ECB violations
164 Willow Avenue, Bronx • Block 02587 • Lot 0001
37 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 20, 2026 | 39181286N | ACTIVE | CLASS - 1 | IN BASEMENT USING PVC PIPING ON WASTE LINE UNDER SLOPE SINK. IN CAFETERIA ROOM OPEN WASTE LINE. DOOR BY THE WATER MET... | $2,500 | $0 | Aug 7, 2026 |
| Mar 20, 2026 | 39181298K | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN EXP #2 IN THE ALLEY THAT THE INSTALLATION OF A/C SPLIT UNIT COMPRESSOR,... | $2,500 | $0 | Aug 7, 2026 |
| Mar 20, 2026 | 39181297Z | ACTIVE | CLASS - 1 | ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON THE 1ST FL ELECTRICAL CLOSET W... | $1,200 | $0 | Aug 7, 2026 |
| Mar 20, 2026 | 39181246Z | ACTIVE | CLASS - 2 | CLASS 2: FIREFIGHTER'S SERVICE PHASE I SWITCH MULFUNCTIONING - CYLINDER ROTATES 360, NOT ALWAYS ACTIVATING PHASE I OP... | $625 | $0 | Apr 10, 2026 |
| Mar 20, 2026 | 39181285L | ACTIVE | CLASS - 1 | OBSERVED THROUGHOUT THE BUILDING NO TRAP WRAP INSULATION UNDER SINKS IN BATHROOMS. ON 4TH FLOOR IN BATHROOM SPRINKLER... | $2,500 | $0 | Aug 7, 2026 |
| Aug 15, 2025 | 39157266X | ACTIVE | CLASS - 2 | CLASS 2: FIRE TABS ON HOISTWAY DOORS HANGING ROLLERS ARE NOT SET TO THE UPRIGHT POSITION, RE-ADJUST. TOE GUARD LOOSE,... | $625 | $0 | Aug 29, 2025 |
| Feb 7, 2025 | 39137840N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Mar 21, 2025 |
| Sep 3, 2024 | 39123781P | ACTIVE | CLASS - 1 | DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE... | $1,250 | $0 | Oct 18, 2024 |
| Apr 12, 2024 | 39111552N | RESOLVE | CLASS - 1 | ONLY ELEVATOR IN THE BUILDING OUT OF SERVICE. | $1,250 | $0 | Jun 7, 2024 |
| Apr 5, 2024 | 39110882L | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). BRAKE MAINTENANCE TAG EXPIRED AND MISSING THE DATE BRAKE... | $1,250 | $0 | Jun 7, 2024 |
| Oct 25, 2023 | 38274987M | RESOLVE | CLASS - 1 | 97-X-17=ENTIRE DEVICE IS INOPERATIVE UPON INSPECTION ARRIVAL. THIS IS THE ONLY ELEVATOR PREMISES. CREATING A HAZARDOU... | $1,250 | $0 | Nov 24, 2023 |
| Aug 21, 2023 | 39092940Y | RESOLVE | CLASS - 2 | FOUND BOILER NOT OPERABLE, CORRODED AND LEAKING RETURN LINE, BODY FDRAIN MISSING ON SAFETY RELIEF VALVE, COIL RELIEF ... | $625 | $0 | Oct 20, 2023 |
| Aug 21, 2023 | 39093003Y | RESOLVE | CLASS - 1 | OUT OF SERVICE, RESTORE TO SERVICE | $0 | $0 | Nov 3, 2023 |
| Aug 21, 2023 | 39092939R | RESOLVE | CLASS - 2 | FOUND DIRTY GLASS GAUGE, CORRODED HARTFORD LOOP, COIL RELIEF VALVE MISSING. | $625 | $0 | Oct 20, 2023 |
| Mar 22, 2023 | 39082019P | RESOLVE | CLASS - 2 | JIM CAPS INSTALLED ON CAST IRON FITTINGS ON FIRST FLOOR. AS PER PLUMBING CODE 708.1.6., REPAIR AND/OR REPLACE | $625 | $0 | Mar 27, 2023 |
| Sep 30, 2021 | 39048453Z | RESOLVE | CLASS - 2 | FOUND BOTH OIL PUMP SETS RUNNING CONSTANT, SHOULD RUN WHEN BURNER RUNS, LATCHES AND BOLTS MISSING ON BOILER DOORS, GL... | $625 | $0 | Oct 15, 2021 |
| Oct 16, 2018 | 35359674P | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. IN 10/12/17 AND 09/05/18. TWO VIOLATIONS WAS ISSU... | $0 | $0 | Nov 30, 2018 |
| Sep 5, 2018 | 35358606Z | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT FAILUR TO COMPLY WITH AN ORDER TO THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS #35294527K(... | $6,250 | $6,250 | Nov 2, 2018 |
| Aug 14, 2018 | 38264725N | RESOLVE | CLASS - 1 | CU05L10; 29L11. 05L10-UPON INSPECTION OF DEVICE IT WAS FOUND THAT THECAR DOOR ZONE RESTRICTOR IS DEFECTIVE REPAIR AND... | $0 | $0 | Nov 2, 2018 |
| Jul 13, 2018 | 35343226P | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT.FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT & CERTIFY SUMMONS #35313174P & 35... | $0 | $0 | Aug 31, 2018 |
| May 15, 2018 | 35331840R | RESOLVE | CLASS - 2 | EXPOSED ENERGIZED WIRING. OBSERVED AT ELECTRIC METER BANK. TWO METER SWITCHES NOT PROPERLY MOUNTED TO METER CAN ENCLO... | $0 | $0 | Aug 3, 2018 |
| May 8, 2018 | 35331800M | RESOLVE | CLASS - 2 | BUILDINGS OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY.NOTED:OBSERVED A 4 STORY BUILDING OCCUPIED BY D.H.S.AS A ... | $0 | $0 | Jul 6, 2018 |
| Apr 24, 2018 | 35313174P | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. IN OCTOBER 12, 2017, JANUARY 02,2018. TWO ELECTRI... | $0 | $0 | Jun 29, 2018 |
| Mar 19, 2018 | 38262209H | RESOLVE | CLASS - 2 | 59B07,68M07,68M07,99BB05,42D06,40D06,50D06,39Q03,16T07,21U07,39B07,100X10,70O02,34U07,80M07,67X10,61T07. 59-PERFORM B... | $0 | $0 | Jun 1, 2018 |
| Jan 2, 2018 | 35274515P | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMLPLY WITH AN ORDER OF THE COMMISSIONER. IN OCTOBER 12, 2017 A ELECTRICAL VIOLATION WAS IS... | $0 | $0 | Mar 2, 2018 |
| Oct 12, 2017 | 35294527K | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED AT WATER MAIN LOCATED IN THE BASEMENT: MAIN GROUNDING CONDUCTOR ELECTR... | $0 | $0 | Jan 5, 2018 |
| Oct 12, 2017 | 35294403Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON TOP FLOOR NO PRESSURE GAUGE INSTALLED AT THE INSPEC... | $0 | $0 | Jan 5, 2018 |
| Oct 12, 2017 | 35294528M | RESOLVE | CLASS - 2 | UNAPPROVED, UNSAFE, UNSUITABLE ELECTRICAL EQUIPMENT, APARATUS, DEVICES, MATERIALS, APPLIANCES OR WIRING IN USE. OBSER... | $0 | $0 | Jan 5, 2018 |
| Jun 5, 2017 | 35267636X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON ALL FLOORS ABOVE THE CELLAR NO PRESSURE GAUGES INSTALL... | $0 | $0 | Aug 18, 2017 |
| Jul 21, 2016 | 35200991Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG CODE COMPLIANT. NOTED: AT CELLAR, EXPOSED, LOOSE ELECTRIC WIRING LEFT AND RIGHT OF ELEVATOR ... | $0 | $0 | Sep 16, 2016 |
| Jul 21, 2016 | 35200989P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING CODE COMPLIANT: LACK OF EMERGENCY LIGHTING PER BC1006.1; 27-542. NOTED: AT 2A,4A AND ADJ... | $0 | $0 | Sep 16, 2016 |
| Jul 21, 2016 | 35200990M | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO BUILDING DEPT RECORDS. NOTED: BUILDING OCCUPIED AS HOMELESS SHELTER WITH 179 MALES. LNO #5705 L... | $0 | $0 | Sep 16, 2016 |
| Sep 19, 2014 | 35080301Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. NOTED: 1) THERE ARE EXPOSED (OPEN) ROOF WOOD STRUCTURE AT TOP (4TH... | $0 | $0 | Oct 31, 2014 |
| Jan 31, 2009 | 34753419R | RESOLVE | CLASS - 2 | SIDEWALK SHED DOES NOT MEET CODE SPECIFICATIONS SIDEWALK SHED ERECTED UNDER PERMIT #210046118 HAS INOPERABLE/NOT LIT ... | $0 | $0 | Apr 3, 2009 |
| Apr 27, 2001 | 38116022M | RESOLVE | Non-Hazardous | 7L11-15L11-16L12-20L11-28H11-44L11-55X11 7L11=LIGHT RAY 15L11=NOT SELF CLOSING 3RD FLOOR 16H12=1ST FL 20L11=LIGHTS 44... | $0 | $0 | Jul 6, 2001 |
| Apr 27, 2001 | 38116542X | RESOLVE | Non-Hazardous | 7L11-15L11-16H12-20L11-28H11-44L11-55X11 7L11=LIGHT RAY 15L11=NOT SELF CLOSING 3RD FL 16H12=1ST FL. 20L11-LIGHTS 44L1... | $180 | -$180 | Jul 6, 2001 |
| Jan 23, 1998 | 38069619X | RESOLVE | Non-Hazardous | 57O,74X,28H,74D,40U,35Z, 79-FIX EMS PHONE 35-WATER LOCKS IN MOTOR ROOM OVER MAIN MACHINE 40-2 YEAR TEST 74-SECURE SMO... | $180 | $0 | Apr 24, 1998 |