ECB violations
728-734 Kelly Street, Bronx • Block 02708 • Lot 0025
73 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 17, 2026 | 39177450Y | ACTIVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN MAIN ELECTRICAL ROOM NEW ELECTRICAL PANELS INSTALLED ALSO THE LAUNDRY R... | $1,250 | $0 | Sep 25, 2026 |
| Feb 17, 2026 | 39177488J | ACTIVE | CLASS - 2 | OBSERVED ON THE ROOF STANDING WATER DUE TO IMPROPER DRAINAGE. AT EXTERIOR STREET LEVEL STORM DRAIN IS CRUSHED. IN THE... | $1,250 | $1,250 | Sep 25, 2026 |
| Feb 17, 2026 | 39177489L | ACTIVE | CLASS - 1 | OBSERVED AT EXTERIOR STREET LEVEL SPRINKLER SIGNAGE INDICATES SPRINKLERS SYSTEM THROUGHOUT THE BUILDING WHEN THERE IS... | $2,500 | $2,500 | Sep 25, 2026 |
| Feb 17, 2026 | 39177487H | RESOLVE | CLASS - 1 | OBSERVED ON SEVENTH FLOOR AND IN BASEMENT, PVC PIPING IS INSTALLED ON WASTE LINES. IN BASEMENT SPRINKLER HEADS ARE OB... | $2,500 | $0 | Sep 25, 2026 |
| Aug 12, 2025 | 35718435J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING EXTERIOR WALL(S) OR APPURTENANCES. NOTE:-AT THE TIME OF INSPECTION OBSERVED(1) AT ROOF L... | $0 | $0 | Oct 17, 2025 |
| Feb 3, 2025 | 39137219P | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBVSERED NON SELF CLOSING DOORS THROUGHOUT BUILDING., REPAIR/REPLACE DOOR | $625 | $0 | Jul 25, 2025 |
| Feb 3, 2025 | 39137218N | RESOLVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED UNSAFE STORAGE UNDERNEATH STAIRCASE (MINI FRIDGES) LEA... | $2,500 | $0 | Apr 18, 2025 |
| Feb 3, 2025 | 39137198P | RESOLVE | CLASS - 2 | FOUND OIL FIRED FEDERAL BOILERS ACTIVE WITH DEFECTS. CONDENSATE RETURN TANK DEFECTIVE LEAKING WATER. CORRECT ALL VIOL... | $625 | $0 | Aug 1, 2025 |
| Feb 3, 2025 | 39137217L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Apr 18, 2025 |
| Feb 8, 2023 | 39512859P | RESOLVE | CLASS - 2 | NOTE: OBSERVED SIDEWALK SHED AT EXP1,4; HAVE MISSING SCREW CAPS CREATE SHARP EDGE(3307.6.5.6) CONDITION, CUT HAZARD F... | $2,400 | $0 | Apr 21, 2023 |
| Nov 28, 2022 | 35541089P | RESOLVE | CLASS - 2 | FAILURE TO SECURE/SUPPORT RACEWAYS/CABLE ASSEMBLIES/BOXES/CABINETS/FITTINGS.I OBSERVED IN VENT CONTROL RM LOCATED UND... | $0 | $0 | Feb 3, 2023 |
| Nov 28, 2022 | 35541088N | RESOLVE | CLASS - 1 | FAILURE TO PROTECT TEMP WIRING FROM IMPROPER CONDUCT.I OBSERVED IN ROOFTOP VENT CONTROL RM LOCATED UNDER ELEVATOR MOT... | $1,600 | $0 | Feb 3, 2023 |
| Nov 1, 2022 | 39073136J | RESOLVE | CLASS - 2 | AT CELLAR LEVEL, GAS METER ROOM, WALLS DO NOT MEET ,CONSTRUCTION TECHNICAL SPECIFICATIONS (FIRE RESISTANT WALL) WALLS... | $0 | $0 | Jan 13, 2023 |
| Nov 1, 2022 | 39073127H | RESOLVE | CLASS - 2 | AS PER TWO 60 HP, FEDERAL BOILERS; COMBUSTION AIR FAN NOT OPERATING-NO BELT GUARDS ON TWO OIL PUMPS AT OIL STATION-HO... | $0 | $0 | Dec 16, 2022 |
| Nov 1, 2022 | 39073135H | RESOLVE | CLASS - 2 | AT 3RD FLOOR, SMOKE DOOR NEAR ROOM # 310, AT CELLAR LEVEL, CAFETERIA EXIT DOOR AND BOILER ROOM,2ND EXIT DOOR TO PARKI... | $0 | $0 | Jan 13, 2023 |
| Dec 28, 2020 | 39034046Y | RESOLVE | CLASS - 2 | SAFETY VALVES LEAKING-GUARD MISSING FOR GAGE GLASS-SMOKE ALARM NOT SOUNDING OFF WHEN TESTED; CORRECT ALL VIOLATING CO... | $0 | $0 | Mar 19, 2021 |
| Mar 10, 2020 | 39019344R | ACTIVE | CLASS - 1 | UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE . RESTORED TO SERVICE IMMEDIATELY AND CONTACT NYCDOB FOR A COMPLETE I... | $1,250 | $0 | Nov 20, 2020 |
| Mar 10, 2020 | 39019343P | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Nov 20, 2020 |
| Mar 10, 2020 | 39019345Z | RESOLVE | CLASS - 1 | UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE . RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYCDOB FOR A COMPLETE IN... | $1,250 | $0 | Nov 20, 2020 |
| Feb 11, 2020 | 37017544J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #38269665N ISSUED ON 05-09-2019,AND TO FILE... | $625 | $0 | Nov 20, 2020 |
| Jan 14, 2020 | 39015728H | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS LISTED IN ECB# 35442252M ISSUED ON 07/08/2019 UNCORRECTED., FILE A CERTIFICATE OF... | $625 | $0 | Sep 11, 2020 |
| Jan 14, 2020 | 39015730R | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS CITED IN ECB #35442253Y ISSUED ON 07/08/2019 STILL IN EFFECT, FILE A CERTIFICATE ... | $625 | $0 | Sep 11, 2020 |
| Jan 14, 2020 | 39015729J | RESOLVE | CLASS - 2 | I OBSERVED IN THE COMMERCIAL KITCHEN THE USE OF DUPLEX RECEPTACLES NOT OF THE GFCI TYPE NOR GFCI PROTECTED AS REQUIRE... | $0 | $0 | Feb 26, 2021 |
| Jan 14, 2020 | 39015731Z | RESOLVE | CLASS - 1 | I OBSERVED IN THE ELECTRICAL EQUIPMENT ROOM A 200 AMP SERVICE DISCONNECT WITH THE NEUTRAL NOT BONDED AS REQUIRED., PR... | $0 | $0 | Feb 26, 2021 |
| Aug 28, 2019 | 38271037P | RESOLVE | CLASS - 1 | 97.X.10=CLASS 1 RESTORE TO SERVICE ENTIRE DEVICE INOPERATIVE | $312 | $0 | Oct 18, 2019 |
| Jul 8, 2019 | 35442251K | RESOLVE | CLASS - 1 | UNSAFE, UNSUITABLE, ELECTRICAL EQUIPEMENT/WIRING INUSE. I OBSEVRED ON THE ROOF THE USE OF ARMORED CABLE TO POWER UP A... | $1,600 | $0 | Aug 30, 2019 |
| Jul 8, 2019 | 35442252M | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUYND FAULT CIRCUIT INTERRUPTER AS REQUIRED. I OBSERVED IN THE COMMERCIAL KITCHEN THROUGHOUT 110... | $1,200 | $0 | Aug 30, 2019 |
| Jul 8, 2019 | 35434215N | RESOLVE | CLASS - 1 | FGC408.2/MISCELLANEOUS VIOLATION:FUTURE CONNECTIONS EXIST ON GAS PIPING.OBSERVED IN LAUNDRY ROOM A FUTURE CONNECTION ... | $0 | $0 | Dec 13, 2019 |
| Jul 8, 2019 | 35442253Y | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUDING ELECTRICAL CONDUCTOR IN ACCORDANCE WITH SECTION. I OBSERVED IN THE CELLAR A 200 AMP SERVI... | $4,800 | $0 | Aug 30, 2019 |
| Jul 8, 2019 | 35434214L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLAINT MANNER.OBSERVED IN THE CELLAR AT THE FIRE SPRINKLER CONTROL VALVES R... | $1,250 | $0 | Oct 2, 2020 |
| May 9, 2019 | 38269665N | RESOLVE | CLASS - 2 | 16H11,17M07,80B09,77Q03,42T11,56Y13,59B07,52U07,68M07,72B07;(16)WORN DOOR RELEASE ROLLERS(17)MISSING HOISTWAY DOOR GI... | $625 | $0 | Jul 5, 2019 |
| Feb 26, 2019 | 38267917L | RESOLVE | CLASS - 2 | 71X10,39O02,21M07,29M07,53M07,56O02,56Y13,44O02,70O02. 71X10-REPAIR PIT LIGHT; 39O02 CLEAN TOP OF CAR; 21M07-PROVIDE ... | $310 | $0 | Apr 19, 2019 |
| Jan 4, 2019 | 38267096N | RESOLVE | CLASS - 1 | 97-X-10=UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE.RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYC DOB FOR COMPLE... | $312 | $0 | Mar 1, 2019 |
| Dec 18, 2018 | 35391612J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35331818K ISSUED ON 5/25/18 AND TO FIL... | $1,250 | $0 | Feb 19, 2019 |
| Oct 26, 2018 | 35389283P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/ VIOLATION #35331818K ISSUED ON 05/25/18 AND TO FILE ... | $1,250 | $0 | Dec 21, 2018 |
| Sep 12, 2018 | 35386936J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35331818K ISSUED ON 05-25-18 & TO FILE A C OF C PURSUAN... | $1,250 | $0 | Nov 16, 2018 |
| Aug 24, 2018 | 32097196N | RESOLVE | CLASS - 2 | B254,50. SPILL SWITCH MISSING. CORRECT VIOLATING CONDITIONS AND SUBMIT CERTIFICATES OF CORRECTION. | $625 | $0 | Oct 19, 2018 |
| Aug 1, 2018 | 32097424X | RESOLVE | CLASS - 2 | 32A,50A-AS PER CLASS 2 (B254) 28-301.1 FAILURE TO MAINTAIN. 32A)EXPOSED ELECTRICAL WIRES AT FEEDER BOX. 50A)"U" RATED... | $0 | $0 | Sep 21, 2018 |
| Jul 19, 2018 | 35387461J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35331818K ISSUED ON 05-25-18 & TO FILE A C OF C PURSUAN... | $1,250 | $0 | Oct 5, 2018 |
| Jun 8, 2018 | 35335590L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT FIRST FLOOR CLASS ROOM,TWO EXIT SIGN IN SIDE THAT ROOM IS NO... | $250 | $0 | Aug 31, 2018 |
| May 25, 2018 | 35331818K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT CELLAR LEVEL TANK ROOM FLOOR BEING HELD UP BY STEEL ADJUSTAB... | $1,250 | $0 | Jul 20, 2018 |
| May 25, 2018 | 35334107H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDINGS IN CODE-COMPLIANT MANNER.OBSERVED ON 05/25/2018 AT ABOVE ADDRESS ON CELLAR LEVEL GAS ME... | $625 | $0 | Jul 20, 2018 |
| May 25, 2018 | 35331817Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC1008.1;27-371.AT R... | $0 | $0 | Jul 20, 2018 |
| May 25, 2018 | 35331816R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NO FIRE STOPPINGPER 712.3;27-345.NOTED:HOLES IN WALL AND CEILIN... | $1,250 | $0 | Jul 20, 2018 |
| May 16, 2018 | 35331832R | RESOLVE | CLASS - 1 | NON CURRENT CARRYING ELECTRICAL CONDUCTIVE MATERIAL IS NOT GROUNDED. OBSERVED AT EXTERIOR PERIMETER. A FULLY OPERATIO... | $4,800 | $0 | Jul 20, 2018 |
| Oct 5, 2017 | 35297193N | RESOLVE | CLASS - 1 | SEC. 411.1 RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED ON 10-5-17 AT ABOVE ADDRESS RESIDENTIAL GAS FL... | $1,600 | $0 | Apr 13, 2018 |
| Jun 20, 2017 | 37003035Y | RESOLVE | CLASS - 2 | FAILURE TO FILE ANNUAL CERTIFICATION THAT COOLING TOWER 1000002676 HASBEEN INSPECTED,TESTED,AND DISINFECTED,AND THAT ... | $1,000 | $0 | Dec 11, 2017 |
| May 23, 2017 | 35267482M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:NO FIRE STOPPINGPER BC712.3;37-345.NOTED:OBSERVED ON ELLAR LEVE... | $1,250 | $0 | Aug 4, 2017 |
| May 23, 2017 | 35267388X | RESOLVE | CLASS - 1 | FGC411.1/RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT.OBSERVED ON 5/23/17 AT ABOVE ADDRESS IN CELLAR RESIDENTIAL... | $1,600 | $0 | Jul 21, 2017 |
| Dec 7, 2016 | 38251540Y | RESOLVE | CLASS - 2 | 1L10,5J1,10H11,17H11,67L10,68M7,56Y2,56713. 1L10-EMERGENCY STOP SWITCH DEFECTIVE REPAIR; 5J1-CAR DOOR MISALIGNED ADJU... | $0 | $0 | Feb 3, 2017 |