ECB violations
1145-1147 Southern Boulevard, Bronx • Block 02728 • Lot 0034
37 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 27, 2025 | 39164911P | RESOLVE | CLASS - 1 | CEASE USE ITERM: BRAKE MONITOR SWITCH BYPASSED. ADJUST FOR PROPER TENSION FOR GOVERNOR ROPE. . REMEDY: RESTORE TO SER... | $1,250 | $0 | Jan 2, 2026 |
| Oct 27, 2025 | 39164910N | RESOLVE | CLASS - 1 | CEASE USE ITEM: BRAKE MONITORING SWITCH BYPASSED. REMEDY: RESTORE TO SERVICE IMMEDIATELY AND EMAIL THE ELEVATOR DIVIS... | $1,250 | $0 | Jan 2, 2026 |
| Dec 20, 2024 | 39133479N | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF EXITING DOORS THROUGHOUT 1ST FLOOR. POTENTIAL FIRE OR EVACUATION HAZARD... | $625 | $0 | Mar 7, 2025 |
| Dec 20, 2024 | 39133480K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Mar 7, 2025 |
| Dec 20, 2024 | 39133481M | RESOLVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED COMNUSTILBE MATERIALS UNDER STAIRCASE A AND B. (TOOLS,... | $2,500 | $0 | Mar 7, 2025 |
| Dec 20, 2024 | 39133482Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED UNPERMITTED ACCESS PANELS THROUGHOUT BUILDING. PLASTI... | $1,250 | $0 | Mar 7, 2025 |
| Sep 11, 2023 | 39094476Z | RESOLVE | CLASS - 2 | MISSING MOTOR ROOM SIGNAGE; CLEAN ELEVATOR PIT; REPAIR PHONE IN ELEVATOR | $625 | $0 | Nov 17, 2023 |
| Sep 11, 2023 | 39094477K | RESOLVE | CLASS - 2 | REPLACE GOVERNORS ROPES BECAUSE OF ROUGHING AND RUSTPPROVIDE MOTOR ROOM SIGNAGE; REAPIR EMERGENCY PHONE | $625 | $0 | Nov 17, 2023 |
| Apr 19, 2023 | 38274812K | RESOLVE | CLASS - 1 | 59-A-10.59-BRAKE MONITOR SWITCH ALTERED.DISABLE SWITCH WITH CAR SWITCHES BY REMOVING BOLTS THAT MONITOR WEAR OF BREAK... | $1,250 | $0 | Jun 30, 2023 |
| Apr 19, 2023 | 39084200Z | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP GENERATOR DISCONNECT SWITCH THE IMPROPER FUSING OF THE CONDUCTORS, I NOTED THE FUSES RATED ... | $2,430 | $0 | Jan 16, 2024 |
| Apr 19, 2023 | 39084199K | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOFTOP DEFECTIVE FANS. I NOTED THE FANS WERE OFF, THE CIRCUIT BREAKERS WERE IN THE TRIPPED POSITIO... | $400 | $0 | Jun 30, 2023 |
| Apr 19, 2023 | 39084223L | RESOLVE | CLASS - 2 | OBSERVED SPRINKLER HEAD IS OBSTRUCTED BY CEILING. AS PER PC 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, ... | $312 | $0 | Jun 30, 2023 |
| Apr 19, 2023 | 38274811Z | RESOLVE | CLASS - 1 | 59BB5, 59A10: 59-BRAKE MAINTENANCE TAG EXPIRED MUST PERFORM AND FILE FOR TEST ON TAG AND MCP BY CONTROLLER. 59-BRAKE ... | $1,250 | $0 | Jun 30, 2023 |
| Nov 12, 2021 | 39051034L | RESOLVE | CLASS - 1 | ROPE GRIPPER DEFECTIVE UNABLE TO RESET NO OIL(CU). BRAKE TAG EXPIRED ON 9/25/20. IN CAR PHONE NOT WORKING. MUST HAVE ... | $1,280 | $0 | Jan 7, 2022 |
| Nov 12, 2021 | 39051035N | RESOLVE | CLASS - 2 | BRAKE TAG EXPIRED ON 9/25/20. | $655 | $0 | Jan 7, 2022 |
| May 28, 2019 | 35387718X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISISONERS ORDER CONTAINED IN SUMMONC/VIOLATIONS #35379751H ISSUED ON 11-13-18 N TO FIL... | $0 | $0 | Oct 17, 2019 |
| May 28, 2019 | 35422420Y | RESOLVE | CLASS - 1 | FILED A CERTIFICATE OF CORRECTION OR OTHER RELATED MATEIRALS CONTAINING MATERIAL FALSE STATEMENTS.OBSERVED THE VIOLAT... | $5,000 | $0 | Oct 17, 2019 |
| May 28, 2019 | 35387719H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISISONERS ORDER CONTAINED IN SUMMONC/VIOLATIONS #35379751H ISSUED ON 11-13-18 N TO FIL... | $0 | $0 | Oct 17, 2019 |
| May 28, 2019 | 35387717Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISISONERS ORDER CONTAINED IN SUMMONC/VIOLATIONS #35379750X ISSUED ON 11-13-18 N TO FIL... | $0 | $0 | Oct 17, 2019 |
| Feb 26, 2019 | 38268363N | RESOLVE | CLASS - 1 | CU5A10 DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLE. THIS IS A SAFETY FEATURE TO ENSURE PASSENGERS SAFETY. | $1,250 | $0 | Apr 19, 2019 |
| Nov 13, 2018 | 35379752J | RESOLVE | CLASS - 3 | FAILURE TO PROVIDE REQUIRED CIRCUIT DIRECTORY/IDENTIFICATION.OBSERVED ON ALL FLOORS PANELS INSTALLED MTH BRANCH CIRCU... | $100 | $0 | Feb 1, 2019 |
| Nov 13, 2018 | 35379750X | RESOLVE | CLASS - 1 | EC240.22.IMPROPER FUSES OF NEUTRAL.OBSERVED IN ELEVATOR MOTOR ROOM IN 30 AMP DISCONNECT THE FUSING OF THE NEUTRAL SUP... | $400 | $0 | May 10, 2019 |
| Nov 13, 2018 | 35379751H | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTER(GFCI)PROTECTION.OBDERVED IN MECHANICAL AND ELEVATOR ROOMS THE INS... | $1,200 | $0 | May 10, 2019 |
| Nov 13, 2018 | 35379754N | RESOLVE | CLASS - 1 | MC1006.8.1.FAILURE TO PROVIDE REMOTE SHUT OFF.OBSERVED ON ALL FLOORS GAS FIRED HEATING SYSTEMS WITH LOCAL SHUTOFF SWI... | $400 | $0 | May 10, 2019 |
| Nov 13, 2018 | 35379753L | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE/MAINTAIN SUFFICIENT ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIPMENT.OBSERVED IN LAUNDRY ROOM, THE INS... | $250 | $0 | Feb 1, 2019 |
| Dec 11, 2017 | 38259571N | RESOLVE | CLASS - 2 | 6X10)DOOR POSITION MONITORING SYSTEM IS INOPERATIVE DPMS, REPAIR. IF NOT IN SYSTEM, FILE APPLICATION TO INSTALL, ASAP. | $500 | $0 | Feb 2, 2018 |
| Dec 24, 2007 | 34614156Y | RESOLVE | Hazardous | JOB SITE FENCE DEFECTIVE CHAIN LINK WITH PLY BOARD FENCE AT SOUTHERN BLVD IS LEARNING TOWARDS SIDEWAY IN DANGER OF CO... | $500 | $0 | Feb 15, 2008 |
| Apr 29, 2007 | 34568249Z | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN RETAINING WALL AT REAR OF PREMISES,EXPOSURES.THE RETAINING WALL AT NORTHWEST OF PREMISES COLLASPE... | $800 | $0 | Sep 21, 2007 |
| Mar 3, 2007 | 34559661X | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN FENCE AT CONSTRUCTION SITE.DEFECT:PLYWOOD FENCE & CHAIN LINK FENCE ARE BROKEN,OUT OF PLUMB & COLL... | $400 | $0 | Apr 20, 2007 |
| Jan 31, 2007 | 34563318K | RESOLVE | Hazardous | FAILURE TO MEET ADJOINING STRUCTURE DURING CONST OPERATIONS. NOTED: THE RETAINING WALL AT THE REAR OF PREMISES HAS CO... | $1,000 | $0 | Nov 16, 2007 |
| Jan 31, 2007 | 34563317Z | RESOLVE | Hazardous | JOB SITE FENCE DEFECTIVE. NOTED: CONST FENCE UNSTABLE IN DANGER OF FALLING IN & OUT VACANT LOT, CONST FENCE IS MISSIN... | $500 | $0 | Nov 16, 2007 |
| Jan 31, 2007 | 34563319M | RESOLVE | Hazardous | WORK W/O A PERMIT. HAZARDOUS NOTED: CONST FENCE BEEN ERECTED AT FRONT OF VACANT LOT W/O A DOB PERMIT. REMEDY: OBTAIN ... | $800 | $0 | Nov 16, 2007 |
| Jan 31, 2007 | 34563320J | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE CONTRACTORS SIGN AT TIME OF INSP. REMEDY: PROVIDE CONTRACTOR'S SIGN. | $500 | $0 | Nov 16, 2007 |
| Dec 8, 2006 | 34548241X | RESOLVE | Hazardous | JOB SITE FENCE DEFECTIVE:CHAIN LINE FENCE W/LEVEL METAL POSTS ERECTED UNDER APPL#200901710 WHICH EXPIRES 12/31/05 HAS... | $500 | $0 | Apr 20, 2007 |
| Sep 27, 2006 | 34540120N | RESOLVE | Hazardous | FAILURE TO PROVIDE ADEQUATE PROTECTION FOR SIDEWALK DURING CONSTRUCTION OPERATIONS THE FENCE ON SOUTHERN BLVD IS INAD... | $2,000 | $0 | Apr 20, 2007 |
| Sep 27, 2006 | 34540119X | RESOLVE | Hazardous | FAILURE TO MEET ADJOINING STRUCTURE DURING CONST OPERATIONS THE RETAINING WALL @ THE REAR OF PREMISES HAS COLLAPSED O... | $1,000 | $0 | Mar 8, 2007 |
| Sep 22, 2006 | 34530766N | RESOLVE | Hazardous | FAILURE TO SAFEGUARD PUBLIC & PRIVATE PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. WORK BEING PERFORMED UNDER APPL 2... | $1,000 | $0 | Apr 20, 2007 |