ECB violations
University Avenue, Bronx • Block 02531 • Lot 0001
44 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 20, 2026 | 39177955J | RESOLVE | CLASS - 1 | OBSERVED ON THE FIRST FLOOR ELECTRICAL ROOM A NEW GAS LINE INSTALLED WITHIN 3 FEET OF THE ELECTRICAL PANELS. GAS PIPE... | $2,500 | $0 | Oct 2, 2026 |
| Jul 25, 2022 | 39066623L | RESOLVE | CLASS - 2 | I OBSERVED ON THE EXTERIOR OF THE BUILDING ABOVE THE ICE MACHINE FOR THE STORE A CONVENIENCE OUTLET NOT OF THE GFCI /... | $1,200 | $0 | Sep 16, 2022 |
| May 9, 2022 | 39062811K | RESOLVE | CLASS - 2 | I OBSERVED IN STAIRCASE #4(APTS R THRU W) THE IMPROPER INSTALLATION OF EMERGENCY LIGHTING THE WIREMOLD RACEWAY IS INS... | $0 | $0 | Jul 15, 2022 |
| May 9, 2022 | 39062809L | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF THE UNPERMITTED USE OF LFMC. THE RACEWAY INSTALLED WAS GREATER THAN 6FT AND UNSUPPORTED AS REQ... | $0 | $0 | Jul 15, 2022 |
| May 9, 2022 | 35644370Z | RESOLVE | CLASS - 2 | WORK W/O PERMIT.OBSERVED IN BASEMENT/CELLAR NEWLY INSTALLED GAS PIPING & NEWLY INSTALLED GAS VALVE.NO PERMITS ON FILE... | $625 | $0 | Sep 16, 2022 |
| May 9, 2022 | 35654861M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER LACK OF EMERGENCY LIGHTING FOR EXIT DISCHARGES AND PUBLIC CORRI... | $625 | $0 | Dec 9, 2022 |
| May 9, 2022 | 39062810Z | RESOLVE | CLASS - 2 | I OBSERVED IN THE MAIN ELECTRICAL ROOM ELECTRICAL DISTRIBUTION SWITCHES NOT LABELED AS REQUIRED IN EC 230.2 (E), GROU... | $0 | $0 | Sep 23, 2022 |
| Dec 19, 2018 | 35393008M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN VIOLATION #35361726K ISSUED ON 09/22/18 AND TO FILE A CER... | $0 | $0 | Feb 15, 2019 |
| Dec 5, 2018 | 35373078J | RESOLVE | CLASS - 1 | EC314.29.CONDUIT BODES SHALL BE ACCESSIBLE.OBSERVED IN ELECTRICAL CLOSET ON 1ST FLOOR OF BUILDING ON WEST 164TH STREE... | $0 | $0 | May 10, 2019 |
| Dec 5, 2018 | 35373077H | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE/MAINTAIN SUFFICIENT ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIPMENT.OBSERVED IN BUILDING TO THE RIGHT... | $250 | -$250 | Feb 15, 2019 |
| Dec 5, 2018 | 35373079L | RESOLVE | CLASS - 2 | EC404.8A.SERVICE DISCONNECTING MEANS NOT MORE THAN 6'7" FROM FLOOR OBSERVED CIRCUIT BREAKER ENCLOSURE MOUNTED ABOVE M... | $400 | -$400 | Feb 15, 2019 |
| Dec 5, 2018 | 35373076X | RESOLVE | CLASS - 1 | FAILURE TO PROTECT AGAINST OVERCURRENT PER EC.OBSERVED BYPASS METER EQUIOMENT CLOSET LOCATED IN BUILDING TO THE RIGHT... | $0 | $0 | May 10, 2019 |
| Sep 22, 2018 | 35361726K | RESOLVE | CLASS - 1 | FILED A CERTIFICATE OF CORRECTION OR OTHER RELATED MATERIAL CONTAININGMATERIAL FALSE STATEMENT(S)NOTED:AT SOUTH EAST ... | $0 | $0 | Apr 12, 2019 |
| Jul 22, 2018 | 35361725Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MAMNER.NOTED:EXHAUST/CHIMNEY FOR 1ST FLOOR COMMERCIAL STOVE INCORRECTLY TE... | $312 | $0 | Apr 12, 2019 |
| May 29, 2018 | 32097027M | RESOLVE | CLASS - 2 | B254,11A,50A,50B,50C,50D. AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAINTAIN 11A-SKIMMING BLOWDOWN VALVE NOT INSTALLE... | $0 | $0 | Jul 20, 2018 |
| May 17, 2018 | 35334179R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTE EXHAUST/CHIMNEY FOR COMMERCIAL STOVE INCORRECTLY TERMINATE... | $312 | $0 | Jul 20, 2018 |
| Apr 5, 2018 | 35325718M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: OBSERVED AT EAST WING OF 165 WEST 169TH STREET, EXTERIO... | $0 | $0 | Jun 1, 2018 |
| Apr 5, 2018 | 35326378J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED EXHAUST/CHIMNEY FOR COMMERCIAL STOVE LOCATED IN RESTAURAN... | $1,250 | $0 | Jun 15, 2018 |
| Nov 6, 2017 | 35296954Y | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED IN ELECTRICAL ROOM THE FOLLOWIN... | $1,200 | $0 | Apr 27, 2018 |
| Nov 6, 2017 | 35296929M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION OR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER... | $0 | $0 | Apr 27, 2018 |
| Nov 6, 2017 | 35296930J | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.NOTED:OBSERVED ON THE 169ST SIDE, FIRE ESCAPE EGRESS PASSAGE ABOVE TH... | $250 | $0 | Apr 27, 2018 |
| Nov 6, 2017 | 35296928K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES NOTED: OBSERVED AT THE EAST PARAPET WALL (FACING OGDEN AVENUE), ... | $250 | $0 | Apr 27, 2018 |
| Apr 24, 2017 | 35253312M | RESOLVE | CLASS - 1 | FGC408.2/DRIPS FUTURE CONNECTION EXIST DOWN STREAM OF APPLIANCE.OBSERVED ON 4/24/17 AT ABOVE ADDRESS FUTURE GAS CONNE... | $0 | $0 | Sep 7, 2017 |
| Apr 24, 2017 | 35253349X | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS,DEVICES,APPARATUS, APPLIANCE OR WIRING IN USE.AT TIME OF ... | $1,600 | $0 | Sep 8, 2017 |
| Apr 24, 2017 | 35260253R | RESOLVE | CLASS - 2 | FGC408.2/DRIPS FUTURE CONNECTION EXIST DOWN STREAM OF APPLIANCE.OBSERVED ON 4/24/17 AT ABOVE ADDRESS FUTURE GAS CONNE... | $800 | $0 | Sep 1, 2017 |
| Apr 24, 2017 | 35260275H | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O PERMIT.AT TIME OF MY INSPECTION I OBSERVED NEW LIGHTS & EMERGENCY LIGHT SYSTEMS, EXTERIOR CONDUIT... | $800 | $0 | Sep 8, 2017 |
| Dec 13, 2016 | 35189882K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER COMPLETED IN NOV# 35216497P ISSUED ON 10/28/16 & TO FILE A C OF C PURSU... | $0 | $0 | Feb 3, 2017 |
| Dec 13, 2016 | 35189881Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN NOV# 35216495L ISSUED ON 10/28/16 & TO FILE A C OF C PURSU... | $0 | $0 | Feb 3, 2017 |
| Oct 28, 2016 | 35216496N | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC102... | $500 | $0 | Jan 6, 2017 |
| Oct 28, 2016 | 35216497P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER OBSERVED ON 10/28/16EXCESSIVE STORAGE IN GAS METER ROOM. NO STORAGE... | $1,000 | $0 | Jan 6, 2017 |
| Oct 28, 2016 | 35216494J | RESOLVE | CLASS - 1 | SEC. 403.8 MISC VIOLATION UNPAINTED GAS PIPING NOT PROTECTED FROM ELEMENTS. OBSERVED ON 10/28/16 GAS PIPING ALONG SID... | $1,600 | $0 | Jan 6, 2017 |
| Oct 28, 2016 | 35216495L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 10/28/16 GAS SMELL IN APT 3J. CALLED FIRED DEPT & THEY... | $1,000 | $0 | Jan 6, 2017 |
| Aug 22, 2016 | 35188055M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35177739J ISSUED ON 05/03/16 & TO FILE A C OF C PURSUANT TO 28... | $0 | -$800 | Feb 14, 2017 |
| May 3, 2016 | 35177739J | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.AS PER C/O #17490-55 CELLAR ON GROUND TO BE STO... | $0 | $0 | Feb 6, 2017 |
| Jul 9, 2014 | 35101733H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT BASEMENT 4 DUMWAITER SHAFTS THAT ARE OUT OF SERVICE NOT SEALED ... | $250 | $0 | Aug 29, 2014 |
| Jul 9, 2014 | 35066681Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER RE:IN CELLAR THERE IS THE USE OF FERNCO COUPLINGS BEING USED ON 3" ... | $250 | $0 | Aug 29, 2014 |
| Jul 9, 2014 | 35066682X | RESOLVE | CLASS - 2 | WORK W/O PERMIT WORK NOTED IN CELLAR @ THE FL THERE WAS A TRAP THAT WAS REPLACED W/ NO PERMIT.REM:OBTAIN PERMIT OR RE... | $800 | $0 | Aug 29, 2014 |
| Jul 9, 2014 | 35101734J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT EAST SIDE YARD EXTERIOR CONCRETE STAIRS MISSING HANDRAILS. REME... | $250 | $0 | Aug 29, 2014 |
| Oct 26, 2013 | 35016717L | RESOLVE | CLASS - 1 | THE FOLLOWING CONDITION:MASONRY PARAPET WALL WORK BEING DONE @ROOF OVER THE BLDGS ENTRANCE DOOR W/O PROTECTION OF A S... | $2,400 | $0 | Feb 28, 2014 |
| Oct 26, 2013 | 35016718N | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATION. NOTED: THE FOLLOWING CONDITIONS. MASO... | $2,400 | $0 | Feb 14, 2014 |
| Oct 26, 2013 | 35016716J | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. NOTED: THE FOLLOWING CONDITIONS WORKERS ON ROOF DOING MASONRY WORK ON PARAPET WALLS: WORK OBSERVED... | $1,600 | $0 | Feb 14, 2014 |
| May 2, 2012 | 34937167X | RESOLVE | CLASS - 1 | WORK W/O PERMIT. WORK NOTED: SHED STRUCTURE APPROX. 27' LONG X 9' WIDEX 10' HIGH CONSTRUCTED OF SHEETROCK WALLS AND W... | $0 | $0 | Jun 29, 2012 |
| Oct 22, 2009 | 34787584X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE - COMPLIANT MANNER. DEFECT NOTED: MAIN METAL STAIRS, STEEL RISER CORRODED & RUSTED @... | $1,000 | $0 | Jul 23, 2010 |
| Mar 3, 1993 | 34086818H | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT NOTED SUBDIVIDED APT 169A & 169B N/E SECTION PARTITION ERECTED REMEDYOBTIAN A PERMIT IF FEASIBL... | $0 | $0 | May 14, 1993 |