ECB violations
115 Henwood Place, Bronx • Block 02826 • Lot 0034
56 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 19, 2026 | 39181004X | ACTIVE | CLASS - 3 | FOUND BOILER WAS REMOVED, FAILURE TO FILE LAA FOR CAP AND REMOVAL OF BOILER. FILE LAA AND CALL FOR AN INSPECTION. | $500 | $0 | Nov 13, 2026 |
| Mar 19, 2026 | 39181062Y | ACTIVE | CLASS - 2 | CLASS 2: ELEVATOR MACHINE ROOM DOOR SIGN MISSING, PROVIDE. FIRE EXTINGUISHER SERVICE TAG EXPIRED, REPLACE. PIT LIGHT ... | $625 | $0 | Nov 13, 2026 |
| Mar 19, 2026 | 39181061M | ACTIVE | CLASS - 1 | OBSERVED THROUGHOUT BUILDING SPRINKLER HEADS OBSTRUCTED, CAPS MISSING FROM SPRINKLER HEADS AND PIPE PENETRATIONS WITH... | $2,500 | $0 | Nov 13, 2026 |
| Nov 26, 2024 | 39131464L | ACTIVE | CLASS - 2 | OBSERVED OBSTRUCTED SPRINKLE HEAD IN THE REFUSE ROOM LOCATED ON THE 7TH FLOOR. AS PER 102.3 OF THE PLUMBING CODE INST... | $625 | $0 | Jul 15, 2025 |
| Nov 26, 2024 | 39131463J | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS STATED IN ECB# 39092802X ISSUED ON 08/17/2023. PURSUANT T... | $2,500 | $0 | Jul 15, 2025 |
| Nov 26, 2024 | 39131462H | ACTIVE | CLASS - 2 | OBSERVED PAINTED SPRINKLER HEADS THROUGHOUT REFUSE ROOMS. AS PER 102.3 OF THE PLUMBING CODE INSTALLATIONS, BOTH EXIST... | $625 | $0 | Jul 15, 2025 |
| Nov 26, 2024 | 39131479Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Jul 15, 2025 |
| Nov 26, 2024 | 39131480L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED AC HVAC SYSTEM MOUNTED ON BEAM WITH PLYWOOD NOT SECUR... | $1,250 | $0 | Mar 28, 2025 |
| Jan 3, 2024 | 39102637H | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS STATED IN ECB# 39081576N ISSUED ON 03/16/2023. PURSUANT T... | $2,500 | $0 | Apr 19, 2024 |
| Aug 25, 2023 | 39093396Y | RESOLVE | CLASS - 2 | FOUND MOTORIZED FREAH AIR NOT WORKING WHEN BOILER GOES ON . | $0 | $0 | Nov 3, 2023 |
| Aug 17, 2023 | 39092793N | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP ELEVATOR MOTOR ROOM THE CORRECTION OF ECB #39081576N ISSUED ON 03/16/2023 CORRECTED WITHOUT... | $800 | $0 | Jan 26, 2024 |
| Aug 17, 2023 | 39092782H | RESOLVE | CLASS - 2 | HOLE PENETRATION/BOX HOLES CUT OUT OF THE SHEETROCK OF THE "INSPECTION TEST VALVE CLOSET", LOCATED ON 14TH FLOOR NEAR... | $625 | $0 | Jan 26, 2024 |
| Aug 17, 2023 | 38274864M | RESOLVE | CLASS - 2 | 59BB5 (59-BB-5) BROKE MAINTENANCE TAG EXPIRED MUST PERFORM MAINTENANCE & FILE ON TAG BY CONTROLLER AND ON NCP. | $625 | $0 | Nov 3, 2023 |
| Aug 17, 2023 | 39092802X | ACTIVE | CLASS - 2 | OBSERVED IN THE REFUSE ROOM LOCATED ON THE 7TH FLOOR SPRINKLER HEAD IS BEING OBSTRUCTED BY THE DATA BOX. AS PER 102.3... | $625 | $0 | Jan 26, 2024 |
| Mar 16, 2023 | 39081576N | RESOLVE | CLASS - 1 | I OBSERVED IN THE REAR OF THE ROOFTOP ELEVATOR MOTOR ROOM A 30 AMP FUSED DISCONNECT SWITCH WITH THE NEUTRAL CONDUCTOR... | $1,600 | $0 | Nov 14, 2023 |
| Mar 14, 2023 | 39081375R | RESOLVE | CLASS - 1 | DOOR RESTRICTOR REMOVED; REPAIR; EMERGENCY PHONE NOT WORKING, REPAIR; MOTOR ROOM DOOR HANDLE DAMAGED; REPAIR DOOR HAN... | $1,250 | $0 | Jun 16, 2023 |
| May 2, 2022 | 39061409H | RESOLVE | CLASS - 2 | I OBSERVED ON ALL FLOORS CONVENIENCE RECEPTACLES NOT OF THE TAMPER RESISTANT TYPE NOR WITH PROPER TAMPER RESISTANT CO... | $800 | $0 | Jul 15, 2022 |
| May 2, 2022 | 39061410P | RESOLVE | CLASS - 2 | I OBSERVED IN THE 7TH FLOOR (A) STAIRWELL THE IMPROPER INSTALLATION OF A LIGHT FIXTURE MOUNTED TO THE FRAME OF AN EXI... | $500 | $0 | Jul 15, 2022 |
| May 2, 2022 | 39061408X | RESOLVE | CLASS - 1 | I OBSERVED IN THE ELECTRICAL EQUIPMENT SERVICE ROOM EXCESSIVE STORAGE OF FLAMMABLE LIQUIDS, MATERIALS, TOOLS AT NO TI... | $3,000 | $0 | Jun 17, 2022 |
| May 2, 2022 | 39061421K | RESOLVE | CLASS - 2 | AT 8TH FLOOR, STAIRCASE A, AT 7TH FLOOR STAIR A&B, AT 6TH FLOOR STAIR A&B, CORRIDORS, UTILITY ROOMS. THERE ARE NO EME... | $3,125 | $0 | Jun 17, 2022 |
| May 2, 2022 | 39061422M | RESOLVE | CLASS - 2 | AT CELLAR LEVEL, STAIR A& B CORRIDOR, EXCESSIVE STORAGE OF INFLATABLE MATERIAL OBSTRUCTING THE EMERGENCY EXIT, PROVID... | $625 | $0 | Jul 15, 2022 |
| Apr 1, 2021 | 37021231K | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $3,125 | $0 | Nov 12, 2021 |
| Oct 29, 2019 | 38272088J | RESOLVE | CLASS - 2 | 59-BB-7,67-X-10,80-B-14=(59,BB,7) BRAKE MAINTEANCE TAG EXPIRED (67,X,10) IN CAR PHOEN THAT WORKING (80,B,14) COUNTER ... | $625 | $0 | Feb 14, 2020 |
| Jul 26, 2019 | 39006514H | RESOLVE | CLASS - 2 | DRAFT REGULATOR INSTALLED IN FLUE PIPING IN ADDITION TO BUILT IN DRAFT PROTECTION ON BOILER. | $625 | $0 | Feb 14, 2020 |
| Apr 24, 2019 | 35414811L | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES,OR WIRING IN USE.OBSERVED IN... | $800 | $0 | Nov 27, 2019 |
| Apr 24, 2019 | 35414812N | RESOLVE | CLASS - 2 | FAILURE TO SECURE/SUPPORT RACEWAYS/CABLE ASSEMBLIES/BOXES/CABINETS/FITTINGS.OBSERVED IN ROOFTOP ELEVATOR MOTOR ROOM T... | $400 | $0 | Nov 27, 2019 |
| Apr 24, 2019 | 35414809M | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/O A PERMIT.OBSERVED IN BASEMENT OUTSIDE OF ENTRANCE TO BOILER ROOM & IN ROOFTOP ELEVATOR MOTOR ROOM... | $800 | $0 | Nov 22, 2019 |
| Apr 24, 2019 | 35414810J | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTOR(GFCI)PROTECTION.OBSERVED IN RM 14D(OFFICE)NO GFCI PROTECTION(RECE... | $1,200 | $0 | Nov 27, 2019 |
| Oct 23, 2018 | 35361110M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER BC 7123;BC 27-345.NOTED:AT 1ST DTORY IN EL... | $1,250 | $0 | Jun 14, 2019 |
| Oct 23, 2018 | 35361109P | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT BULKHEAD AT ROOF EXIT DOOR WIRE GLASS PANE IS CRACKED ... | $500 | $0 | Jun 14, 2019 |
| Oct 23, 2018 | 35361399M | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES.NOTED:AT EXPOSURE #1 TO THE RIGHT OF BUILDING ENTRANCE FENCE LO... | $500 | $0 | Jun 14, 2019 |
| Aug 8, 2018 | 32097367Z | RESOLVE | CLASS - 2 | B254;32A;50A;50B;50C;50D:LAARS PW 1200 N BOILER:50A-FRESH AIR VENTILATION (OF) INTER-LOCKED W/BOILER-50B-BOILER ROOM ... | $1,562 | $0 | Oct 5, 2018 |
| May 18, 2018 | 37010568M | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APP... | $1,250 | $0 | Jan 28, 2019 |
| Apr 17, 2018 | 32096876M | RESOLVE | CLASS - 2 | AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAINTAIN 50A-SPILL SWITCH NOT INSTALLED; 50B- FIRE DAMPERS NOT INSTALLED IN... | $1,562 | $0 | Jun 29, 2018 |
| Mar 17, 2018 | 35322571N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY COMMISSIONER'S ORDER CONTAINED SUMMONS/VIOLATION# 35253302Z ISSUED ON 4/21/2017 & TO FILE A C OF C ... | $1,250 | $0 | Jun 1, 2018 |
| Feb 14, 2018 | 35312670J | RESOLVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT... | $0 | $0 | Jun 27, 2018 |
| Oct 17, 2017 | 35294535K | RESOLVE | CLASS - 1 | 110.2 SERVICE IN EXCESS OF 1000 KVA HAS NOT BEEN SUBMITTED FOR APPROVAL. OBSERVED IN ELECTRICAL VAULT ROOM. THE INSTA... | $0 | $0 | Jun 27, 2018 |
| Sep 22, 2017 | 35277400Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIO # 35253302Z ISSUED ON 04/21/17 & TO FILE A C... | $800 | $0 | Jun 27, 2018 |
| Aug 2, 2017 | 38256530N | RESOLVE | CLASS - 1 | CU05A10,05B01,02B10,16H11,17H11. CEASE USE (05) DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH/DISABLED AND RENDERED INO... | $1,000 | $0 | Jan 12, 2018 |
| Apr 21, 2017 | 35253302Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 4-21-17AT ABOVE ADDRESS GAS LEAK FOUND IN GAS METER RO... | $1,000 | $0 | Jun 27, 2018 |
| Apr 21, 2017 | 35253303K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 4-21-17 AT ABOVE ADDRESS NO SPEINKLER IN COMPACTOR. RE... | $500 | $0 | Jun 27, 2018 |
| Apr 21, 2017 | 35252979X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: 4TH FL WALL OPEN TO STAIRCASE,3RD FL,2ND FL,AT CELLAR LEVEL... | $500 | $0 | Jun 27, 2018 |
| Apr 21, 2017 | 35253301R | RESOLVE | CLASS - 1 | SEC. 408.2 DRIPS FUTURE CONNECTIONS EXITS DOWNSTREAM OF APPLIANCE. OBSERVED ON 4-21-17 AT ABOVE ADDRESS FUTURE GAS CO... | $800 | $0 | Jun 27, 2018 |
| Apr 21, 2017 | 35253300P | RESOLVE | CLASS - 1 | SEC. 401.1 GAS PIPING NOT LABELED OBSERVED ON 4-21-17 AT ABOVE ADDRESSGAS PIPE THROUGHOUT BASEMENT NOT LABELED. REMED... | $800 | $0 | Jun 27, 2018 |
| Apr 21, 2017 | 35253304M | RESOLVE | CLASS - 1 | FGC403.9.3/PIPE DOPE DOPE ONLY.OBSERVED ON 4/21/17 AT ABOVE ADDRESS PERMATEX USED ON GAS PIPES IN GAS METER ROOM.PIPE... | $1,600 | $0 | Jun 8, 2018 |
| Dec 13, 2016 | 35221973N | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE COMLPIANT MANNER. NOTE:(1)MISSING LIGHTING FIXTURE AT 6TH FL STAIRWELL(2)HOLES IN CE... | $200 | $0 | Mar 3, 2017 |
| Dec 13, 2016 | 35222653Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: LACK OF SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC903.2;... | $500 | $0 | Mar 3, 2017 |
| Dec 13, 2016 | 35222651P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. @ TIME OF INSP ON 12/13/16 @ ABOVE PLACE OF OCCURENCE ADDRESS OBSE... | $0 | $0 | Mar 3, 2017 |
| Dec 13, 2016 | 35222652R | RESOLVE | CLASS - 2 | FAILURE TO PAINT DEDICTED SPRINKLER PIPING/VALVES IN ACCORDANCE W/ SECTION. @ TIME OF INSP ON 12/13/16 @ ABOVE PLACE ... | $1,600 | $0 | Mar 3, 2017 |
| Apr 14, 2016 | 35095198R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BUILDING. NORTH ELEVATION, EXPOSURE #3 OBSERVE CRACKS IN PARAPET AND MASONRY FACADE UPPE... | $1,250 | -$1,371 | Jun 3, 2016 |