ECB violations
East 141 Street, Bronx • Block 02572 • Lot 0006
47 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 5, 2024 | 39110905P | ACTIVE | CLASS - 1 | NO DLM WAS INSTALLED ON THIS CONTROLLER AS MANDATED BY THE 2014 NYCBC SECTION 3.10.12. IN CAR PHONE NOT WORKING. BASE... | $3,125 | $0 | Jun 7, 2024 |
| Feb 5, 2024 | 39105152N | ACTIVE | CLASS - 2 | OBSERVED IN THE BOILER ROOM LOCATED IN THE BASEMENT/CELLAR 2 CABINETS BEING STORED BEHIND ON OF THE BOILERS. AS PER 3... | $625 | $0 | Apr 27, 2024 |
| Feb 5, 2024 | 39105151L | ACTIVE | CLASS - 2 | OBSERVED LIGHTS INSTALLED TO CLOSE TO THE SPRINKLER HEADS. AS PER 314.5 OF THE FIRE CODE SPRINKLER HEADS SHALL NOT BE... | $625 | $0 | Apr 27, 2024 |
| Dec 29, 2023 | 39102496N | ACTIVE | CLASS - 2 | EMERGENCY EXITS CORRIDORS ARE BLOCKED, DAYCARE, GROUND LEVEL., PROVIDE PROPER CORRIDOR WIDTH | $625 | $0 | Jan 10, 2024 |
| Dec 29, 2023 | 39102494J | ACTIVE | CLASS - 2 | NO EMERGENCY LIGHTING IN HALLWAYS, CORRIDORS, AND STAIRCASES THROUGHOUT BUILDING., REPAIR AND/OR REPLACE LIGHTING | $1,250 | $0 | Jan 10, 2024 |
| Dec 29, 2023 | 39102493H | ACTIVE | CLASS - 2 | EMERGENCY EXITS DOORS DO NOT FUNCTION/OPEN PROPERLY THROUGHOUT BUILDING., REPAIR AND/OR REPLACE | $625 | $0 | Jan 4, 2024 |
| Dec 29, 2023 | 39102495L | ACTIVE | CLASS - 2 | HOLE PENETRATION FOUND THROUGHOUT BUILDING., PROVIDE/MAINTAIN FIRE STOPPING | $1,250 | $0 | Jan 10, 2024 |
| Dec 28, 2023 | 39102345X | ACTIVE | CLASS - 1 | CLASS 1 ITEM: NO DOOR LOCK MONITORING INSTALLED ON THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 ... | $3,125 | $0 | Jan 10, 2024 |
| Aug 8, 2022 | 39067605M | RESOLVE | CLASS - 2 | AT CELLAR, FIRST FLOOR, 2ND FLOOR 3RD FLOOR, PUBLIC CORRIDOR (STAIRCASE), OPEN PUBLIC SPACES, UTILITY ROOMS. EMERGENC... | $0 | $0 | Aug 20, 2022 |
| Aug 8, 2022 | 39067588J | ACTIVE | CLASS - 2 | FOUND EXPOSED WIRES ON COMBUSTION AIR FAN, COVER TO COMBUSTION AIR FAN NOT PROPERLY SECURED, SAFETY RELIEF VALVE LEAK... | $625 | $0 | Aug 20, 2022 |
| Jul 29, 2022 | 39066958N | ACTIVE | CLASS - 2 | AS PER ONE WEIL MCLAIN 1288 IN CELLAR BOILER ROOM; MOTOR COVERING AND BELT GUARD FOR COMBUSTION AIR FAN NOT IN PLACE-... | $625 | $0 | Aug 20, 2022 |
| Jul 27, 2022 | 39066796J | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $3,125 | $0 | Jul 27, 2022 |
| May 9, 2022 | 39061830L | ACTIVE | CLASS - 2 | AT FIRST FLOOR, EXIT DOORS SHOW FAILURE TO CLOSE & OPEN PROPERLY., REPAIR/REPLACE DOOR | $625 | $0 | May 11, 2022 |
| May 9, 2022 | 39061829Y | RESOLVE | CLASS - 2 | REQUIREMENT OF EMERGENCY LIGHTS & SIGNAL AT STARIRCASE H, I, FROM 3RD FL TO CELLAR, REPAIR AND/OR REPLACE LIGHTING | $0 | $0 | May 11, 2022 |
| May 9, 2022 | 39061833R | ACTIVE | CLASS - 2 | I OBSERVED THROUGHOUT BUILDING SPRINKLER HEADS ARE INSTALLED TO CLOSE TO LIGHT FIXTURES, ALSO BOILER #2 HAS AN ACTIVE... | $625 | $0 | May 11, 2022 |
| Sep 20, 2021 | 39047756L | RESOLVE | CLASS - 2 | COVERS MISSING FOR ELECTRICAL CONNECTION BOXES AT TWO SOLENOID GAS VALVES. | $625 | $0 | Oct 15, 2021 |
| Aug 13, 2021 | 39045992Y | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Sep 14, 2021 |
| Mar 19, 2019 | 39001646R | RESOLVE | CLASS - 1 | FAILURE TO COMPLY, COMPLY WITH COMMISSIONER'S ORDER; COMPLY WITH CODE | $0 | $0 | May 3, 2019 |
| Jan 16, 2019 | 35372663X | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS I OBSER THE GROUNDING ELECTRODE CONDUCTOR DISCONNECTED AT THE WATERMAIN.REM:PROV... | $0 | $0 | Mar 29, 2019 |
| May 21, 2018 | 35334104M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. OBSERVED ON 05/21/18 AT ABOVE ADDRESS IN CELLAR GAS METER ROOM DO ... | $0 | $0 | Aug 3, 2018 |
| May 21, 2018 | 35331847J | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. MULTIPLE EXHAUST FAN UNITS NOT WORKING. UNITS ARE LOCATED ON ROOF.... | $0 | $0 | Aug 3, 2018 |
| May 21, 2018 | 35341603M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.NO FIRE STOPPING PER712.3;27-345.FIRE STOP MISSING IN THE GAS METER... | $0 | $0 | Aug 31, 2018 |
| Apr 10, 2018 | 32096625H | ACTIVE | CLASS - 2 | B254,50A,50B,50C. AS PER CLASS 2 (B254) 28-301.1 FAILURE TO MAINTAIN 50A-HEATING PUMP OVER BOILER IS LEAKING; 50B-EXP... | $3,125 | $3,125 | Jun 1, 2018 |
| Dec 5, 2017 | 35297427R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.NOTED: OBSERVED ON THE EXTERIOR OF STAIR "H" ROOF BULKHEAD,DETACH... | $0 | $0 | Mar 2, 2018 |
| Dec 5, 2017 | 35297190H | RESOLVE | CLASS - 1 | UNPAINTED GAS PIPING NOT PROTECTED FROM CORROSIAN.OBSERVED ON 12/05/2017 @ ABOVE ADDRESS GAS PIPING TO HVAC ON THE 2N... | $0 | $0 | Mar 2, 2018 |
| Oct 10, 2017 | 35294239X | RESOLVE | CLASS - 2 | FAILURE TO USE APPROVED CONDUCTORS AND/OR EQUIPMENT. OBSERVED ON ROOFTOPS ON NORTH AND SOUTH SIDE INSTALLATION OF FLO... | $0 | $0 | Jan 5, 2018 |
| Oct 10, 2017 | 35293969N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 10/10/2017 AT ABOVE ADDRESS NO INSPECTOR'S TEST VA... | $0 | $0 | Jan 5, 2018 |
| Oct 10, 2017 | 35294238Y | RESOLVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN HALLWAYS NEAR CENTRAL STAIRWELLS ON NORTH AND SOUTH SIDES ON 2ND FLOORS... | $0 | $0 | Jan 5, 2018 |
| Oct 10, 2017 | 35294237M | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED GROUNDING CONDUCTORS IN DOMESTI... | $0 | $0 | Jan 5, 2018 |
| Jun 1, 2017 | 35267837M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 6-1-17 IN BASEMENT OF ABOVE ADDRESS COPPER PIPE GOING ... | $0 | $0 | Aug 18, 2017 |
| Jun 1, 2017 | 35268055M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES & PUBLIC CORR... | $0 | $0 | Aug 18, 2017 |
| Jun 1, 2017 | 35268051P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: OBSERVED ON THE ROOF OF THE SOUTH BLDG,MISSING & DETACHED ROO... | $0 | $0 | Aug 18, 2017 |
| Jun 1, 2017 | 35268052R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. NOTED: OBSERVED ON CELLAR LE... | $0 | $0 | Aug 18, 2017 |
| Jun 1, 2017 | 35270645P | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/OUT A PERMIT.OBSERVED MULTIPLE SPLIT A.C UNITS ON 2ND FL ROOFTOP THESE UNITS ARE NOT COVERED UNDER ... | $0 | $0 | Oct 20, 2017 |
| Jun 1, 2017 | 35267838Y | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC 1... | $0 | $0 | Aug 18, 2017 |
| Jun 1, 2017 | 35267839X | RESOLVE | CLASS - 1 | SEC. 401.1 MISC VIOLATIONS GAS PIPING NOT LABELED. OBSERVED ON 6-1-17 IN BASEMENT OF ABOVE ADDRESS GAS PIPING THROUGH... | $0 | $0 | Aug 18, 2017 |
| Jun 1, 2017 | 35270644N | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT OBSERVED NO TAMPER RESISTANT OUTLETS THROUGHOUT HULLS AS WELL AS NO... | $0 | $0 | Oct 20, 2017 |
| Jun 1, 2017 | 35268054K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED: OBSERVED DEFECTIVE DOOR/GATE HARDWARE-EXTERIOR EXIT GATES A... | $0 | $0 | Aug 18, 2017 |
| Jun 1, 2017 | 35268053Z | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED: OBSERVED ON 1ST FL SOUTH BLDG EXIT DOOR LEADING TO PARKING LOT IS RACKED,KNOWING O... | $0 | $0 | Aug 18, 2017 |
| Aug 31, 2016 | 35207151N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:FRESH AIR VENT FOR GAS METER ROOM DOES NOT EXIST. AT BASEMENT I... | $0 | $0 | Nov 18, 2016 |
| Aug 31, 2016 | 35207642H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 8/31/16THROUGH DOB RECORD.NO ANNUAL BOILER INSPECTION.... | $0 | $0 | Nov 18, 2016 |
| Aug 31, 2016 | 35207150L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. AT BASEMENT VARIOUS AREA... | $0 | $0 | Nov 18, 2016 |
| Aug 31, 2016 | 35207641X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 8/31/16 AT 11:30AM IN BASEMENT.THROUGHOUT INSTALLED... | $0 | $0 | Nov 18, 2016 |
| Nov 20, 2014 | 35073160Y | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. NOTED: AT TIME OF INSPECTION,AT APPROX. 12PM LICENSED ELECTRICIAN,LICENSE #12221,DID NO... | $1,630 | $0 | Jan 16, 2015 |
| Oct 31, 2014 | 35079177H | RESOLVE | CLASS - 1 | NEW BUILDING OCCUPIED WITHOUT A VALID CERT OF OCCUPANCY. BUILDING OCCUPIED BY NYC DEPT OF HOMELESS SERVICES. CERT OF ... | $0 | $0 | Dec 19, 2014 |
| Apr 17, 2000 | 34233666P | RESOLVE | Non-Hazardous | NEW BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY N.B # 52/88 NOTE: T C OFO #73030 EXPIRED 11/13/99 REME... | $2,500 | $0 | Jun 9, 2000 |
| Jul 7, 1999 | 34188248M | RESOLVE | Non-Hazardous | NEW BLDG #52/88 OCCUPIED W/O A VALID C OF O. C OF O #71553 EXPIRED 6/11/98. REMEDY: DISCONTINUE ILLEGAL OCCUPANCY OR ... | $0 | $0 | Aug 27, 1999 |