Issued Violation Status Severity Description Penalty Balance due Hearing
Jul 14, 2026 39196031N ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSP... $1,250 $1,250 Sep 18, 2026
Mar 18, 2026 39180968X RESOLVE CLASS - 1 OBSERVED AT THE 6TH-STORY HALLWAY IN THE EAST SECTION OF THE BUILDING, A WASHING UNIT AND TABLE ARE BEING STORED, CRE... $2,500 $2,500 Jan 21, 2027
Mar 18, 2026 39180969H RESOLVE CLASS - 2 OBSERVED KEY-OPERATED LOCKS ARE INSTALLED ON DOORS PROVIDING ROOF ACCESS AND RE-ENTRY AT BOTH THE EAST AND WEST SECTI... $0 $0 May 29, 2026
Aug 21, 2025 39157996H ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSP... $1,250 $1,250 Oct 31, 2025
Jun 6, 2025 39150241H ACTIVE CLASS - 2 PROVIDE CERTIFICATE OF COMPLIANCE. $1,250 $1,250 Dec 5, 2025
Jun 6, 2025 39150242J ACTIVE CLASS - 1 RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-9... $1,250 $1,250 Dec 5, 2025
Jan 31, 2025 39137093Z RESOLVE CLASS - 1 OBSERVED AT EXPOSURE#2 PARAPET LEVEL , STEP CRACKS AND MORTAR MISSING IN BETWEEN BRICKS., REPAIR AND/REPLACE; REPAIR ... $0 $0 Dec 8, 2025
Dec 12, 2024 39132730J RESOLVE CLASS - 1 : FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON IN... $0 $0 Mar 17, 2026
Nov 25, 2024 39131287J RESOLVE CLASS - 1 RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION. THE DEVICE IS FOUND TO BE OUT-OF-SERVICE, AS PER 1RCNY 11-02... $0 $0 Jul 25, 2025
Jan 4, 2024 39102734J RESOLVE CLASS - 1 UPON INSPECTION OBSERVED AT EXP.3/REAR COURTYARD HAS A LARGE WOODEN BOX BEING STORED DIRECTLY UNDERNEATH A FIRE ESCAP... $312 $0 Aug 2, 2024
Dec 4, 2023 39100660R RESOLVE CLASS - 1 UPON MY INSPECTION FIND THE HAS NOT BEEN RESTORED TO SERVICE. CLASS 1 CONTINUED $1,563 $0 Feb 16, 2024
Jun 21, 2023 39088877Z RESOLVE CLASS - 1 RESTORE TO SERVICE; ELEVATOR OUT OF SERVICE $312 $0 Sep 1, 2023
May 24, 2023 39087010L RESOLVE CLASS - 1 RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION , THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATING A HAZARDO... $625 $0 Aug 4, 2023
Mar 29, 2023 39082608N RESOLVE CLASS - 1 ELEVATOR CURRENTLY OUT OF SERVICE IN THE LOBBY WITH DOORS CLOSED $0 $0 Jun 2, 2023
Jan 23, 2023 39078240M RESOLVE CLASS - 1 RESPONDING ON A 311 ELEVATOR COMPLAINT, UPON INSPECTION OF DEVICE, VIOLATION , WAS FOUND, ITEMS; DOOR ZONE RESTRICTOR... $0 $0 Aug 25, 2023
Oct 26, 2021 39050053M RESOLVE CLASS - 2 CLASS 2 VIOLATION ISSUED,/ CAR DOOR GIBBS MISSING, PROVIDE,/ NO ACCESS TO BASEMENT FLOOR,PROVIDE ACCESS,/ NO ACCESS I... $312 $0 Mar 4, 2022
Apr 28, 2021 39040307Y RESOLVE CLASS - 2 NO RE-SHACKLE TAG ON CAR TOP, PROVIDE. MACHINE HAS OIL LEAK, CLEAN AND SEAL. $312 $0 Jul 30, 2021
Jan 7, 2021 39034468Y RESOLVE CLASS - 2 PHONE INOPERATIVE, REPAIR. NO ACCESS TO PIT OR MACHINE ROOM. REMEDY; KEYS MUST BE ON SITE TO GAIN ACCESS IN THE EVENT... $0 $0 Apr 16, 2021
Mar 13, 2020 39019667L RESOLVE CLASS - 2 BOILER FLOODED-NAME PLATE/MISSING, NOT AFFIXED TO BOILER-BODY DRAINS NOT INSTALLED ONTO SAFETY VALVES; CORRECT ALL VI... $0 $0 Apr 23, 2021
Mar 11, 2020 39019484Z RESOLVE CLASS - 1 CEASE USE, 1/ ITEM, ALTERED CAR DOOR RESTRICTOR REMEDY; REPAIR AND CONTACT NYCDOB FOR RESTORE TO SERVICE RE INSPECTIO... $1,250 $0 Sep 18, 2020
Dec 4, 2019 35512930N RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#39011324N ISSUED ON 10/17/19 & TO FILE A C OF C PURSUAN... $0 $0 Feb 5, 2020
Dec 4, 2019 35512931P RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#39011325P ISSUED ON 10-17-19 & TO FILE A C OF C PURSUAN... $0 $0 Feb 5, 2020
Nov 13, 2019 38272288Y RESOLVE CLASS - 2 20M7,37D6,37R6,37B2,40M7,39B10,67X10,11M7,70M7:(20,M,7)VISION PANEL GLASS MISSING ON THE 2ND FL. (37,D,6)OVERHEAD DOO... $312 $0 Jan 3, 2020
Nov 13, 2019 38272289X RESOLVE CLASS - 2 11M7,20L10,37R7,40M7,67X10,70M7:(11,M,7)NO ACCESS TO THE BASEMENT FROMTHE CAR STATION. (20,L,10)LOBBY VISION GLASS BR... $312 $0 Jan 3, 2020
Oct 17, 2019 39011320X RESOLVE CLASS - 2 NOTED: OBSERVED AT EXPOSURE 1 (EAST ELEVATION) OF 1455 WALTON AVENUE, DIAGONAL CRACKS AT THE CORNER OF ENTRANCE NEAR ... $0 $0 Dec 6, 2019
Oct 17, 2019 39011325P RESOLVE CLASS - 1 NOTED: FULL HEIGHT PARTITIONS ERECTED AT NORTHEAST CORNER OF CELLAR TO CREATE LIVING QUARTERS FOR THE PORTER, WITH NO... $0 $0 Dec 6, 2019
Oct 17, 2019 39011329M RESOLVE CLASS - 1 I OBSERVED IN THE CELLARS ELECTRICAL ROOM A 200 AMP SERVICE SWITCH THAT IS MISSING THE MAIN BONDING JUMPER BETWEEN TH... $0 $0 Aug 13, 2021
Oct 17, 2019 39011324N RESOLVE CLASS - 1 NOTED: FULL HEIGHT PARTITIONS ERECTED AT NORTHEAST CORNER OF CELLAR TO CREATE LIVING QUARTERS FOR THE PORTER, WITH NO... $0 $0 Dec 6, 2019
Oct 17, 2019 35434241R ACTIVE CLASS - 1 FUTURE CONNECTION EXIST DOWN STREAM FROM APPLIANCE.OBSERVED ON 10/17/19 AT THE ABOVE ADDRESS FUTURE GAS CONNECTION EX... $2,500 $0 Feb 14, 2020
Jan 16, 2019 38265068R RESOLVE CLASS - 1 16F1; 37I10, 37O2, 37D6,2X10,40M7. 16F1-ADJUST HOISTWAY DOORS SPPED DOORS CLOSING TOO HARD ALL FLOORS; 37I10-BROKEN O... $1,250 $0 Jun 14, 2019
Oct 18, 2018 38265945J RESOLVE CLASS - 2 10H11,32J01,40P16,67X10. DOOR GIBS ARE WORN REPLACE; 32J01-SHOES ALL ON CAR ARE MISALIGNED AND LOOSE ADJUST; 40P16-NO... $0 $0 Dec 7, 2018
Sep 26, 2018 38265756K RESOLVE CLASS - 1 37R7,37T7,40M7,67X10,97X10. 37R7-OVERHEAD ACCESS DOOR PINNED CLOSE; 37T7-OVERHEAD DOOR NOT LABELED; 40M7-NO ACCESS TO... $1,250 $0 Nov 16, 2018
Sep 26, 2018 38265755Z RESOLVE CLASS - 1 3.I.10,(C/U)5.A.7,11.B.7,32.B.10,(C/U)37.D.6,(C/U)37.R.9,40.M.7,67.X.10,70.M.7-(3,I,10)CAR STATION EMERGENCY LIGHT DA... $1,250 $0 Nov 16, 2018
May 22, 2018 32096899P RESOLVE CLASS - 2 B254,50A,50B,50C,50D. AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAINTAIN 50A-COLD WATER PIPING TO BOILER COIL NOT SUP... $310 $0 Jul 20, 2018
May 15, 2018 35331958M RESOLVE CLASS - 2 FAILURE TO PROVIDE ADEQUATE GROUNDING OF ELECTRICAL SYSTEMS. OBSERVED IN 600 AMP SERVICE SWITCH W/ 450 FUSE PROTECTIO... $1,200 $0 Aug 10, 2018
May 15, 2018 35331956Z RESOLVE CLASS - 2 FAILURE TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS/ENCLOSURES/CABLE ARMOR. OBSERVED IN BASEMENT EL... $600 $0 Aug 10, 2018
May 15, 2018 35331962P RESOLVE CLASS - 2 SEC: EC 300.15A. FAILURE TO PROVIDE TO ACCESS TO CONDUIT BODY COVER. OBSERVED IN BASEMENT ELEVATOR, MACHINE ROOM THE ... $400 $0 Aug 10, 2018
May 15, 2018 35331960L RESOLVE CLASS - 2 FAILURE TO PROTECT CONDUCTORS AGAINST OVERCURRENT PER EC. OBSERVED IN BASEMENT SERVICE DISCONNECT FOR PUBLIC METER TH... $1,200 $0 Aug 10, 2018
May 15, 2018 35334314K RESOLVE CLASS - 2 FAILURE TO SECURE/SUPPORT RACEWAYS/CABLE ASSEMBLIES/BOXES/CABINETS/FITTINGS. OBSERVE IN BASEMENT AREA AND ALONG EXTER... $400 $0 Aug 3, 2018
May 15, 2018 35329149J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: OBSERVED AT INNER ENTRANCE COURTYARD,LEFT(SOUTH)SIDE(1453 SID... $620 $0 Jun 29, 2018
May 15, 2018 35331961N RESOLVE CLASS - 2 FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERUPPTER (GFCI)PROTECTION. OBSERVED IN BASEMENT THE USE OF AN ELECTRIC WAS... $1,200 $0 Aug 10, 2018
May 15, 2018 35331963R RESOLVE CLASS - 2 FAILURE TO PROPERLY CONNECT CONDUCTORS TO TERMINALS. OBSERVED IN ELEVATOR MOTOR ROOMS IN BASEMENT OF BLDG 1453 & 1455... $600 $0 Aug 10, 2018
May 15, 2018 35331957K RESOLVE CLASS - 2 PROHIBITED USE OF ELECTRICAL METALLIC TUBING (EMT). OBSERVED ON EXTERIOR OF 1455 WALTON AVENUE THE USE OF EMT SUPPLYI... $250 $0 Jun 29, 2018
Apr 18, 2018 38262711N RESOLVE CLASS - 1 CU5X10; 42N11,70O2,75I11,71X10,30M11,47Y13,29M11. 5X10-DOOR ZONE RE STRICTOR INOPERTIVE, REPAIR; 42N11-FUSES BYPASSED... $1,250 $0 Jun 1, 2018
Jan 18, 2018 38260292Z RESOLVE CLASS - 1 CEASE USE 5X10, 65N10, 68B7, 52Y2, 44413, 39O2,70O2 5X10-DOOR RESTRICTOR IS INOPERATIVE,REPAIR .THIS DEVICE INSURES T... $1,000 $0 Jun 22, 2018
Aug 3, 2017 35284707Z RESOLVE CLASS - 1 AN UNLAWFUL ACT. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERFIFY ECB #35253328R I... $2,400 $0 Sep 29, 2017
Jun 21, 2017 38255788X RESOLVE CLASS - 1 97X17 THE ONLY ELEVATOR IN BLDG(OR SECTION OF BLDG) OUT OF SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF ... $1,000 $0 Aug 18, 2017
Apr 25, 2017 35253330X RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS APPARATUS,DEVICES,APPLIANCES OR WIRING IN USE. AT THE TIM... $1,600 $0 Aug 11, 2017
Apr 25, 2017 35253329Z RESOLVE CLASS - 1 SEC. 503.5 INSTALLATION NOT CONFORM W/REQUIREMENTS FOR CLASSIFIED LOCATION. ATHE TIME OF MY INSPECTION I OBSERVED THE... $1,600 $0 Aug 11, 2017
Apr 25, 2017 35253328R RESOLVE CLASS - 1 ELECTRICAL WORK W/O A PERMIT. AT THE TIME OF MY INSPECTION I OBSERVED NEW CONDUIT & A SERVICE SWITCH FEEDING TO A GAS... $1,600 $0 Aug 11, 2017