ECB violations
East 173 Street, Bronx • Block 02791 • Lot 0009
46 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 4, 2025 | 39169304X | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION. AT TIME OF INSPECTION, VIOLATING... | $1,250 | $1,250 | Jun 12, 2026 |
| Dec 4, 2025 | 39169305H | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION. AT TIME OF INSPECTION, VIOLATING... | $1,250 | $1,250 | Jun 12, 2026 |
| Dec 4, 2025 | 39169303Y | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION. AT TIME OF INSPECTION, VIOLATING... | $1,250 | $1,250 | Jun 12, 2026 |
| Oct 20, 2025 | 39164109H | ACTIVE | CLASS - 2 | OBSERVED ON THE FIRST FLOOR SPRINKLER HEAD SPRAY OBSTRUCTED BY LIGHT FIXTURE AND NOT USING THE PROPER MATERIAL ON SPR... | $1,280 | $1,280 | Aug 3, 2026 |
| Dec 2, 2024 | 39131688K | ACTIVE | CLASS - 2 | PAINTED SPRINKLER HEADS ON THE SECOND AND FIRST FLOORS. AS PER 102.3 OF THE PLUMBING CODE INSTALLATIONS, BOTH EXISTIN... | $625 | $0 | Apr 18, 2025 |
| Dec 2, 2024 | 39131698Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Apr 18, 2025 |
| Dec 2, 2024 | 39131697M | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED DOORS CLOSING BUT NOT LATCHING. IN CASE OF EMERGENCY ... | $1,250 | $1,250 | Apr 18, 2025 |
| Jul 5, 2024 | 39118443X | RESOLVE | CLASS - 2 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB# 39098193R ISSUED ON 10/27/2023 AND FILE ... | $3,125 | $3,125 | Sep 20, 2024 |
| Dec 29, 2023 | 39102450H | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB# 39093599Y ISSUED ON 08/28/2023. PURSUAN... | $2,500 | $2,500 | Apr 26, 2024 |
| Dec 29, 2023 | 39102448Z | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB# 39084227Z ISSUED ON 04/19/2023 PURSUANT... | $2,500 | $0 | Mar 15, 2024 |
| Dec 29, 2023 | 39102447R | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB# 39084226R ISSUED ON 04/19/2023PURSUANT ... | $2,500 | $0 | Mar 15, 2024 |
| Oct 27, 2023 | 39098193R | RESOLVE | CLASS - 1 | I OBSERVED THE SIDEWALK SHED LOCATED AT EXPOSURES #3 AND 4 WITHOUT ILLUMINATION AS REQUIRED UPON THE COMPLETION OF TH... | $2,500 | $2,500 | Feb 2, 2024 |
| Oct 27, 2023 | 39098195K | RESOLVE | CLASS - 2 | I OBSERVED THE CONDITIONS SITED IN ECB# 39084226R ISSUED ON 04/19/2023 STILL IN EFFECT WITH NO CORRECTIONS MADE. PHOT... | $3,125 | $1,875 | Aug 25, 2026 |
| Oct 27, 2023 | 39098192P | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT AREA PAST THE ELECTRICAL EQUIPMENT IN THE ROOM USED FOR STORAGE THE EXPOSED AND ENERGIZED ... | $8,000 | $4,000 | Aug 25, 2026 |
| Oct 27, 2023 | 39098194Z | RESOLVE | CLASS - 1 | I OBSERVED THE CONNECTION OF FLEXIBLE CORD TO THE JUNCTION BOX SUPPLYING POWER TO THE SIDEWALK SHED ALONG EXPOSURE #3... | $1,600 | $1,600 | Feb 2, 2024 |
| Aug 30, 2023 | 39131063K | ACTIVE | CLASS - 1 | FAILURE TO COMPLY WITH COMMISSION'S ORDER DATED 08/30/23/UNDER COMPLAINT NUMBER 2375239 TO REPAIRS DAMAGED WALLS A RE... | $1,250 | $1,250 | Mar 28, 2025 |
| Aug 28, 2023 | 39093598M | RESOLVE | CLASS - 2 | EMERGENCY EXIT OUTSIDE STAIRWAY WALLS ARE CRACKED WITH SPALLING CEMENT STUCCO, LEADING TO EXIT OUTSIDE SIDEWALK., MAI... | $1,250 | $0 | Dec 1, 2023 |
| Aug 28, 2023 | 39093600M | RESOLVE | CLASS - 2 | FAILURE TO DISTRIBUTE OR POST SAFE CONSTRUCTION BILL OF RIGHTS, POST OR DISTRIBUTE SAFE CONSTRUCTION BILL OF RIGHTS | $1,250 | $0 | Dec 1, 2023 |
| Aug 28, 2023 | 39093597K | RESOLVE | CLASS - 2 | G-CONTRACTOR (GC-623495)ASSOCIATED WITH JOB APPLICATION, (JOB NO.X00466337) -INADEQUATE TPP & TPP NOT BEING COMPLIED ... | $0 | $0 | Dec 24, 2024 |
| Aug 28, 2023 | 39093596Z | RESOLVE | CLASS - 2 | FAILURE TO DISTRIBUTE AND POST NOTICE OF TENANT PROTECTION PLAN, POST/DISTR. NOTICE | $1,250 | $0 | Dec 1, 2023 |
| Aug 28, 2023 | 39093595R | RESOLVE | CLASS - 2 | METAL STAIRS ARE RUSTED AND DETERIORATED WITH CRACKS LEADING TO THE CELLAR LEVEL/BASEMENT., REPAIR AND/OR REPLACE | $625 | $0 | Dec 1, 2023 |
| Aug 28, 2023 | 39093599Y | RESOLVE | CLASS - 1 | ROOF IN DIS-REPAIR AND SHOWING SIGNS OF MAJOR DETERIORATION, INCLUDING CRACKED STONES ALONG THE ROOF PARAPET, (IN DAN... | $1,250 | $0 | Dec 1, 2023 |
| Apr 19, 2023 | 39084227Z | RESOLVE | CLASS - 1 | I OBSERVED IN DOB RECORDS THE SUBMITTAL OF A CERTIFICATE OF CORRECTION FOR ECB #35433921X STATING THAT THE VIOLA6TING... | $12,500 | -$12,500 | Sep 10, 2024 |
| Apr 19, 2023 | 39084226R | RESOLVE | CLASS - 1 | I OBSERVED IN THE REAR AREA OF THE BASEMENT EXPOSED AND ENERGIZED WIRES INSTALLED IN AN OPEN WOOD FRAME WALL, THE WIR... | $8,000 | -$8,000 | Sep 10, 2024 |
| Oct 25, 2021 | 35635695M | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS.NOTED:OBSERVED AT 1ST FL 1 UN... | $1,250 | $0 | Feb 18, 2022 |
| Jan 14, 2020 | 35459241H | RESOLVE | CLASS - 2 | FAILURE TO GROUND ELECTRICAL SYSTEM. I OBSERVED IN THE(MAIN)ELECTRICALROOM IN THE BASEMENT,THE GROUNDING ELECTRODE CO... | $2,400 | $0 | Jan 29, 2021 |
| Jan 14, 2020 | 39015709M | ACTIVE | CLASS - 2 | NOTED: OBSERVED ON THE 1ST. FLOOR, UNITS 1 BEING USE AS A LOUNGE,CAFETERIA AND LAUNDRY ROOM AND UNIT 2 BEING USE FOR ... | $3,125 | $0 | Jan 29, 2021 |
| Jul 9, 2019 | 35433921X | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED I... | $800 | $0 | Sep 13, 2019 |
| Apr 10, 2019 | 39002038H | RESOLVE | CLASS - 2 | BLR LKING-PEERLESS LC-5-OIL LN BENT-SEAL BASE- | $312 | $0 | May 31, 2019 |
| Jan 17, 2019 | 35379801R | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPARTMENT RECORDS. NOTED: OBSERVED ON... | $3,125 | $0 | Mar 15, 2019 |
| Jan 17, 2019 | 35372660K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR VI... | $1,250 | $0 | Mar 15, 2019 |
| Aug 8, 2018 | 32097656P | RESOLVE | CLASS - 2 | B254;11A;50A;50B:AS PER CLASS 2 (B254) 28-301.1 FAILURE TO MAINTAIN.50A:BOILER ROOM DOOR NOT SELF CLOSING.50B:TEMPERA... | $625 | $0 | Oct 5, 2018 |
| Jun 8, 2018 | 37010136Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35293670Z ISSUED ON 9/21/2017,AND TO FILE ... | $1,250 | $0 | Aug 31, 2018 |
| Jun 8, 2018 | 37010135R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35293669L ISSUED ON 9/21/2017,AND TO FILE ... | $625 | $0 | Aug 31, 2018 |
| Mar 16, 2018 | 35313050N | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT.FAILURE TO COMPLY W/THE COMM'S ORDER.FAILURE TO CORRECT & CERTIFY SUMMONS #35293829L ISSUED FOR WORKI... | $1,250 | $0 | Aug 10, 2018 |
| Sep 21, 2017 | 35293670Z | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR DOB RECORDS. C OF O# 44783 INDICATES 1ST STORY TO HAVE 2 APTS W/ ... | $3,000 | $0 | Nov 17, 2017 |
| Sep 21, 2017 | 35293669L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTED: @ EXP#3 PARAPET WALL & CHIMNEY @ PARAPET WALL LEANING OUTWA... | $500 | $0 | Nov 17, 2017 |
| Sep 21, 2017 | 35293830Z | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE /MAINTIAN SUFFICIENT ACCESSW/WORK SPACE ABOVE ELEC TRICAL EQUIPMENT. AS NOTED IN PREVIOUS ECB ISSU... | $500 | $0 | Mar 9, 2018 |
| Sep 21, 2017 | 35290921K | RESOLVE | CLASS - 2 | SEC: FGC 411.1. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED ON 9/21/17 @ ABOVE ADDRESS RESIDENTIAL GA... | $800 | $0 | Nov 17, 2017 |
| Sep 21, 2017 | 35293829L | RESOLVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED THE INSTALLATION OF GFCI TYPE OUTLETS IN LAUNDRY ROOM AND BATHROOMS ON FLO... | $800 | $0 | Mar 9, 2018 |
| Sep 21, 2017 | 35290922M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 9/21/17@ ABOVE ADDRESS SPRINKLER BRANCH (PIPE) IN OFFI... | $250 | $0 | Nov 17, 2017 |
| May 16, 2017 | 35260945H | RESOLVE | CLASS - 1 | FGC411.1/MISCELLANEOUS VIOLATIONS:RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT.OBSERVED IN LAUNDRY ROOM ON 1ST F... | $1,600 | $0 | Jul 7, 2017 |
| May 16, 2017 | 35260895Z | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS,APPARATUS,DEVICE,APPLIANCE OR WIRING IN USE.OBSERVED NO G... | $800 | $0 | Jul 7, 2017 |
| Jan 5, 2017 | 35225700X | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O OR BLDG DEPT RECORDS. NOTED: C OF O #44783 INDICATES 1ST FL AS 2 RESIDEN... | $1,200 | $0 | Mar 3, 2017 |
| Dec 9, 2016 | 35222199H | RESOLVE | CLASS - 1 | SEC. 408.2 MISC VIOLATION DRIPS-FUTURE CONNECTS EXIST DOWN STREAM OF APPLIANCE. OBSERVED ON 12-9-16 FUTURE GAS CONNEC... | $800 | $0 | Feb 17, 2017 |
| Dec 9, 2016 | 35222198X | RESOLVE | CLASS - 1 | SEC. 411.1 MISC VIOLATIONS RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED ON 12-9-16 RESIDENTIAL GAS FLE... | $1,600 | $0 | Feb 17, 2017 |