| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 12, 2026 | 39200273P | ACTIVE | CLASS - 2 | CLASS 2 ITEMS: MULTIPLE FIRE EXTINGUISHERS FOUND STORED IN MACHINE ROOM, REMOVE. REPAIR DAMAGED MACHINE ROOM LIGHT FI... | $625 | $625 | Oct 16, 2026 |
| Jun 1, 2026 | 39190668N | ACTIVE | CLASS - 2 | FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39107502N, FILE A CERTIFICATE OF CORRECTION | $1,250 | $1,250 | Aug 21, 2026 |
| Jun 1, 2026 | 39190669P | ACTIVE | CLASS - 2 | FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39107503P, FILE A CERTIFICATE OF CORRECTION | $1,250 | $1,250 | Aug 21, 2026 |
| Nov 12, 2024 | 39129973R | RESOLVE | CLASS - 1 | RESPONDING, TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION OF THE SINGLE DEVICE, BUILDING, DEVICE IS FOUND TO BE OUT OF... | $1,250 | $1,250 | Jan 27, 2026 |
| May 2, 2024 | 39113293R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CAB LIGHTS UNGUARDED, PROVIDE GUARD. PIT DIRTY, CLEAN. BRAKE M... | $0 | $0 | Jul 19, 2024 |
| Mar 1, 2024 | 39107502N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER; NOTED IN CELLAR STORAGE ROOM, EXPOSED ELECTRICAL WIRE CONNECTI... | $1,250 | $1,250 | Sep 27, 2024 |
| Mar 1, 2024 | 39107503P | ACTIVE | CLASS - 1 | OCCUPANCY CONTRARY; NOTED BUILDING DEPARTMENT RECORDS INDICATE BUILDING AS 6 STORY 78 FAMILY WITH 1 IN CELLAR. AT INS... | $2,500 | $2,500 | Sep 27, 2024 |
| Mar 1, 2024 | 39107504R | RESOLVE | CLASS - 1 | WORK WITHOUT PERMIT; NOTED AT CELLAR LEVEL ERECTED VARIOUS FULL HEIGHT PARTITIONS AND DOORS FOR 3 BATHROOMS AND 3 ADD... | $0 | $0 | Feb 28, 2025 |
| Jan 26, 2024 | 39104404X | RESOLVE | CLASS - 1 | PHASE 2 FIREMEN SERVICE NOT OPERATING PROPERLY; REPAIR; EMERGENCY PHONE NOT WORKING REPAIR; PROVIDE KEYS TO MOTOR ROOM | $1,250 | $0 | Apr 5, 2024 |
| Nov 27, 2023 | 39100154Y | ACTIVE | CLASS - 1 | AT THE TIME OF INSPECTION I OBSERVED IN APARTMENT 2G NEW INSTALLATION OF OUTLETS IN THE BATHROOM KITCHEN HALLWAY BOTH... | $1,600 | $0 | Feb 2, 2024 |
| Nov 27, 2023 | 39100153M | ACTIVE | CLASS - 1 | AT THE TIME OF INSPECTION I OBSERVED IN APARTMENT 2G LOOSE NEUTRALS AND UNGROUNDED OUTLETS THROUGHOUT THE ENTIRE APAR... | $1,600 | $0 | Feb 2, 2024 |
| Dec 29, 2022 | 39076598H | RESOLVE | CLASS - 2 | CLEAN MOTOR ROOM; REMOVE UN-ELEVATOR RELATED MATERIAL FROM MOTOR ROOM; FIX ALARM BELL INSIDE ELEVATOR | $312 | $0 | Sep 12, 2023 |
| Dec 9, 2022 | 37024814X | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $1,250 | $0 | Aug 7, 2023 |
| Oct 9, 2021 | 39049081L | RESOLVE | CLASS - 2 | CLASS 2 VIOLATION ISSUED ITEMS,/ IN CAR FAN NOT WORKING,REPAIR,/ DIRTY CAR TOP, CLEAN,/ NO ACCESS TO CELLAR FLOOR, PR... | $625 | $0 | Jan 21, 2022 |
| Jun 21, 2021 | 35575684P | RESOLVE | CLASS - 2 | MISSING (SWS) PARAPET INFO PANEL NOTE:ATOI OBSERVED HDSWS INSTALLED@EXP1&4.PEDESTRIAN WALKING UNDER THIS SWS.ALSO OBS... | $625 | $0 | Apr 1, 2022 |
| Jun 21, 2021 | 35575683N | RESOLVE | CLASS - 2 | PEDESTRIAN PROTECTION DOESNT MEET CODE SPEC NOTE:ATOI OBSERVED HDSWS INSTALLED@EXP1&4.PEDESTRIAN WALKING UNDER THIS S... | $2,400 | $0 | Apr 1, 2022 |
| Oct 22, 2020 | 39030896M | RESOLVE | CLASS - 1 | DOOR RESTRICTOR DAMAGED/INOPERATIVE (CEASE USE). | $312 | $0 | Sep 10, 2021 |
| Aug 6, 2019 | 38271011R | RESOLVE | CLASS - 2 | 12-M-07, 16-B-01, 26-B-11, 59-B-01, 64-M-07, 05-E-10. 12-M # IN CAR LIGHT MISSING COVER, 16-B #ADJUST LOBBY HOISTWAY ... | $625 | $0 | Feb 14, 2020 |
| Mar 24, 2019 | 35365324X | RESOLVE | CLASS - 1 | FAILURE TO TAKE AND PROVIDE ADEQUATE SAFETY MEASURES (SIDEWALK SHED; NETTING ETC) WHERE REQUIRED TO PROTECT AND SECUR... | $10,000 | $0 | Nov 8, 2019 |
| Aug 20, 2018 | 35319563X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BLDG FACADE & APPURTENANCES. ROOF LEVEL OBSERVED LEANING PARAPET WALL ON WEST ELEVATION ... | $0 | $0 | Oct 5, 2018 |
| Jun 29, 2018 | 32097257H | RESOLVE | CLASS - 2 | 50A-E. AS PER CLASS 2(B254)28-301.1, FAILURE TO MAINTAIN. (50A)FRESH AIR FAN NOT WORKING. (50B)AIR FLOW PROVING SWITC... | $312 | $0 | Sep 28, 2018 |
| May 18, 2018 | 37010561J | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APP... | $1,250 | $0 | Sep 21, 2018 |
| May 18, 2018 | 38262852R | RESOLVE | CLASS - 1 | CU05Z10;70O02;37D06;02X10;16K10. 05-DOOR ZONE RESTRICTOR ALTERED/INOPERATIVE CAUSING A HAZARDOUS CONDITION. REPAIR AN... | $1,250 | $0 | Aug 3, 2018 |
| Feb 9, 2018 | 35265381Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS AND APPURTENANCES. NOTE: EXP 1 NORTH ELEVATION: STEP CRACKS IN BRICKS AND... | $1,000 | $0 | Apr 13, 2018 |
| Dec 19, 2017 | 35298024R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 12-19-17 AT ABOVE ADDRESS FLUE PIPE TO BOILER IN POOR ... | $0 | $0 | Apr 13, 2018 |
| Dec 19, 2017 | 32092095L | RESOLVE | CLASS - 1 | 3C,3A,50,15,51-50)NEED TO INSTALL LOCK ASSEMBLY ON BOILER DOOR. 3A,C)FLUE PIPE OUTSIDE OF BOILER ROOM CORRODED AND SE... | $1,000 | $0 | May 1, 2018 |
| Dec 19, 2017 | 35297355R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPINGPER BC 712.3;27-345 NOTE:HOLES IN CEILING AND W... | $0 | $0 | Feb 2, 2018 |
| Dec 19, 2017 | 35298023P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 12-19-17 AT ABOVE ADDRESS. NOTED: CAST IRON PIPE HAS 2... | $250 | $0 | Apr 13, 2018 |
| Dec 19, 2017 | 35297733P | RESOLVE | CLASS - 2 | FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS. OBSERVED 3 SERVICE SWITCHES IN BASEMENT AREA W/ GROUNDING CONDUCTORS, IN... | $750 | $0 | May 11, 2018 |
| May 17, 2017 | 35260637X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NOTED: AT CELLAR IN BOILER R... | $0 | $0 | Jul 7, 2017 |
| May 17, 2017 | 35267401L | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,DEVICES,MAERIALS,APPLIANCES OR WIRING IN USE.OBSERVED THR... | $1,600 | $0 | Jul 7, 2017 |
| May 17, 2017 | 35267400J | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS.OBSERVED IN BASEMENT AT WATER MAIN PIPE:THE MAIN GROUNDING CONDUCTOR FOR ELECTRI... | $4,800 | $0 | Jul 7, 2017 |
| May 17, 2017 | 35267230X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:SERVICE EQUIPMENT BOILER.OBSERVED IN BOILER ROOM LEAKING FROM T... | $1,000 | $0 | Jul 7, 2017 |
| May 17, 2017 | 35260449Z | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT.OBSERVED IN HALLWAYS:THE REMOVAL OF OLD LIGHT FIXTURES(FLOURESCENT)AND INSTALLATION ... | $800 | $0 | Jul 7, 2017 |
| Mar 27, 2017 | 38253834Z | RESOLVE | CLASS - 2 | 2X10R/C 70O2R/C 15M7,41W7,12Q3 59BB7, 68M7,68B7,16M7,16J1,26R11,40R9 RECURRING CONDITION.02X20 PHONE INOPERATIVE.RECU... | $1,250 | $0 | Jun 16, 2017 |
| Mar 27, 2017 | 38253835K | RESOLVE | CLASS - 1 | 02X10,70O2. CENTURY VERTICAL SYSTEMS,INC. LICENSE #L 51001 SUBMITTED A NOTARIZED STATEMENT TO BE USED ON THE DISMISSA... | $0 | $0 | Jun 16, 2017 |
| Mar 27, 2017 | 38253837Y | RESOLVE | CLASS - 2 | 02X10,70O2. RESPONDENT FAILED TO COMPLY W/THE COMMISSIONER'S ORDER TO CORRECT, THE VIOLATING CONDITIONS AND FILEA CER... | $0 | $0 | Jun 16, 2017 |
| Jan 10, 2017 | 38250645X | RESOLVE | CLASS - 1 | 5M7,52H11(CU); 16L10(CU); 16X10(CU); 32H11,40O2,56Y10,70O2,67X10. 52M7-HOIST ROPES WAY UNDERSIZED MUST REPLACE IMMEDI... | $2,500 | $0 | Mar 3, 2017 |
| Dec 15, 2016 | 35222663M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: FAILURE TO COMPLY W/ THE LAW FOR DRAINAGE SYSTEM PER PC 702.1; 27-... | $500 | $0 | Mar 31, 2017 |
| Dec 15, 2016 | 35222630X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTE: APPROX 2 1/2"WIDE STEP CRACK ABOVE 6TH FL WINDOW TO PARAPET AT... | $500 | $0 | Feb 3, 2017 |
| Dec 6, 2016 | 38251263P | RESOLVE | CLASS - 2 | 2X10,32H10,52B14,70O2. 2-OUTSIDE COMMUNICATION CAR PHONE INOPERATIVE REPAIR; 32-GUIDESHOES WORN REPAIR; 52-HOIST ROPE... | $500 | $0 | Jan 20, 2017 |
| Nov 2, 2016 | 35172514X | RESOLVE | CLASS - 2 | FAILURE TO POST PERMITS FOR WORK AT PREMISES,OBSERVED NO PERMITS POSTED IN FRONT OF BLDG IN LOBBY OR ON APT #5B DOOR ... | $0 | $0 | Dec 30, 2016 |
| Nov 2, 2016 | 35172515H | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. OBSERVED IN LOBBY AREA APPROX 200 PI... | $400 | $0 | Feb 24, 2017 |
| Nov 2, 2016 | 35172513Y | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE APPROVED/ACCEPTED PLANS AT JOB SITE AT TIME OF INSPECTION. PLANS FOR JOB#240148782-01-EW-OT ISSUE ... | $250 | $0 | Feb 24, 2017 |
| Nov 2, 2016 | 35172516J | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OEPRATIONS. OBSERVED IN LOBBY AREA APPROX 200PC ... | $0 | $0 | Dec 30, 2016 |
| Aug 11, 2016 | 37001152Y | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 7TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APP... | $800 | $0 | Mar 31, 2017 |
| Jul 6, 2016 | 38244127P | RESOLVE | CLASS - 2 | 02X10,40P16,70O02.02X10 REPAIR PHONE,PROVIDE SERVICE;40P16 PROVIDE ROOM ACCESS;70O02 CLEAN PIT. | $250 | $0 | Oct 14, 2016 |
| May 19, 2016 | 35174273N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALLS AND APPURTENANCES. NOTED AT TIME OFINSPECTION (I) AT EXP1 (I)DETERORATED TRIANGULA... | $500 | $0 | Jul 15, 2016 |
| Nov 28, 2015 | 35160954L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED @ 1ST FL APT 1B W/ BATHROOM FL COLLAPSE APPROX 90% ONTO CELLA... | $1,000 | $0 | Jan 29, 2016 |
| Sep 21, 2015 | 36023211X | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE TECHNICAL REPORT IN COMPLIANCE WITH CODEPROVISIONS: PERIODIC INSPECTION OF EXTERIOR WAL... | $2,000 | $0 | Mar 4, 2016 |