ECB violations
1021-1029 Bruckner Boulevard, Bronx • Block 02746 • Lot 0001
82 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 5, 2025 | 39159395L | RESOLVE | CLASS - 2 | FIRE STOPPING MISSING THROUGHOUT VARIOUS LOCATIONS AT WALL PENETRATION AT BASEMENT LEVEL., PROVIDE/MAINTAIN FIRE STOP... | $0 | $0 | Nov 21, 2025 |
| Sep 5, 2025 | 39159394J | RESOLVE | CLASS - 2 | OBSERVED STAIRCASES PAN FOR STEPS FROM GROUND FLOOR AND SECOND FLOOR ROTTED WITH HOLES. SAME CONDITIONS OBSERVE AT EX... | $0 | $0 | Nov 21, 2025 |
| Sep 5, 2025 | 39159396N | RESOLVE | CLASS - 2 | CELLAR LEVEL CONCRETE CEILING DETERIORATED UNDER THE APT 1C SECTION OF BUILDING & STARTING TO COME APART. SOME SECTIO... | $0 | $0 | Nov 21, 2025 |
| Oct 28, 2020 | 39031195Y | RESOLVE | CLASS - 2 | CORROSION ON COLD WATER PIPING-BODY DRAINS NOT INSTALLED ON SAFETY VALVE-UNCAPPED PIPING, VALVE AT SIDE OF BOILER- EX... | $0 | $0 | Jan 29, 2021 |
| Apr 13, 2018 | 32096635L | RESOLVE | CLASS - 2 | 50A,50B,50C,50D,50E-AS PER CLASS 2 (B254) 28-301.1 FAILURE TO MAINTAIN. 50A)GAS TRAIN NOT SUPPORTED. 50B)HOLE IN CEIL... | $625 | $0 | Jun 29, 2018 |
| Jan 22, 2018 | 35312631R | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT & CERTIFY SUMMONS#35293699M ISS... | $0 | $0 | Mar 16, 2018 |
| Jan 9, 2018 | 35282225R | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35294401P ISSUED ON 10/12/17 AND TO FI... | $2,400 | $0 | Mar 2, 2018 |
| Jan 9, 2018 | 35282226Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35221222M ISSUED ON / / AND TO FILE A ... | $2,400 | $0 | Mar 2, 2018 |
| Nov 30, 2017 | 35280400X | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#35221222M ISSUED ON 11/14/16 AND TO FIL... | $2,400 | $0 | Jan 19, 2018 |
| Oct 13, 2017 | 35280030H | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35221222M ISSUED ON 11/14/16 AND TO FI... | $6,000 | $0 | Jan 19, 2018 |
| Oct 12, 2017 | 35294401P | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT.OBSERVED IN OIL TANK ROOM IN CELLAR RECENTLY INSTALLED WATER SUPPLY AND SANITARY WASTE PIPING F... | $1,600 | $0 | Jan 19, 2018 |
| Oct 12, 2017 | 35290624Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:NO FIRE STOPPING PER BC 712.3;27-345 NOTED:OBSERVED AT BASEMENT... | $0 | $0 | Dec 1, 2017 |
| Oct 12, 2017 | 35294402R | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED.OBSERVED IN OIL TANK ROOM IN CELLAR RECENTLY INSTALLED WATER SU... | $1,000 | $0 | Jan 19, 2018 |
| Oct 12, 2017 | 35293698K | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS.OBSERVED @WATER MAIN LOCATED INSIDE OIL TANK ROOM IN BSMT:MAIN GROUNDING CONDUCT... | $4,800 | $0 | Jan 19, 2018 |
| Oct 12, 2017 | 35293699M | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS,DEVICES,MATERIALS,APPLIANCES OR WIRING IN USE.OBSERVED T... | $4,000 | $0 | Jan 19, 2018 |
| Oct 10, 2017 | 35274108H | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. IN 8/3/17 2 ELECTRICAL VIOLATIONS WAS ISSUE TO THE R... | $2,400 | $0 | Jan 19, 2018 |
| Jun 12, 2017 | 35286902N | RESOLVE | CLASS - 1 | SEC. 401.1 MISC VIOLATION GAS PIPING NOT LABELED OBSERVED ON 6-12-17 AT THE ABOVE ADDRESS GAS PIPING IN BASEMENT NOT ... | $400 | $0 | Sep 15, 2017 |
| Jun 12, 2017 | 35270665M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:ROOF LEVELTHROUGHOUT BY PARAPET WALLS ROOFING MATERIAL SE... | $0 | $0 | Aug 4, 2017 |
| Jun 12, 2017 | 35270664K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:NO FIRE STOPPINGPER BC712.3;27-345.NOTED:CELLAR LEVEL MISSING F... | $0 | $0 | Aug 4, 2017 |
| Jun 12, 2017 | 35287448R | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. OBSERVED EMT CONDUCTS & MC CABLES NEWLY INSTALLED TO VARIOUS LOCATIONS FOR LIGHTS & POW... | $400 | $0 | Jan 19, 2018 |
| Jun 12, 2017 | 35287447P | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT MATERIALS,APPARATUS,DEVICES,APPLIANCE,OR WIRING IN USE. OBSERVED IM... | $1,600 | $0 | Jan 19, 2018 |
| May 27, 2017 | 35275799K | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUM/VIO#35221222M ISSUED ON 11/14/16 & TO FILE A C OF C PURSUANT TO... | $6,000 | $0 | Oct 20, 2017 |
| Mar 18, 2017 | 35234999Y | RESOLVE | CLASS - 1 | UNLAWFUL ACTS;FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.AT THE TIME OF MY INSPECTION DOB RECORDS INDICATED ... | $6,000 | $0 | May 5, 2017 |
| Jan 17, 2017 | 35229692N | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35221222M ISSUED ON 11-14-16 & TO FI... | $2,400 | $0 | Mar 3, 2017 |
| Nov 14, 2016 | 35216872H | RESOLVE | CLASS - 2 | WOKR W/O A PERMIT. WORK NOTED: AT CELLAR LEVEL ERECTED FULL HEIGHT PARTITIONS FOR 2 ROOMS,BATHROOM ENCLOSURE & INSTAL... | $0 | $0 | Jan 6, 2017 |
| Nov 14, 2016 | 35221222M | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. AT THE TIME OF MY INSPECTION 1:35PM ON 11/14/16 AT THE ABOVE PLACE OF OCCURANCE ADDRESS I OBSERVED... | $1,600 | $0 | Feb 24, 2017 |
| Nov 14, 2016 | 35216873J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. DEFECTS NOTED: RIGHT SIDE FACADE(BRUCKNER BLVD)HAS (PAN) ON FIRE E... | $250 | $0 | Jan 6, 2017 |
| Jun 1, 2016 | 35195275J | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. WORK NOTED: AT CELLAR LEVEL ERECTED FULL HEIGHT PARTITIONS FOR 2 ROOMS,BATHROOM ENCLOSURE & INSTAL... | $0 | $0 | Mar 24, 2017 |
| Jun 1, 2016 | 35195124M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. DEFECTS NOTED: RIGHT SIDE FACADE(BRUCKNER BLVD)PAN ON FIRE ESCAPE ... | $250 | $0 | Mar 24, 2017 |
| Jun 1, 2016 | 35195123K | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. DEFECTS NOTED: BULKHEAD EXIT DOOR IS NOT SEPF CLOSING. REMEDY: COMPLY W/NOTICE OF VIOLATION. | $2,500 | $0 | Jul 29, 2016 |
| Jan 30, 2011 | 34859642P | RESOLVE | CLASS - 1 | SEC. 1020.2 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED: UPON INSPECTION AT STAIRWAY IS BLOCKED W/DEBRIS. ... | $1,000 | $0 | Jul 1, 2011 |
| Nov 7, 2007 | 34619120P | RESOLVE | Hazardous | FAILURE TO MAINTAIN INTERIOR. 1ST FLR COMMERCIAL STORE HAS CEILING PARTIALLY MISSING W/ WOOD DEBRIS FALLING DOWN. WAT... | $0 | $0 | Feb 15, 2008 |
| Jun 7, 2007 | 34567688X | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN INTERIOR OF BLDG. DEFECT: THE FLR ON EXPOSURE 4 HAS COLLAPSED TO BASEMENT. THE COLLAPSE APPEARS T... | $800 | $0 | Aug 24, 2007 |
| Jan 26, 2005 | 34445483R | RESOLVE | Hazardous | FAILURE TO COMPLY WITH AN ORDER OF THE DEPARTMENT.NOTED:CRACK IN BRICK WALL RUNNING FROM FIRE ESCAPE ROOF LANDING TO ... | $1,500 | $0 | Mar 28, 2006 |
| Jan 26, 2005 | 34445482P | RESOLVE | Hazardous | 20050805YCTURAL CRACK IN FACADE BRICK WORK,AT TOP LEVEL OF SOUTHERN FIRE ESCAPEAT REAR OF BLDG.AND INTERSECTING AND W... | $2,000 | $0 | Mar 28, 2006 |
| Mar 23, 2004 | 34423739Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT IS CRACK IN BRICK WALL FREOM ESCAPE ROOF BASKET TO TOP OF FIFTH STO... | $2,500 | $0 | May 7, 2004 |
| Aug 2, 2001 | 34289408P | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. HORIZONTAL CRACKS, LOOSE BRICKS, AND RUSTED SAGGING LINTELS ABOVE FIFTH F... | $2,500 | $0 | Sep 21, 2001 |
| Aug 2, 2001 | 34289407N | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. WORK NOTED: INSTALLED A 4' X 4' OPENING BETWEEN CELLAR AND FIRST FLOOR STORE COMPRIMING FIRE R... | $2,500 | $0 | Oct 26, 2001 |
| Aug 2, 2001 | 34289405J | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING. DEFECT IS: (1) PLASTER CEILING IS SAGGING, BROKEN AND DEFECTIVE AT VARIOUS LOCATION OF ... | $2,500 | $0 | Oct 26, 2001 |
| Aug 2, 2001 | 34289406L | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY BUILDING DEPT. RECORDS. LEGAL USE: STORAGE CURRENTS USE: HOUSEAPPLIANCE REQUIRE... | $2,500 | $0 | Oct 26, 2001 |
| May 14, 2001 | 34271139K | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG WALL.(DEFECT)DEFECTIVE AND CROCKED BRICKWORK WITH DEFECTIVE AND ROTTED STEEL WINDOW... | $2,500 | $0 | Jul 6, 2001 |
| Apr 26, 2000 | 34233628Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECT IS: SOGGING AND OBFECTIVE PRIVATE HALL APPROX.2TO3 INCHES AND CRACKED AND DEFECTIVE CERAMI... | $2,500 | $0 | Jun 9, 2000 |
| Apr 26, 2000 | 34233629X | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT IS:VERTICAL CRACKS IN BRICK WORK ON THE 5TH FL. SOUTH WALL(BRUBCKNE... | $2,500 | $0 | Jun 9, 2000 |
| Oct 22, 1998 | 34171285K | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING. DEFECT IS: BROKEN & DEFECTIVE CEILING BEAMS AT EAST SIDE 1027 BRUCKNER BLVD. 1ST STORY ... | $2,500 | $0 | Dec 11, 1998 |
| Sep 29, 1997 | 34135976L | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. WORK NOTED CONSTRUCTED INTERIOR PARTITION IN CENTER OF STOREIN HALFAND CREATING BATHROOM IN RE... | $1,000 | $0 | Jan 9, 1998 |
| Sep 25, 1997 | 34149520K | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT WORK NOTED INSTALLED HUNG CEILING AT FRONT OF STORE. REMEDY: FILE & OBTAIN APPROVAL A PERMIT /O... | $1,000 | $0 | Jan 9, 1998 |
| Sep 25, 1997 | 34149521M | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT WORK NOTED CONSTRUCTED OF STAIRS & PLATFORM IN REAR OF COURTYARD TO REAR ENTRANCE OF LOBBY. CON... | $1,000 | $0 | Jan 9, 1998 |
| Nov 21, 1995 | 34126684P | RESOLVE | Non-Hazardous | REPLACED EXTERIOR STAIRS AND PLATFORM AT REAR EXIT OF BUILDING WITH WOOD. REMEDY: REPLACE STAIRS AND PLATFORM WITH NO... | $350 | $0 | May 10, 1996 |
| Jan 12, 1995 | 34117193X | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE VENTILATION IN BATHROOM AT REAR OF CORNER STORE(DE-LI) REMEDY:PROVIDE VENTILATION FOR REMOVE BATHR... | $0 | $0 | Apr 10, 1995 |
| Jan 12, 1995 | 34117191M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. DEFECT IS: COMBUTIBLE MATERIAL USED TO COVER CEILING AT FRONT OF COMMERCIAL SPACE. REMEDY: REMOV... | $1,000 | $0 | Mar 31, 1995 |