ECB violations
1211-1213 Seneca Avenue, Bronx • Block 02761 • Lot 0043
46 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 8, 2026 | 39191636N | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE MAIN ELECTRICAL ONE NEW PANEL INSTALLED 20/40 CKT, THAT REPLACED A ... | $2,500 | $0 | Jul 10, 2026 |
| Jun 8, 2026 | 39191699K | ACTIVE | CLASS - 1 | 3 BOILERS NOT WOKING, RESTROOMS NOT EQUIPED WITH OPEN ENDED TOILET SEATS.PER PC .420.3 WATER CLOSETS SHALL BE EQUIPPE... | $2,500 | $0 | Jul 10, 2026 |
| Jun 8, 2026 | 39191638R | ACTIVE | CLASS - 1 | ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL RM THE STO... | $1,200 | $0 | Jul 10, 2026 |
| Jun 8, 2026 | 39191637P | ACTIVE | CLASS - 1 | FAILURE TO PROTECT CONDUCTOR(S) AGAINST OVERCURRENT. OBSERVED IN THE ELEVATOR MACHINE RM THE DISCONNECT SW THE FUSES ... | $4,800 | $0 | Jul 10, 2026 |
| Jun 13, 2025 | 39151012Z | ACTIVE | CLASS - 1 | AT TIME OF INSPECTION I OBSERVED EMERGENCY EGRESS WAY BLOCKED BY BUILDING MAINTENANCE SUPPLIES AND PARTS. ALSO FIRE E... | $1,250 | $0 | Jul 4, 2025 |
| Jun 10, 2025 | 39150565Y | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS ... | $1,250 | $0 | Jul 4, 2025 |
| Jun 10, 2025 | 39150633R | ACTIVE | CLASS - 2 | I FOUND A HYDROTHERM MR1500BP A MODULAR BOILER WITH TWO BOILER OF THE SIX ARE DISCONNECTED AND A THIRD BOILER IS LEAK... | $1,250 | $0 | Jul 4, 2025 |
| Jun 9, 2025 | 39150424K | ACTIVE | CLASS - 1 | : FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON IN... | $1,250 | $0 | Jul 4, 2025 |
| Oct 2, 2023 | 39096214H | ACTIVE | CLASS - 2 | -EMERGENCY FENCE EXIT DOORS AND HARDWARE DO NOT OPEN AND OR UNLATCH, LOCATED AT EXSPOSURE 2 & 3, PROVIDE LEGAL HARDWARE | $625 | $0 | Oct 10, 2023 |
| Oct 2, 2023 | 39096245K | ACTIVE | CLASS - 2 | OBSERVED ACTIVE LEAK IN THE BOILER ROOM ON 1 1/4 BALL VALVE ALSO ACTIVE LEAK IN STAFF RESTROOM LOCATED ON GROUND FLOO... | $625 | $0 | Oct 10, 2023 |
| Oct 2, 2023 | 38274982N | ACTIVE | CLASS - 1 | 97-X-17=ENTIRE DEVICE INOPERATIVE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS COND... | $3,125 | $0 | Oct 27, 2023 |
| Oct 2, 2023 | 39096216L | ACTIVE | CLASS - 2 | -CRACKS ON FACADE AND OBOVE WINDOW LENTALS, LEADING TO INTERIOR LEAKS LOCATED AT EXPOSURE 2 & 3 SIDE., REPAIR AND/OR ... | $625 | $0 | Oct 10, 2023 |
| Oct 2, 2023 | 39096215J | ACTIVE | CLASS - 2 | -EMERGENCY EXITS DOORS, DO NOT SELF-CLOSE LOCATED AT OFFICE SPACE EXPOSURE 1 AND BOILER ROOM MECHANICAL ROOM. ALSO, E... | $625 | $0 | Oct 10, 2023 |
| Oct 2, 2023 | 39096213X | ACTIVE | CLASS - 2 | -SIGNIFICATE BUBLING LOCATED ON ROOF., REPAIR AND/OR REPLACE | $625 | $0 | Oct 10, 2023 |
| May 17, 2023 | 39086473N | ACTIVE | CLASS - 2 | OBSERVED IN BASEMENT/CELLAR UNAPPROVED COUPLING INSTALLED ON PIPPING. AS PER PC 102.3 MAINTENANCE. INSTALLATIONS, BOT... | $625 | $0 | May 29, 2023 |
| May 11, 2023 | 39086086N | ACTIVE | CLASS - 2 | AS PER ONE WEIL MCLAIN LGB-9 HOT WATER HEATING BOILER IN BASEMENT. PERMIT NO. X00242139. BOILER NOT REGISTERED., MAIN... | $625 | $0 | May 29, 2023 |
| May 11, 2023 | 38274826L | ACTIVE | CLASS - 1 | 97X10,2X10,1X10,AND 5L10 ENTIRE DEVICE INOPERATIVE MUST REPAIR.ALARM BELL INOPERATIVE ALARM BELL ON STOP SWITCH INOPE... | $1,250 | $0 | Aug 18, 2023 |
| May 11, 2023 | 39086084J | ACTIVE | CLASS - 2 | AS PER ONE HYDROTHERM BOILER 02 IN CELLAR; NO NAME PLATE-HEAT STRESS FROM FLAME ROLL-OUT ON FRONT COVER-PRESSURE RANG... | $625 | $0 | May 29, 2023 |
| May 11, 2023 | 39086085L | ACTIVE | CLASS - 2 | PRESSURE RANGE IN COMPOUND GAGE NOT AS PER BOILER CODE-INSULATED COVERING SHOWING SIGNS OF FLAME ROLL-OUT AND HEAT ST... | $625 | $0 | May 29, 2023 |
| Oct 18, 2021 | 39049737P | ACTIVE | CLASS - 2 | I OBSERVED IN THE BOILER ROOM B BOILER IS LEAKING PROFUSELY FROM REAR., REPAIR AND/OR REPLACE | $625 | $0 | Nov 12, 2021 |
| Oct 18, 2021 | 35635692R | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.NOTED:OBSERVED AT ROOF BULKHEAD IN THE "A" BUILDING EXIT DOOR DOES NOT SELF-CLOSE AND REMA... | $1,562 | $0 | Jan 21, 2022 |
| Oct 13, 2021 | 39049205Y | ACTIVE | CLASS - 2 | FOUND BOILER B, ON THIS BANK OF BOILERS LEAKING BETWEEN SECTION, REPAIR OR REPLACE, ALSO SAFETY RELIEF VALVE ON SAME ... | $625 | $0 | Oct 15, 2021 |
| Oct 13, 2021 | 39049206X | ACTIVE | CLASS - 2 | FOUND ONE WEIL MCLAIN LGB-9 NOT REGISTERED ON DOB RECORDS,, MAINTAIN BOILER; RE-FILE PERMIT AND CALL FOR INSPECTION. | $625 | $0 | Oct 15, 2021 |
| Jan 6, 2021 | 39034399J | ACTIVE | CLASS - 2 | SAFETY LEAKING ON BOILER ON LEFT SIDE SECOND FROM THE BACK OF BOILER. | $625 | $0 | Jan 22, 2021 |
| Nov 26, 2019 | 38272431H | RESOLVE | CLASS - 2 | 13-B-10, 2-B-10, 72-M-7 )2,B,10) ALARM BELL INSUFFICIENT BATTERY BURNING OUT, (13,B,10) EMERGENCY LIGHT NOT WORKING.(... | $625 | $0 | Mar 20, 2020 |
| Oct 31, 2019 | 39012086L | ACTIVE | CLASS - 2 | NOTED: OBSERVED THROUGHOUT BUILDINGS A AND B AT VARIOUS FLOORS, FIREPROOF SELF-CLOSING CORRIDOR DOORS ARE RACKED AND ... | $625 | $0 | Nov 12, 2019 |
| May 10, 2019 | 39002821J | ACTIVE | CLASS - 2 | CORROSION ON PIPING, ELECTRICAL BOX COVER FALLING OFF, PRESSURE RELIEF VALVES LEAKING, HOT WATER SUPPLY HEADER LEAKIN... | $0 | $0 | May 15, 2019 |
| May 10, 2019 | 39002822L | ACTIVE | CLASS - 2 | AS PER TWO HYDROTHERM BOILERS AT ABOVE LOCATION AND AS PER DOB RECORDS. FAILURE TO FILE A COMPLETE BOILER SAFETY, INI... | $0 | $0 | May 15, 2019 |
| Oct 22, 2018 | 32097862X | RESOLVE | CLASS - 2 | 6A:BOILER IN FRONT OF BOILER OF 02 SAFETY LEAKING NEW TO BC CHECKED (BOILER ON LEFTSIDE IN THE BACK) | $0 | $0 | Feb 15, 2019 |
| Sep 11, 2018 | 35347524L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC1008.1.8; 27-371(... | $0 | $0 | Nov 30, 2018 |
| Sep 6, 2018 | 38265121R | RESOLVE | CLASS - 1 | CU1L10; CU2L10; CU97X10. 1L10-EMERGENCY STOP SWITCH DID NOT RING; 2L10-EMERGENCY ALARM BELL DID NOT RING; NO PHONE IN... | $0 | $0 | Nov 16, 2018 |
| Jun 13, 2018 | 32096822R | RESOLVE | CLASS - 2 | 24B,50. (50)SPILL SWITCH MISSING. CORRECT ALL VIOLATING CONDITION & SUBMIT C OF C. | $0 | $0 | Aug 17, 2018 |
| May 9, 2018 | 35331827M | RESOLVE | CLASS - 1 | EC-110.2(A).OBSERVED IN KITCHEN ROOM.DEFECTIVE WIRING IN USE;TWO COMMERCIAL GRADE HEATING OVENS WIRED TO SAME SAFETY ... | $0 | $0 | Jul 6, 2018 |
| May 9, 2018 | 35331826K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON ROOF.APPROXIMATELY SEVEN EXHAUST FAN THAT PROVIDE V... | $0 | $0 | Jul 6, 2018 |
| Oct 6, 2017 | 35293783P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. RE-ISSUE #351128388Y ISSUED: 02/11/2016. NOTE: SPALLING, CRA... | $0 | $0 | Jan 5, 2018 |
| Oct 6, 2017 | 35293968L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 10/06/2017 AT ABOVE ADDRESS HOT WATER RETURN PIPIN... | $0 | $0 | Jan 5, 2018 |
| Oct 6, 2017 | 35293967J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 10/06/2017 AT ABOVE ADDRESS RP2 APPEARS TO BE LEAK... | $0 | $0 | Jan 5, 2018 |
| Jun 1, 2017 | 35267631R | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER-APPLIANCE. OBSERVED IN APT 3P ON 3RD FL GAS STOVE LEAKING. FDNY SHU... | $0 | $0 | Aug 18, 2017 |
| Jun 1, 2017 | 35267813H | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE POWER FOR EMERGENCY EXIT LIGHTING. NOTE: AT BLDG SECTION'B',5TH STY,EMERGENCY SECTION'C' AT 1ST ST... | $0 | $0 | Aug 18, 2017 |
| Feb 11, 2016 | 35128388X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.SPALLING,CRACKS AND WATER INTRUSION THROUGHOUT FACADE.ALSO AT ROOF ... | $0 | $0 | Apr 1, 2016 |
| Jun 28, 2001 | 34289049M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL NOTED: PARAPET WALL CRACKED AT VARIOUS LOCATIONS ON SEWECIT AVENCE SIDE AN... | $0 | $0 | Aug 17, 2001 |
| Jun 28, 2001 | 34289050J | RESOLVE | Non-Hazardous | EXPIRED PERMIT. SIDEWALK. NOTED: EXPIRED SHED PERMIT #200304809. REMEDY: RENEW PERMIT. | $0 | $0 | Aug 17, 2001 |
| Mar 31, 2000 | 34219889L | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. DEFECT IS CRACKED DEFECTIVE AND BULDING BRICK PARAPET WALL THROUGHOUT BUI... | $2,500 | $0 | May 12, 2000 |
| Mar 31, 2000 | 34219890Z | RESOLVE | Non-Hazardous | HAVING ERECTED A SIDEWALK SHED AT FRONT AND SIDE (FOILE ST) OF BUILDING WITHOUT A PERMIT. REMEDY: OBTAIN APPROVALS AN... | $2,500 | $0 | Jul 14, 2000 |
| May 13, 1999 | 34177659N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. DEFECT IS FRONT TO MAINTAIN EXTERIOR BUILDING WALL. DEFECT IS FRONT BRICK... | $0 | $0 | Jul 23, 1999 |
| Jul 15, 1998 | 34165872Y | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT IS EXTIRE FRONT BRICK WORK OF PARAPET WALLS ARE BROKEN & DEFECTIVE ... | $0 | $0 | Sep 25, 1998 |