Skip to content

ECB violations

Willow Avenue, Bronx • Block 02585 • Lot 0001

37 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Feb 13, 2020 39017562X ACTIVE CLASS - 2 RESPONDENT FAILED TO ALLOW MANDATORY ANNUAL INSPECTION BY THE DEPARTMENT OR APPROVED AGENCY PER 28-304.6.1 AND APPEND... $3,125 $0 Jul 24, 2020
Apr 9, 2019 38269234L RESOLVE CLASS - 1 CU59L10; 35M07,80M15,77K10,52M15. CEASE USE ITEM; 59L-REPAIR MISSING PARTS, NOTIFY THE DOB FOR RESTORE TO SERVICE REI... $1,250 $0 Nov 8, 2019
Mar 21, 2018 38262218J RESOLVE CLASS - 2 05R05 WORK W/O A PERMIT. A NEW OPERATOR, CLUTCH ARM AND RELEASE ROLLERS WAS INSTALL W/O A PERMIT ON AN APPLICATION BE... $0 $0 Aug 10, 2018
Mar 20, 2018 38262211R RESOLVE CLASS - 2 67X10 REPAIR ELEVATOR TWO-WAY COMMUNICATION (PHONE) $1,562 -$1,562 Aug 24, 2018
Oct 19, 2011 38218209J RESOLVE CLASS - 2 08V01 16A10 42D06 60L07 61M07 70O02 71M07 72M07 68M07. 08V01-ADJUST FLR STOPS. 16A10-REPAIR-CLOSE ALL HOLES IN HOISTW... $500 $0 Dec 16, 2011
Oct 19, 2011 38218210R RESOLVE CLASS - 2 97X10. 97X10-REPAIR/RESTORE TO SERVICE-DEVICE CEASE USED ON 06/24/11 ONE OF TWO FREIGHT CARS (BOTH) OUT OF SERVICE IN... $500 $0 Dec 16, 2011
Oct 19, 2011 38218211Z RESOLVE CLASS - 2 97X10. 97X10-REPAIR-RESTORE TO SERVICE SO THAT PROPER INSPECTION MAY BE PERFORMED BY DOB-ONE OF TWO FREIGHT CARS (BOT... $500 $0 Dec 16, 2011
Jun 24, 2011 38217028X RESOLVE CLASS - 1 06N10,21N10,43L10,98U05,99U05,44H10,12Q03,21Q03,100M07,16L10,40M07.(CU)REAR GATE SWITCH BLOCKED IN C/U STREET LEVEL I... $1,000 $0 Sep 13, 2011
Jun 24, 2011 38217029H RESOLVE CLASS - 2 97X10)ONE OF 2 FRIGHT ELEVATORS IN BLDG IS OUT OF SERVICE. $500 $0 Sep 13, 2011
Dec 22, 2010 34893538Y RESOLVE CLASS - 1 UNLAWFUL ACTS FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER RESPONDENT FAILED TO CORRECT THE CONDITIONS CITED IN P... $2,400 $0 Oct 5, 2012
Jun 13, 2010 34852605Y RESOLVE CLASS - 1 OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C/O OR BLDG DEPT RECORDS. ILLEGAL OCCUPANCY ON 2ND FLR, FACTORY SPACE CONVE... $2,400 $0 Oct 5, 2012
Jun 13, 2010 34852606X RESOLVE CLASS - 2 OPERATION OF A PA W/O A CURRENT C/O. REMEDY: OBTAIN A CURRENT C/O. $800 $0 Oct 5, 2012
Apr 16, 2010 32068021Z RESOLVE CLASS - 2 B254/16/32A/46A/HIGH PRESSURE BOILER(STEAM)NB#16271 $0 $0 Jun 4, 2010
Apr 16, 2010 32068020R RESOLVE CLASS - 2 B254/16/32A/46A/20/HIGH PRESSURE BOILER NB#15273/50-COMBUSTIBLE STORAGE IN BOILER ROOM, MUST REMOVE ALL COMBUSTIBLES. $0 $0 Jun 4, 2010
Nov 4, 2009 34816007X RESOLVE CLASS - 1 SEC.3314.1.1 THE PERMIT HOLDER OR PERSON DIRECTLY IN CHARGE OF ANY SCAFFOLDING EQUIPMENT SHALL IMMEDIATELY NOTIFY THE... $1,600 $0 May 14, 2010
Nov 4, 2009 34816006Y RESOLVE CLASS - 2 FAILED TO NOTIFY DEPT OBTAIN PERMIT PRIOR TO USE/INST. OFF OUTRIGGER BEAMS IN CONNECTION W/SUSPENDED SCAFFOLD. OUTRIG... $400 $0 May 14, 2010
Feb 11, 2009 32065682M RESOLVE CLASS - 3 VIOLATING CONDITIONS 50A,32A,50B 50A-STEAM LEAK ON MAIN STOP VALVE. 50B-INSTALL PERMANENT FRESH AIR ENTRY LOUVER. $0 $0 Apr 3, 2009
Feb 11, 2009 32065683Y ACTIVE CLASS - 2 50A-LUDELL GAS FIRED WATER HEATER MODEL DC-9502 NOT VENTED TO OUTSIDE OF BUILDING INSTALL FLUE PIPE VENTING TO OUTSID... $500 $0 Apr 3, 2009
Jan 17, 2009 34741461M RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTE: CONCRETE LINTELS SPALLING AND DEFECTIVE WILLOW AVE SIDE ... $5,000 $0 Mar 20, 2009
Dec 21, 2004 32046834Z RESOLVE Non-Hazardous 48B 50A 50B 1984 CYCLOTHERM NATL BD 16271 50A. LOW WATER CUT-OFF LEAKING 50B. PIPE DOWN GLASS DRAIN VALVE. $0 $0 Feb 4, 2005
Dec 21, 2004 32046835K RESOLVE Non-Hazardous 18A 18B 50A 50B 1974 CYCLOTHERM NATL BD 15273 50A. LOW WATER CUT OFF LEAKING. 50B PIPE DOWN GLASS DRAIN VALVE. $0 $0 Feb 4, 2005
Dec 21, 2004 32046833R RESOLVE Non-Hazardous 48A 48B 50A 50B 50C CYCLOTHERM 1983 NATL BL 16192 50A SAFETY VALVE LEAKING REPLACE. 50B PIPE DOWN GLASS DRAIN VALVE. ... $0 $0 Feb 4, 2005
Dec 21, 2004 32046838X RESOLVE Non-Hazardous 48B 50 1983 N.B. 16180 50 PIPE SAFETY VALVE DISCHARGE DOWN 18" FROM THE FLOOR. $0 $0 Feb 4, 2005
Jan 28, 2004 32043836Z RESOLVE Non-Hazardous 50A 50B CYCLOTHERM FTSM BOILER NB15963 GAS 1981 50A MISSING SECONDARY BLOWDOWN VALVE ON THE BLR 50B NO DISCHARGE PIPE... $0 $0 Mar 19, 2004
Jan 28, 2004 32043833N RESOLVE Non-Hazardous 48AB 50A 50B 32A CYCLOTHERM FTSM HP STEAM BOILER NB 16184 GAS FIRED 1983 50A STEAM PRESSURE GAUGE DIAL RANGE IS 0-200... $180 $0 Mar 19, 2004
Jan 28, 2004 32043835R RESOLVE Non-Hazardous 50A 50B CYCLOTHERM FTSM HP STEAM BOILER NB 16180 GAS 1983 50A THE STEAM PRESSURE GAUGE HAS A DIAL RANGE OF 0-200 PSI ... $0 $0 Mar 19, 2004
Jan 28, 2004 32043834P RESOLVE Non-Hazardous 48AB 50A 50B CYCLOTHERM FTSM HLP STEAM BOILER NB 15772 GAS 1979 50A STEAM PRESSURE GAUGE HAS A DIAL RANGE OF 0-200 PS... $0 $0 Mar 19, 2004
Jan 28, 2004 32043832L RESOLVE Non-Hazardous 50A 50B 50C 50D CYCLOTHERM FISTM HLP STM BLR NB 15273,2070 GAS 1974 50A THE STEAM PRESSURE GAUGE HAS A DIAL RANGE OF ... $0 $0 Mar 19, 2004
Jan 28, 2004 32043831J RESOLVE Non-Hazardous 6A 50A 48B 25AB 50B 50C 50D CYCLOTHERM FTSM HP STEAM BOILER NB16271 GAS FIRED 1984 50A STEAM PRESSURE GAUGE DIAL RANG... $0 $0 Mar 19, 2004
Jan 28, 2004 32043830H RESOLVE Non-Hazardous 48AB 50A 50B 50C 50D 50E CYCLOTHERM FTSM HP STEAM BCR NB16192 2070HR GAS 1983 50A MISSING STAP VALVE ON STEAM OUTLET ... $0 $0 Mar 19, 2004
Jun 13, 2002 34303001L RESOLVE Non-Hazardous FAILURE TO PROVIDE 10'X12' ELEVATOR LANDINGS ON ALL FLOORS. FAILURE TO PROVIDE 3' NUMBER IN STAIRWAY ON EACH FLOOR. F... $600 $0 Oct 25, 2002
Jan 13, 1998 38069068Z RESOLVE Non-Hazardous 50Y62M54Q53X46H18Q3O31R11Q3A57O30O35X 32-CLEAN CAR TOP 35-REMOVED HANGING WIRE OVER BRAKER IN MOTOR ROOM 62-REPLACE T... $350 $0 Feb 27, 1998
Jan 7, 1998 38069055J RESOLVE Non-Hazardous 46H,47H,73X,73X,75U,-PUT ELEVATOR BACK IN SERVICE TO INSPECTION BY D.O.B $0 $0 May 22, 1998
Jan 7, 1998 38069054H RESOLVE Hazardous 18I,18R,52A,36D,2X,1X,57O,11Q,15R,14I, 18-CEASE USE INERLOCK JUMP OUT AND HOISTWAY GATE NOT SECURE CALL FOR REINSPECT... $0 $0 May 22, 1998
Jan 27, 1995 38046932K RESOLVE Non-Hazardous 73X. RESTORE ELEVATOR TO SERVICE SO A PROPER INSPECTION CAN BE MADE. $0 $0 May 2, 1995
Jan 27, 1995 38046933M RESOLVE Non-Hazardous 15B. REPLACE STREET LEVEL DOOR. (HOISTWAY) $0 $0 May 2, 1995
Feb 18, 1993 34046089K RESOLVE Hazardous FAILURE TO MAINTAIN EXTERIOR BUILDING. DEFECT IS: SECTIONS OF CONCRETE LINTEL HAVE FALLEN TO STREET FROM THIRD FLOOR.... $0 $0 Mar 29, 1993