ECB violations

University Avenue, Bronx • Block 02531 • Lot 0001

44 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Feb 20, 2026 39177955J RESOLVE CLASS - 1 OBSERVED ON THE FIRST FLOOR ELECTRICAL ROOM A NEW GAS LINE INSTALLED WITHIN 3 FEET OF THE ELECTRICAL PANELS. GAS PIPE... $2,500 $0 Oct 2, 2026
Jul 25, 2022 39066623L RESOLVE CLASS - 2 I OBSERVED ON THE EXTERIOR OF THE BUILDING ABOVE THE ICE MACHINE FOR THE STORE A CONVENIENCE OUTLET NOT OF THE GFCI /... $1,200 $0 Sep 16, 2022
May 9, 2022 39062811K RESOLVE CLASS - 2 I OBSERVED IN STAIRCASE #4(APTS R THRU W) THE IMPROPER INSTALLATION OF EMERGENCY LIGHTING THE WIREMOLD RACEWAY IS INS... $0 $0 Jul 15, 2022
May 9, 2022 39062809L RESOLVE CLASS - 2 I OBSERVED ON THE ROOF THE UNPERMITTED USE OF LFMC. THE RACEWAY INSTALLED WAS GREATER THAN 6FT AND UNSUPPORTED AS REQ... $0 $0 Jul 15, 2022
May 9, 2022 35644370Z RESOLVE CLASS - 2 WORK W/O PERMIT.OBSERVED IN BASEMENT/CELLAR NEWLY INSTALLED GAS PIPING & NEWLY INSTALLED GAS VALVE.NO PERMITS ON FILE... $625 $0 Sep 16, 2022
May 9, 2022 35654861M RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER LACK OF EMERGENCY LIGHTING FOR EXIT DISCHARGES AND PUBLIC CORRI... $625 $0 Dec 9, 2022
May 9, 2022 39062810Z RESOLVE CLASS - 2 I OBSERVED IN THE MAIN ELECTRICAL ROOM ELECTRICAL DISTRIBUTION SWITCHES NOT LABELED AS REQUIRED IN EC 230.2 (E), GROU... $0 $0 Sep 23, 2022
Dec 19, 2018 35393008M RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN VIOLATION #35361726K ISSUED ON 09/22/18 AND TO FILE A CER... $0 $0 Feb 15, 2019
Dec 5, 2018 35373078J RESOLVE CLASS - 1 EC314.29.CONDUIT BODES SHALL BE ACCESSIBLE.OBSERVED IN ELECTRICAL CLOSET ON 1ST FLOOR OF BUILDING ON WEST 164TH STREE... $0 $0 May 10, 2019
Dec 5, 2018 35373077H RESOLVE CLASS - 2 FAILURE TO PROVIDE/MAINTAIN SUFFICIENT ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIPMENT.OBSERVED IN BUILDING TO THE RIGHT... $250 -$250 Feb 15, 2019
Dec 5, 2018 35373079L RESOLVE CLASS - 2 EC404.8A.SERVICE DISCONNECTING MEANS NOT MORE THAN 6'7" FROM FLOOR OBSERVED CIRCUIT BREAKER ENCLOSURE MOUNTED ABOVE M... $400 -$400 Feb 15, 2019
Dec 5, 2018 35373076X RESOLVE CLASS - 1 FAILURE TO PROTECT AGAINST OVERCURRENT PER EC.OBSERVED BYPASS METER EQUIOMENT CLOSET LOCATED IN BUILDING TO THE RIGHT... $0 $0 May 10, 2019
Sep 22, 2018 35361726K RESOLVE CLASS - 1 FILED A CERTIFICATE OF CORRECTION OR OTHER RELATED MATERIAL CONTAININGMATERIAL FALSE STATEMENT(S)NOTED:AT SOUTH EAST ... $0 $0 Apr 12, 2019
Jul 22, 2018 35361725Z RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MAMNER.NOTED:EXHAUST/CHIMNEY FOR 1ST FLOOR COMMERCIAL STOVE INCORRECTLY TE... $312 $0 Apr 12, 2019
May 29, 2018 32097027M RESOLVE CLASS - 2 B254,11A,50A,50B,50C,50D. AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAINTAIN 11A-SKIMMING BLOWDOWN VALVE NOT INSTALLE... $0 $0 Jul 20, 2018
May 17, 2018 35334179R RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTE EXHAUST/CHIMNEY FOR COMMERCIAL STOVE INCORRECTLY TERMINATE... $312 $0 Jul 20, 2018
Apr 5, 2018 35325718M RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: OBSERVED AT EAST WING OF 165 WEST 169TH STREET, EXTERIO... $0 $0 Jun 1, 2018
Apr 5, 2018 35326378J RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED EXHAUST/CHIMNEY FOR COMMERCIAL STOVE LOCATED IN RESTAURAN... $1,250 $0 Jun 15, 2018
Nov 6, 2017 35296954Y RESOLVE CLASS - 1 FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED IN ELECTRICAL ROOM THE FOLLOWIN... $1,200 $0 Apr 27, 2018
Nov 6, 2017 35296929M RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION OR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER... $0 $0 Apr 27, 2018
Nov 6, 2017 35296930J RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.NOTED:OBSERVED ON THE 169ST SIDE, FIRE ESCAPE EGRESS PASSAGE ABOVE TH... $250 $0 Apr 27, 2018
Nov 6, 2017 35296928K RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES NOTED: OBSERVED AT THE EAST PARAPET WALL (FACING OGDEN AVENUE), ... $250 $0 Apr 27, 2018
Apr 24, 2017 35253312M RESOLVE CLASS - 1 FGC408.2/DRIPS FUTURE CONNECTION EXIST DOWN STREAM OF APPLIANCE.OBSERVED ON 4/24/17 AT ABOVE ADDRESS FUTURE GAS CONNE... $0 $0 Sep 7, 2017
Apr 24, 2017 35253349X RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS,DEVICES,APPARATUS, APPLIANCE OR WIRING IN USE.AT TIME OF ... $1,600 $0 Sep 8, 2017
Apr 24, 2017 35260253R RESOLVE CLASS - 2 FGC408.2/DRIPS FUTURE CONNECTION EXIST DOWN STREAM OF APPLIANCE.OBSERVED ON 4/24/17 AT ABOVE ADDRESS FUTURE GAS CONNE... $800 $0 Sep 1, 2017
Apr 24, 2017 35260275H RESOLVE CLASS - 1 ELECTRICAL WORK W/O PERMIT.AT TIME OF MY INSPECTION I OBSERVED NEW LIGHTS & EMERGENCY LIGHT SYSTEMS, EXTERIOR CONDUIT... $800 $0 Sep 8, 2017
Dec 13, 2016 35189882K RESOLVE CLASS - 2 FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER COMPLETED IN NOV# 35216497P ISSUED ON 10/28/16 & TO FILE A C OF C PURSU... $0 $0 Feb 3, 2017
Dec 13, 2016 35189881Z RESOLVE CLASS - 2 FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN NOV# 35216495L ISSUED ON 10/28/16 & TO FILE A C OF C PURSU... $0 $0 Feb 3, 2017
Oct 28, 2016 35216496N RESOLVE CLASS - 2 FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC102... $500 $0 Jan 6, 2017
Oct 28, 2016 35216497P RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER OBSERVED ON 10/28/16EXCESSIVE STORAGE IN GAS METER ROOM. NO STORAGE... $1,000 $0 Jan 6, 2017
Oct 28, 2016 35216494J RESOLVE CLASS - 1 SEC. 403.8 MISC VIOLATION UNPAINTED GAS PIPING NOT PROTECTED FROM ELEMENTS. OBSERVED ON 10/28/16 GAS PIPING ALONG SID... $1,600 $0 Jan 6, 2017
Oct 28, 2016 35216495L RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 10/28/16 GAS SMELL IN APT 3J. CALLED FIRED DEPT & THEY... $1,000 $0 Jan 6, 2017
Aug 22, 2016 35188055M RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35177739J ISSUED ON 05/03/16 & TO FILE A C OF C PURSUANT TO 28... $0 -$800 Feb 14, 2017
May 3, 2016 35177739J RESOLVE CLASS - 2 OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.AS PER C/O #17490-55 CELLAR ON GROUND TO BE STO... $0 $0 Feb 6, 2017
Jul 9, 2014 35101733H RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT BASEMENT 4 DUMWAITER SHAFTS THAT ARE OUT OF SERVICE NOT SEALED ... $250 $0 Aug 29, 2014
Jul 9, 2014 35066681Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER RE:IN CELLAR THERE IS THE USE OF FERNCO COUPLINGS BEING USED ON 3" ... $250 $0 Aug 29, 2014
Jul 9, 2014 35066682X RESOLVE CLASS - 2 WORK W/O PERMIT WORK NOTED IN CELLAR @ THE FL THERE WAS A TRAP THAT WAS REPLACED W/ NO PERMIT.REM:OBTAIN PERMIT OR RE... $800 $0 Aug 29, 2014
Jul 9, 2014 35101734J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT EAST SIDE YARD EXTERIOR CONCRETE STAIRS MISSING HANDRAILS. REME... $250 $0 Aug 29, 2014
Oct 26, 2013 35016717L RESOLVE CLASS - 1 THE FOLLOWING CONDITION:MASONRY PARAPET WALL WORK BEING DONE @ROOF OVER THE BLDGS ENTRANCE DOOR W/O PROTECTION OF A S... $2,400 $0 Feb 28, 2014
Oct 26, 2013 35016718N RESOLVE CLASS - 1 FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATION. NOTED: THE FOLLOWING CONDITIONS. MASO... $2,400 $0 Feb 14, 2014
Oct 26, 2013 35016716J RESOLVE CLASS - 1 WORK W/O A PERMIT. NOTED: THE FOLLOWING CONDITIONS WORKERS ON ROOF DOING MASONRY WORK ON PARAPET WALLS: WORK OBSERVED... $1,600 $0 Feb 14, 2014
May 2, 2012 34937167X RESOLVE CLASS - 1 WORK W/O PERMIT. WORK NOTED: SHED STRUCTURE APPROX. 27' LONG X 9' WIDEX 10' HIGH CONSTRUCTED OF SHEETROCK WALLS AND W... $0 $0 Jun 29, 2012
Oct 22, 2009 34787584X RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE - COMPLIANT MANNER. DEFECT NOTED: MAIN METAL STAIRS, STEEL RISER CORRODED & RUSTED @... $1,000 $0 Jul 23, 2010
Mar 3, 1993 34086818H RESOLVE Non-Hazardous WORK WITHOUT A PERMIT NOTED SUBDIVIDED APT 169A & 169B N/E SECTION PARTITION ERECTED REMEDYOBTIAN A PERMIT IF FEASIBL... $0 $0 May 14, 1993