOORS (2), AT 3RD ... $1,563 $0 Nov 18, 2022
Jun 8, 2022 39063743M RESOLVE CLASS - 2 GAS METER ROOM IMPROPERLY VENTILATED. GAS METER ROOM SHALL NOT VENT FROM ONE ROOM TO ANOTHER., REPAIR AND/OR REPLACE $0 $0 Jul 29, 2022
Jun 8, 2022 39063738H RESOLVE CLASS - 2 AT STAIR A&B & BOILER ROOM, EMERGENCY LIGHTS/EXIT SIGNS ARE REQUIRED, ALSO, THERE IS NO BACKUP POWER GENERATOR IN CAS... $1,250 $0 Nov 18, 2022
May 9, 2022 35636529L RESOLVE CLASS - 2 UNSAFE UNSUITABLE WIRING IN USE OBSERVED IN MAIN 600 AMP SERVICE SWITCH LOAD SIDE BEING IMPROPERLY TAPPED WITH 12 AWG... $400 $0 Sep 2, 2022
Mar 2, 2022 39057405Z RESOLVE CLASS - 2 FOUND MOBILE TRAILER WITH WEIL MCLAIN BOILER MODEL 1488 88 SERIES 2 ACTIVE WITH DEFECTS. BL#202584-01.EXCESSIVE SOOT ... $0 $0 Apr 29, 2022
Oct 6, 2021 35582492X RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:FIREPROOF SELF-CLOSING DOORS AT 3RD FLOOR STAIR B AND 2ND... $625 $0 Jan 7, 2022
Oct 6, 2021 35582493H RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED OBSERVED AT EXP1 MAIN ENTRANCE.BOTH ENTRANCE DOORS,GLASS ... $625 $0 Mar 4, 2022
Oct 6, 2021 35592067Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.I OBSERVED ON MAIN FLOOR IN LAUNDRY RESIDENTIAL GAS FLEX ON COM... $625 $0 Feb 11, 2022
Oct 1, 2021 39048540R RESOLVE CLASS - 2 LEAK FROM REAR TUBE DOOR IN BOILER-FLUE PIPE CORRODED WITH HOLES AND WITH THINNING METAL GAUGE-NO THERMOMETER ON DOME... $0 $0 Nov 19, 2021
Dec 23, 2020 39033881N RESOLVE CLASS - 3 GASKET ON FLANGE ON RETURN LINE LEAKING. NEED TO CLEAN AND SEAL CHIMNEY BASE DOOR FOR CLEANOUT. NEED TO RAISE ANTI SI... $250 $0 Mar 19, 2021
Oct 2, 2019 38271957H RESOLVE CLASS - 1 97-X-17,02-X-10,40-O-02,60-Q-03,98-BB-05,59-B-05,42-Q-03,56-Y-13,59-D-06=(97-X-17) THE ONY DEVICE IN THE BUILDING REM... $3,125 $0 Jan 31, 2020
Sep 3, 2019 38271426Z RESOLVE CLASS - 1 97X17,60Q03,42Q03,42D06,59D06,59M05,40O02,56Y13,68B07-RETURN TO SERVICE RECURRING CONDITION AGGRAVATED 1 PER 1RCNY 10... $3,125 $0 Apr 10, 2020
Aug 13, 2019 38270462L RESOLVE CLASS - 1 97-X-17 THE ONLY ELEVATOR IN THE BUILDING OUT OF SERVICE BASED UPON MYINSPECTION THE DEVICE IS FOUBD TO LOG OUT OF SE... $1,250 $0 Oct 2, 2020
Aug 6, 2019 35442907Y RESOLVE CLASS - 2 28-301.1. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P 115.6(1968 CODE) FAC APPENDIX E (E4) 2014 CODES. NOT... $0 -$620 Sep 20, 2019
Jul 11, 2019 38270290Y RESOLVE CLASS - 2 29M7,35M7,43X10. 29M7-PROVIDE DOOR OPERATOR COVER; 35M7-PROVIDE SAETY EDGE BOX COVER ON TOP OF CAR; 43X10-REVERSE PHA... $0 $0 Aug 30, 2019
May 20, 2019 35422415J RESOLVE CLASS - 1 UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS MATERIALS OBSERVED IN KITCHEN THE EQUIPMENT DISCONNECTS F... $1,600 $0 Aug 30, 2019
May 20, 2019 35415315R RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 5/20/19 AT ABOVE ADDRESS NO VENTILATION IN GAS MET... $1,250 $0 Nov 1, 2019
May 20, 2019 35415316Z RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 5/20/19 ABOVE ADDRESS ACTIVE LEAK BEHING BOILER ON... $625 $0 Nov 8, 2019
Apr 12, 2019 35359869P RESOLVE CLASS - 1 UNLAWFUL ACTS.FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.IN FEB 27,2019.AN ADMINISTRATIVE CODE VIOLATION WAS IS... $2,500 $0 Aug 30, 2019
Mar 30, 2019 38269162L RESOLVE CLASS - 1 97-X-17. 97-X- REPAIR & RESTORE TO SERVICE IMMEDIATELY THEN NOTIFY NYCDOB OF REPAIR SERVICE. SO ON INSPECTION CAN BE ... $1,250 $0 Sep 27, 2019
Feb 27, 2019 35359000Z RESOLVE CLASS - 1 AN UNLAWFUL ACT.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY CUMMONS #35379767M... $2,500 $0 Jul 12, 2019
Jan 23, 2019 38267424N RESOLVE CLASS - 2 17H11)HOISTWAY DOOR GIBS ON ALL FLOORS ARE WORN, REPLACE. 39O02)CAR TOP DIRTY, CLAEN. 41D06)MOTOR ROOM DOOR UNSECURED... $625 $0 Jul 26, 2019
Jan 12, 2019 35379767M RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED I... $1,600 $0 Jul 12, 2019
Jan 12, 2019 35379768Y RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35372507Y ISSUED ON 11-26-18 & TO FILE A C OF C PURSUAN... $1,250 $0 Nov 8, 2019
Nov 26, 2018 35372507Y RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS DEVICES,APPLIANCES,OR WIRING IN USE.OBSERVED IN... $1,280 $0 Nov 8, 2019
Nov 26, 2018 35372508X RESOLVE CLASS - 2 FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTER(GFCI)PROTECTION.OBSERVED IN COMMERCIAL KITCHEN CONVENIENCE RECEPT... $5,000 $0 Feb 1, 2019
Sep 27, 2018 38265760N RESOLVE CLASS - 2 11B10,39O2,56Y13,56O2,67X10. 11B10-FIREMAN SERVICE LIGHT IN CAR STATION DID NOT WORK; 39O2-CLEAN CAR TOP OIL LEAK; 56... $1,562 $0 Nov 16, 2018
Jun 14, 2018 38263670K RESOLVE CLASS - 1 97X17 UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREAT ING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. RM... $1,250 $0 Aug 17, 2018
Apr 7, 2018 35326381K RESOLVE CLASS - 3 WORK WITHOUT PERMIT.OBSERVED IN THE FRONT OFFICE ON THE 1ST FLR,THE BALL DRIP FOR THE FIRE DEPT CONNECTION RELOCATED ... $250 -$250 Jun 29, 2018
Apr 5, 2018 35326450P RESOLVE CLASS - 1 FGC408.2/DRIPS-FUTURE CONNECTIONS EXIST DOWN STREAM OF APPLIANCE.OBSERVED ON 04/05/18 AT ABOVE ADDRESS FUTURE GAS CON... $6,250 -$6,250 Jun 29, 2018
Feb 1, 2018 35283853M RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35245110Y ISSUED 04/17/17 AND TO FILE... $0 $0 Apr 27, 2018
Dec 15, 2017 35297570J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN FRONT NIGHT OFFICE ON 1ST FLR DEDICATED FIRE SPRINKLER... $250 $0 Apr 13, 2018
Dec 15, 2017 35297569M RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN FRONT OFFICE ON 1ST FLR TO THE RIGHT BALL DRIP INSTALL... $1,000 $0 Apr 13, 2018
Nov 15, 2017 32091970X RESOLVE CLASS - 2 15;32A;40;50A,B,C:NEED TO INSTALL COVER FOR TRANSFER PUMP;CLEAN BOILER ROOM OF SOOT,RAGS AND GARBAGE;SEAL AROUND CHIM... $0 $0 Mar 16, 2018
Nov 6, 2017 35296955X RESOLVE CLASS - 1 ELECTRICAL WORK WITHOUT A PERMIT.OBSERVEDON SIDECOURT YARD & ON ROOFS PERIMETER.THE INSTALLATION OF AN AIR CONDITIONE... $800 $0 May 1, 2018
Apr 26, 2017 35253337Z RESOLVE CLASS - 2 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS APPARATUS,DEVICES,APPLIANCES,OR WIRING IN USE. AT THE TIM... $800 $0 Dec 13, 2017
Apr 26, 2017 35253338K RESOLVE CLASS - 1 FAILURE TO GROUND ELECTRICAL SYSTEMS. AT THE TIME OF MY INSPECTION I OBSERVED THE WATER GROUND CLAMP & CONDUCTOR IN A... $4,800 $0 Dec 13, 2017
Apr 26, 2017 35253315H RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING CODE COMPLIANT MANNER.OBSERVED ON 04/26/17 AT GAS METER AREA,GAS PIPE GOING THROUGH WALL... $500 $0 Dec 13, 2017
Apr 26, 2017 35253336R RESOLVE CLASS - 2 ELECTRICAL WORK W/O A PERMIT. AT THE TIME OF MY INSPECTION I OBSERVED NEW IMC(ALUMINUM)PIPE AT THE DOORWAY ENTRANCE C... $400 $0 Dec 13, 2017
Apr 26, 2017 35253551J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.NOTED:AT ROOF PARAPIT WALL,BRICKS CRACKED AND MISSING MORTAR ALSO... $500 $0 Dec 13, 2017