| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 13, 2020 | 39017562X | ACTIVE | CLASS - 2 | RESPONDENT FAILED TO ALLOW MANDATORY ANNUAL INSPECTION BY THE DEPARTMENT OR APPROVED AGENCY PER 28-304.6.1 AND APPEND... | $3,125 | $0 | Jul 24, 2020 |
| Apr 9, 2019 | 38269234L | RESOLVE | CLASS - 1 | CU59L10; 35M07,80M15,77K10,52M15. CEASE USE ITEM; 59L-REPAIR MISSING PARTS, NOTIFY THE DOB FOR RESTORE TO SERVICE REI... | $1,250 | $0 | Nov 8, 2019 |
| Mar 21, 2018 | 38262218J | RESOLVE | CLASS - 2 | 05R05 WORK W/O A PERMIT. A NEW OPERATOR, CLUTCH ARM AND RELEASE ROLLERS WAS INSTALL W/O A PERMIT ON AN APPLICATION BE... | $0 | $0 | Aug 10, 2018 |
| Mar 20, 2018 | 38262211R | RESOLVE | CLASS - 2 | 67X10 REPAIR ELEVATOR TWO-WAY COMMUNICATION (PHONE) | $1,562 | -$1,562 | Aug 24, 2018 |
| Oct 19, 2011 | 38218209J | RESOLVE | CLASS - 2 | 08V01 16A10 42D06 60L07 61M07 70O02 71M07 72M07 68M07. 08V01-ADJUST FLR STOPS. 16A10-REPAIR-CLOSE ALL HOLES IN HOISTW... | $500 | $0 | Dec 16, 2011 |
| Oct 19, 2011 | 38218210R | RESOLVE | CLASS - 2 | 97X10. 97X10-REPAIR/RESTORE TO SERVICE-DEVICE CEASE USED ON 06/24/11 ONE OF TWO FREIGHT CARS (BOTH) OUT OF SERVICE IN... | $500 | $0 | Dec 16, 2011 |
| Oct 19, 2011 | 38218211Z | RESOLVE | CLASS - 2 | 97X10. 97X10-REPAIR-RESTORE TO SERVICE SO THAT PROPER INSPECTION MAY BE PERFORMED BY DOB-ONE OF TWO FREIGHT CARS (BOT... | $500 | $0 | Dec 16, 2011 |
| Jun 24, 2011 | 38217028X | RESOLVE | CLASS - 1 | 06N10,21N10,43L10,98U05,99U05,44H10,12Q03,21Q03,100M07,16L10,40M07.(CU)REAR GATE SWITCH BLOCKED IN C/U STREET LEVEL I... | $1,000 | $0 | Sep 13, 2011 |
| Jun 24, 2011 | 38217029H | RESOLVE | CLASS - 2 | 97X10)ONE OF 2 FRIGHT ELEVATORS IN BLDG IS OUT OF SERVICE. | $500 | $0 | Sep 13, 2011 |
| Dec 22, 2010 | 34893538Y | RESOLVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER RESPONDENT FAILED TO CORRECT THE CONDITIONS CITED IN P... | $2,400 | $0 | Oct 5, 2012 |
| Jun 13, 2010 | 34852605Y | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C/O OR BLDG DEPT RECORDS. ILLEGAL OCCUPANCY ON 2ND FLR, FACTORY SPACE CONVE... | $2,400 | $0 | Oct 5, 2012 |
| Jun 13, 2010 | 34852606X | RESOLVE | CLASS - 2 | OPERATION OF A PA W/O A CURRENT C/O. REMEDY: OBTAIN A CURRENT C/O. | $800 | $0 | Oct 5, 2012 |
| Apr 16, 2010 | 32068021Z | RESOLVE | CLASS - 2 | B254/16/32A/46A/HIGH PRESSURE BOILER(STEAM)NB#16271 | $0 | $0 | Jun 4, 2010 |
| Apr 16, 2010 | 32068020R | RESOLVE | CLASS - 2 | B254/16/32A/46A/20/HIGH PRESSURE BOILER NB#15273/50-COMBUSTIBLE STORAGE IN BOILER ROOM, MUST REMOVE ALL COMBUSTIBLES. | $0 | $0 | Jun 4, 2010 |
| Nov 4, 2009 | 34816007X | RESOLVE | CLASS - 1 | SEC.3314.1.1 THE PERMIT HOLDER OR PERSON DIRECTLY IN CHARGE OF ANY SCAFFOLDING EQUIPMENT SHALL IMMEDIATELY NOTIFY THE... | $1,600 | $0 | May 14, 2010 |
| Nov 4, 2009 | 34816006Y | RESOLVE | CLASS - 2 | FAILED TO NOTIFY DEPT OBTAIN PERMIT PRIOR TO USE/INST. OFF OUTRIGGER BEAMS IN CONNECTION W/SUSPENDED SCAFFOLD. OUTRIG... | $400 | $0 | May 14, 2010 |
| Feb 11, 2009 | 32065682M | RESOLVE | CLASS - 3 | VIOLATING CONDITIONS 50A,32A,50B 50A-STEAM LEAK ON MAIN STOP VALVE. 50B-INSTALL PERMANENT FRESH AIR ENTRY LOUVER. | $0 | $0 | Apr 3, 2009 |
| Feb 11, 2009 | 32065683Y | ACTIVE | CLASS - 2 | 50A-LUDELL GAS FIRED WATER HEATER MODEL DC-9502 NOT VENTED TO OUTSIDE OF BUILDING INSTALL FLUE PIPE VENTING TO OUTSID... | $500 | $0 | Apr 3, 2009 |
| Jan 17, 2009 | 34741461M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTE: CONCRETE LINTELS SPALLING AND DEFECTIVE WILLOW AVE SIDE ... | $5,000 | $0 | Mar 20, 2009 |
| Dec 21, 2004 | 32046834Z | RESOLVE | Non-Hazardous | 48B 50A 50B 1984 CYCLOTHERM NATL BD 16271 50A. LOW WATER CUT-OFF LEAKING 50B. PIPE DOWN GLASS DRAIN VALVE. | $0 | $0 | Feb 4, 2005 |
| Dec 21, 2004 | 32046835K | RESOLVE | Non-Hazardous | 18A 18B 50A 50B 1974 CYCLOTHERM NATL BD 15273 50A. LOW WATER CUT OFF LEAKING. 50B PIPE DOWN GLASS DRAIN VALVE. | $0 | $0 | Feb 4, 2005 |
| Dec 21, 2004 | 32046833R | RESOLVE | Non-Hazardous | 48A 48B 50A 50B 50C CYCLOTHERM 1983 NATL BL 16192 50A SAFETY VALVE LEAKING REPLACE. 50B PIPE DOWN GLASS DRAIN VALVE. ... | $0 | $0 | Feb 4, 2005 |
| Dec 21, 2004 | 32046838X | RESOLVE | Non-Hazardous | 48B 50 1983 N.B. 16180 50 PIPE SAFETY VALVE DISCHARGE DOWN 18" FROM THE FLOOR. | $0 | $0 | Feb 4, 2005 |
| Jan 28, 2004 | 32043836Z | RESOLVE | Non-Hazardous | 50A 50B CYCLOTHERM FTSM BOILER NB15963 GAS 1981 50A MISSING SECONDARY BLOWDOWN VALVE ON THE BLR 50B NO DISCHARGE PIPE... | $0 | $0 | Mar 19, 2004 |
| Jan 28, 2004 | 32043833N | RESOLVE | Non-Hazardous | 48AB 50A 50B 32A CYCLOTHERM FTSM HP STEAM BOILER NB 16184 GAS FIRED 1983 50A STEAM PRESSURE GAUGE DIAL RANGE IS 0-200... | $180 | $0 | Mar 19, 2004 |
| Jan 28, 2004 | 32043835R | RESOLVE | Non-Hazardous | 50A 50B CYCLOTHERM FTSM HP STEAM BOILER NB 16180 GAS 1983 50A THE STEAM PRESSURE GAUGE HAS A DIAL RANGE OF 0-200 PSI ... | $0 | $0 | Mar 19, 2004 |
| Jan 28, 2004 | 32043834P | RESOLVE | Non-Hazardous | 48AB 50A 50B CYCLOTHERM FTSM HLP STEAM BOILER NB 15772 GAS 1979 50A STEAM PRESSURE GAUGE HAS A DIAL RANGE OF 0-200 PS... | $0 | $0 | Mar 19, 2004 |
| Jan 28, 2004 | 32043832L | RESOLVE | Non-Hazardous | 50A 50B 50C 50D CYCLOTHERM FISTM HLP STM BLR NB 15273,2070 GAS 1974 50A THE STEAM PRESSURE GAUGE HAS A DIAL RANGE OF ... | $0 | $0 | Mar 19, 2004 |
| Jan 28, 2004 | 32043831J | RESOLVE | Non-Hazardous | 6A 50A 48B 25AB 50B 50C 50D CYCLOTHERM FTSM HP STEAM BOILER NB16271 GAS FIRED 1984 50A STEAM PRESSURE GAUGE DIAL RANG... | $0 | $0 | Mar 19, 2004 |
| Jan 28, 2004 | 32043830H | RESOLVE | Non-Hazardous | 48AB 50A 50B 50C 50D 50E CYCLOTHERM FTSM HP STEAM BCR NB16192 2070HR GAS 1983 50A MISSING STAP VALVE ON STEAM OUTLET ... | $0 | $0 | Mar 19, 2004 |
| Jun 13, 2002 | 34303001L | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE 10'X12' ELEVATOR LANDINGS ON ALL FLOORS. FAILURE TO PROVIDE 3' NUMBER IN STAIRWAY ON EACH FLOOR. F... | $600 | $0 | Oct 25, 2002 |
| Jan 13, 1998 | 38069068Z | RESOLVE | Non-Hazardous | 50Y62M54Q53X46H18Q3O31R11Q3A57O30O35X 32-CLEAN CAR TOP 35-REMOVED HANGING WIRE OVER BRAKER IN MOTOR ROOM 62-REPLACE T... | $350 | $0 | Feb 27, 1998 |
| Jan 7, 1998 | 38069055J | RESOLVE | Non-Hazardous | 46H,47H,73X,73X,75U,-PUT ELEVATOR BACK IN SERVICE TO INSPECTION BY D.O.B | $0 | $0 | May 22, 1998 |
| Jan 7, 1998 | 38069054H | RESOLVE | Hazardous | 18I,18R,52A,36D,2X,1X,57O,11Q,15R,14I, 18-CEASE USE INERLOCK JUMP OUT AND HOISTWAY GATE NOT SECURE CALL FOR REINSPECT... | $0 | $0 | May 22, 1998 |
| Jan 27, 1995 | 38046932K | RESOLVE | Non-Hazardous | 73X. RESTORE ELEVATOR TO SERVICE SO A PROPER INSPECTION CAN BE MADE. | $0 | $0 | May 2, 1995 |
| Jan 27, 1995 | 38046933M | RESOLVE | Non-Hazardous | 15B. REPLACE STREET LEVEL DOOR. (HOISTWAY) | $0 | $0 | May 2, 1995 |
| Feb 18, 1993 | 34046089K | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING. DEFECT IS: SECTIONS OF CONCRETE LINTEL HAVE FALLEN TO STREET FROM THIRD FLOOR.... | $0 | $0 | Mar 29, 1993 |