Skip to content

ECB violations

690-700 Beck Street, Bronx • Block 02684 • Lot 0068

10 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Apr 3, 2018 35323335X RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALLS/APPURTENANCES.@ THE TIME OF INSPECTION,I OBSERVED A SECTION OF THE GUTTER ASSEMBLY... $625 $0 May 18, 2018
Jun 19, 2017 32088812N RESOLVE CLASS - 2 B254, 36. FULTON V.T. BLK,10HP, DB 114914 HP STEAM. GAS FIRED 2013; 36-REFERENCED BOILER IN OPERATION IS NOT REGISTER... $250 $0 Aug 4, 2017
Jun 19, 2017 32088813P RESOLVE CLASS - 1 B154,3A,3B,51. FULTON V.T. BLK, 10HP DB114914 HP STEAM, GAS-FIRED 2013 3A-THERMAL WEAR AND COLLAPSE ON SECTIONS OF FL... $1,000 $0 Aug 4, 2017
Jul 24, 2007 32054094M RESOLVE Non-Hazardous B4A-50ABC.FULTON V.T. BOILER,4 HP,NB 43410,GAS,1983.50A-EVIDENCE OF OVERHEATING AT THE UPPER SECTION OF THE BOILER EX... $350 $0 Sep 21, 2007
Mar 30, 2004 32044172J RESOLVE Non-Hazardous 50A,50B. FULTON VERT TBLS BOILER 4HP,NB 43410,GAS 1983 50A-SECONDARY BLOWDOWN SHUT OFF VALVE NOT SCREW OR SLOW CLOSIN... $180 $0 Feb 25, 2005
Mar 1, 2002 32026528M RESOLVE Non-Hazardous 16, 18A, 49. 49) MUST INSTALL A DISCHARGE PIPE ON SAFETY VALVE. MUST INSTALL A DRAIN LINE ON SITE GLASS FOR BLOW DOWN... $0 $0 Apr 19, 2002
Mar 1, 2002 32026529Y RESOLVE Non-Hazardous 16, 36, 49. BQ9. 27-127. LOW PRESSURE BOILER INSTALLED WITHOU A PERMIT ISSUED BY DOB BOILER OPERATING WITHOUT AN EQUI... $0 $0 Sep 27, 2002
Jan 11, 1999 32015555Y RESOLVE Non-Hazardous 36,49A,49B. 36-BOILER NOT REGISTERED. 49A-(BQ9) (27-147) BOILER INSTALLED W/O WORK PERMIT. 49B-ADJUST GAS BURNER CAUS... $350 $0 Jul 23, 1999
Jan 11, 1999 32016888R RESOLVE Hazardous 18A,32A,48A,48B,49,51. 18A-HANDHOLES CORRODED. 32A-WIRING EXPOSED. 48A-WATER GAUGE GLASS DIRTY. 48B-WATER GAUGE GLASS... $400 $0 Feb 26, 1999
Aug 12, 1988 32000527P RESOLVE Unknown IMPROPER BREECHING BOILER EXHAUSTS OUT SIDE WALK FLOOR VENT. $200 $0 Sep 30, 1988