ECB violations

731 Southern Boulevard, Bronx • Block 02720 • Lot 0028

143 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Mar 10, 2026 39179780X ACTIVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS ... $1,250 $0 May 15, 2026
Dec 1, 2025 39168727N ACTIVE CLASS - 1 FILED A CERTIFICATE, FORM, APPLICATION ETC., CONTAINING A MATERIAL FALSE STATEMENT(S). UNPERMITTED PLASTIC ACCESS PAN... $25,000 $25,000 Dec 17, 2026
Dec 1, 2025 39168687H ACTIVE CLASS - 2 CLASS 2: ADJUST 1ST FLOOR DOOR FOR SMOOTH OPERATION. EMERGENCY PHONE INOPERATIVE, PROVIDE 2 WAY COMMUNICATION. FLOOR ... $655 $655 Dec 17, 2026
Dec 1, 2025 39168720K ACTIVE CLASS - 2 OBSERVED ON THE1ST AND 2ND FLOOR SPRINKLER HEADS OBSTRUCTED, THE ROOF VENT TERMINAL NOT PROPERLY SUPPORTED AND FERNCO... $1,280 $1,280 Dec 17, 2026
Dec 1, 2025 39168676M ACTIVE CLASS - 2 FOUND LOCHINVAR GAS FIRED BOILER MODEL #CWN-360, WITH INCORRECT SAFETY RELIEF VALVE,EXPOSED WIRING, LABEL ON RELIEF V... $1,280 $1,280 Dec 17, 2026
Feb 3, 2025 39137264Y RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED FIRE EMERGENCY EXIT BLOCKED BY SEVERAL GARBAGE BINS. LOCATE... $1,250 $1,250 Jun 13, 2025
Feb 3, 2025 39137265X RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $2,500 $2,500 Jun 13, 2025
Feb 3, 2025 39137267J RESOLVE CLASS - 1 I OBSERVED IN DOB RECORDS C OF C0276086 STATING THAT THE VIOLATING CONDITIONS OF ECB#39103082H WERE CORRECTED BY GILB... $0 $0 Jun 13, 2025
Feb 3, 2025 39137268L RESOLVE CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB #39103080Y ISSUED ON 01/09/2024 FOR ELECT... $2,500 $2,500 Jun 13, 2025
Feb 3, 2025 39137269N RESOLVE CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE STORAGE OF BUILDING MATERIAL, OFFICE MATERIALS AND EQUIPMENT. AS PER THE E... $3,000 $3,000 Jun 13, 2025
Feb 3, 2025 39137263M RESOLVE CLASS - 1 UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED UNSAFE STORAGE (BOXES, BROOMS, ELECTRICAL SCOOTER, BUI... $2,500 $1,686 Jun 13, 2025
Feb 3, 2025 39137266H RESOLVE CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB# 39103082H ISSUED ON 01/09/2024 FOR EXCES... $6,250 $6,250 Mar 2, 2026
Dec 11, 2024 39132608X RESOLVE CLASS - 2 INOPERATIVE CA PHONE. MISALIGNED CAB MIRROR. SHORTEN GOVERNOR ROPE. REPLACE GIBS WHERE NEEDED. SECURE GIBS WHERE NEED... $0 $0 Feb 21, 2025
Jan 9, 2024 39103080Y ACTIVE CLASS - 1 I OBSERVED IN THE CORRIDORS THE IMPROPER INSTALLATION OF EMERGENCY LIGHT FIXTURES WITH EXPOSED, ENERGIZED CONDUCTORS.... $1,600 $0 May 3, 2024
Jan 9, 2024 39103081X RESOLVE CLASS - 2 I OBSERVED IN THE ROOFTOP ELEVATOR ROOM A DEFECTIVE GFCI OUTLET, AND IN THE BOILER ROOM FAILURE TO PROVIDE GFCI PROTE... $1,200 $0 May 3, 2024
Jan 9, 2024 39103082H RESOLVE CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM EXCESSIVE STORAGE OF BUILDING MATERIALS, OFFICE EQUIPMENT AND APPLIANCES. AS P... $1,200 $0 May 3, 2024
Jan 3, 2024 39102702P RESOLVE CLASS - 2 GARBAGE BINS BLOCKING EMERGENCY EXITS, GROUND LEVEL, EXPOSURE #3., PROVIDE PROPER CORRIDOR WIDTH $0 $0 Apr 5, 2024
Jan 3, 2024 39102704Z RESOLVE CLASS - 2 IMPROPER AND UNSAFE STORAGE UNDERNEATH ALL STAIRCASES, AND INSIDE MECHANICAL ROOMS, GROUND LEVEL, REPAIR AND/OR REPLACE $0 $0 Apr 12, 2024
Jan 3, 2024 39102703R RESOLVE CLASS - 1 EXPOSED WIRES LEADING FROM THE UNSEALED CEILING RECEPTICAL TO THE EMERGENCY EXIT SIGN LEAVIING THE EMERGENCY SIGN AN ... $1,600 $0 May 3, 2024
Jan 3, 2024 39102700L RESOLVE CLASS - 2 MULTIPLE EMERGENCY LIGHTS DO NOT FUNCTION THROUGHOUT BUILDING, REPAIR/REPLACE LIGHTING $625 $0 Apr 12, 2024
Jan 3, 2024 38275505P RESOLVE CLASS - 2 2X10,40D10,AND 41L10 IN CAR COMMUNICATION(PLAN)INOPERATIVE REPAIR.MACHINE ROOM RAILING UNSERVICABLE MUST REPAIR OR PR... $1,250 $0 May 3, 2024
Jan 3, 2024 39102701N RESOLVE CLASS - 2 LARGE HOLE MADE IN ELEVATOR ROOM WALL TO INSTALL AN AC UNIT LEAVING THE EXTERIOR FACADE, AND INTERIOR FRAMING WALL ST... $0 $0 Aug 12, 2024
Jun 10, 2022 39063872Z RESOLVE CLASS - 2 AT GROUND LEVEL, EMERGENCY EXIT ROUTE TO THE BACKYARD, OBSTRUCTED BY GARBAGE CANS, WHICH MAKE EMERGENCY EXIT DIFFICUL... $0 $0 Jul 29, 2022
Jun 10, 2022 39063871R RESOLVE CLASS - 2 AT ROOF LEVEL , SUPPORT STRUCTURE, METAL MESH FENCE, AROUND THE ROOF, LOOSE, WITHOUT ANCHORS ON THE CORNER JOINTS, AL... $0 $0 Jul 29, 2022
Jun 10, 2022 39063873K RESOLVE CLASS - 2 AT GROUND LEVEL,SPRINKLER RM & FIRE CONTROL PANEL RM, ENCLOSING WALLS OF THE ROOMS, UNFINISHED, WITH EXPOSED SUPPORT ... $0 $0 Jul 29, 2022
Apr 9, 2022 39059990H RESOLVE CLASS - 1 CLASS 1 VIOLATION ISSUED, CAR TOP RUN BOX INSPECTION SWITCH NOT WORKING, REMEDY; REPAIR THEN NOTIFY NYCDOB OF WORKING... $1,250 $0 Dec 12, 2022
Mar 10, 2022 39057836K RESOLVE CLASS - 1 CLASS 1 RTS, / UPON INSPECTION. THE DEVICE IS FOUND TO BE OUT-OF-SERVICE AS PER 1 RCNY 11-02 , REMEDY; RESTORE TO SER... $1,250 $0 Sep 9, 2022
Dec 10, 2020 39033298X RESOLVE CLASS - 1 FOUND ONE WEIL MCLAIN LGB-11 SERIES 2 BOILER IN 1ST FL BOILER ROOM. MAWP 50 PSI WITH PRESSURE RELIEF VALVE RATED AT 7... $1,250 $0 Jan 29, 2021
Jan 21, 2020 35467752J RESOLVE CLASS - 1 NEW BLDG OR OPEN LOT OCCUPID W/O VALID COFO.NOTED AT TIME OF INSPECYTION IOBSERVED JOB#200805021 NB IS OCCUPIED UNDER... $0 $0 May 8, 2020
Dec 13, 2019 35459418Y RESOLVE CLASS - 1 BLDG OR OPEN LOT OCCUPIED W/O A VALID CERT OF OCCUPANCY. NOTE: JOB#200805021 NEW BLDG IS OCCUPIED UNDER T.O.C.#200805... $0 $0 Jul 16, 2021
Oct 31, 2019 39012113H RESOLVE CLASS - 1 NOTED: NEW BUILDING ERECTED UNDER JOB APPLICATION #200805021 IS OCCUPIED UNDER T.C.O. 200805021T005 WHICH EXPIRED ON ... $0 $0 Jul 16, 2021
Jul 22, 2019 35426834M RESOLVE CLASS - 1 FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35415312L ISSUED ON 5/14/19 AND TO FILE ... $0 $0 Jul 16, 2021
Jul 22, 2019 35401499N RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35293818X ISSUED ON 05/14/19 & TO FILE A C OF C PURSUAN... $0 $0 Sep 6, 2019
Jul 22, 2019 35442172M RESOLVE CLASS - 1 BLDG OR OPEN LOT OCCUPIED W/O A VA;LID CERT OF OCCUPANCY. NOTED: AT TIME OF INSPECTION C OF O#20080521T005 EXP ON 5-8... $0 $0 Sep 6, 2019
Jul 22, 2019 35401497J RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35415311J ISSUED ON 05/14/19 & TO FILE A C OF C PURSUAN... $0 $0 Jul 16, 2021
Jun 27, 2019 38270273M RESOLVE CLASS - 1 C/U 76M07,39I10,26B07;(79-M)CEASE USE ITEM PROVIDE AND CONTACT NYC DO B FOR RE-INSPECTION TO RESTORE TO SERVICE,(39-I... $1,250 $0 Aug 16, 2019
May 14, 2019 35415312L RESOLVE CLASS - 1 WORK WITHOUT PERMIT. OBSERVED ON 5/14/19 AT ABOVE ADDRESS GAS PIPING BEING INSTALLED ON TEH 7 AND 8 FLOOR ABOUT 10% O... $1,250 $0 Jul 26, 2019
May 14, 2019 35415311J RESOLVE CLASS - 1 WORK WITHOUT A PERMIT. OBSERVED ON 5/14/19 AT ABOVE ADDRESS PLUMBING WORK AND SANITARY VENT STACKS AS WELL AS HOT AND... $1,250 $0 Jul 26, 2019
May 14, 2019 35293819H RESOLVE CLASS - 1 BUILDING OR OPEN LOT OCCUPIED W/O A VALID CERTIFICATE OF OCCUPANCY.NOTED: BUILDING ERECTED UNDER APPLICATION #NB20080... $0 $0 Jul 26, 2019
May 14, 2019 35293818X RESOLVE CLASS - 1 WORK WITHOUT A PERMIT. NOTED: OBSERVED ON THE 7TH AND 8TH FLOOR "F" LINE UNITS LAYOUT CONFIGURATION CHANGED,ENTRANCE ... $1,250 $0 Jul 26, 2019
May 10, 2019 35422556N RESOLVE CLASS - 1 BUILDING OR OPEN LOT OCCUPIED W/O A VALID C OF O. NOTED:AT TIME OF INSPECTION C OF O#200805021T005 EXPIRED ON 5/8/12 ... $0 $0 Jul 26, 2019
Apr 15, 2019 39002205X RESOLVE CLASS - 2 CORRECT ALL VIOLATING CONDITIONS, SUBMIT A CERTIFICATE OF CORRECTION. $0 $0 Jun 7, 2019
Mar 6, 2019 35400476X RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35373066M ISSUED ON 01/09/19 AND TO FI... $0 $0 Aug 21, 2019
Jan 4, 2019 38267095L RESOLVE CLASS - 2 1.L.10,2.L.10,10.B.7,45.M.7,40.I.10,59.M.7,71.L.10,99.M.7=(1,L,10)EMERGENCY STOP SWITCH WORK BUT NO BUZZER(9,L,10)ALA... $0 $0 Mar 1, 2019
Nov 20, 2018 35370040K RESOLVE CLASS - 1 NEW BUILDING OR LOT OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY C OF O #20080502IT005 EXPIRED 5/8/12. REM: COMP... $1,250 $0 Jan 10, 2019
Nov 16, 2018 35372701H RESOLVE CLASS - 3 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED ON 11/16/2018 AT 731 SOUTHERN BLVD NO SPRINKLER CAGES... $500 $0 Feb 1, 2019
Nov 13, 2018 38261947P RESOLVE CLASS - 1 97X10 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. SERVICE EQUIPMENT ELEVATOR PER BC 3001-227-987 DOB RECOR... $312 $0 Jan 10, 2019
Oct 19, 2018 38265993Y RESOLVE CLASS - 1 61M7,68M7,68M7,97X10. 61M7-CURRENT ELEVATOR PROVIDE TAGGED MISSING ONMAINLINE; 68M7-PROVIDE MAINTENANCE LOG; 68M7-PRO... $1,250 $0 Dec 7, 2018
Oct 15, 2018 37013134Z RESOLVE CLASS - 2 FAILURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPUR... $625 $0 Mar 15, 2019
Sep 26, 2018 35361564R RESOLVE CLASS - 1 NEW BUILDING OR LOT OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY. C OF O #200805021T005 EXPIRED 5/8/12 REMEDY:CO... $0 $0 Nov 16, 2018