ECB violations
1460 Cromwell Avenue, Bronx • Block 02857 • Lot 0028
39 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 31, 2025 | 39172064N | ACTIVE | CLASS - 2 | MISSING IN CASE OF FIRE SIGN IN LOBBY. MISALINGED CAB MIRROR. ADJUST 1ST FLOOR INTERLOCK. INOPERATIVE CAR PHONE. SELF... | $655 | $655 | Jul 10, 2026 |
| Apr 11, 2024 | 37027545K | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8B AND 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTE... | $10,000 | $10,000 | Jul 5, 2024 |
| Apr 9, 2024 | 35681626X | ACTIVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER. NOTE: RESPONDENT FAILURE TO COMPLY PRIOR SUMMON #35675510... | $12,500 | $12,500 | Jun 21, 2024 |
| Feb 15, 2024 | 39106061M | RESOLVE | CLASS - 2 | ADJUST HOISTWAY DOOR CLOSING FORCE IN LOBBY; LOBBY SWING HOISTWAY DOOR NOT CLOSING SHUT; REPAIR EMERGENCY PHONE; PROV... | $0 | $0 | Feb 25, 2025 |
| Jan 11, 2024 | 35675510N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. AS NOTED, EXPOSURE 1 STEP CRACKING, OPEN MORTAR JOINT... | $0 | $0 | Feb 4, 2025 |
| Sep 28, 2023 | 39095962Z | RESOLVE | CLASS - 2 | EMERGENCY PHONE IN CAR NOT WORKING; ALSO MISSING CITY DEVICE # IN CAR | $625 | $625 | Apr 16, 2024 |
| Oct 19, 2022 | 37022870L | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE8B REPORT OF CRITICAL EXAM DOCUMENTING CONDITION OF EXTERIOR WALL&APPURTEN... | $3,125 | $3,125 | Mar 10, 2023 |
| Mar 18, 2022 | 39058340L | ACTIVE | CLASS - 2 | FOUND EXPOSED WIRING, WATER LEAKING FROM BENEATH BOILER, BODY DRAIN MISSING ON SAFETY RELIEF VALVE AND DISCHARGE PIPE... | $3,125 | $3,125 | May 6, 2022 |
| Feb 16, 2022 | 35568569Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #39043886L ISSUED 7/02/21 AND FILE CERTIFI... | $12,500 | $12,500 | May 20, 2022 |
| Jan 19, 2022 | 39054571K | ACTIVE | CLASS - 1 | CEASE USE ITEMS, 1/ DLM. DOOR LOCK MONITORING NOT WORKING, REMEDY REPAIR AND CONTACT NYCDOB FOR RESTORE TO SERVICE RE... | $6,250 | $6,250 | May 6, 2022 |
| Dec 16, 2021 | 35566348L | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#39043886L ISSUED ON 7/2/2021 AND TO FI... | $12,500 | $12,500 | Mar 18, 2022 |
| Nov 10, 2021 | 39051004K | ACTIVE | CLASS - 1 | CEASE USE ITEMS, / CAR DOOR RESTRICTOR TAMPERED WITH AND NOT WORKING / IN CAR ALARM BELL AND IN CAR STOP SWITCH BELL ... | $6,250 | $6,250 | Mar 18, 2022 |
| Nov 4, 2021 | 35566079M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#39043886L ISSUED ON 07/02/21 AND TO FI... | $12,500 | $12,500 | Feb 4, 2022 |
| Sep 22, 2021 | 35563032L | ACTIVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #89043886L ISSUED ON 07/02/21 & TO FILE A... | $25,000 | $25,000 | Dec 17, 2021 |
| Aug 9, 2021 | 35535831J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS.VIOLATION #39043885J ISSUED ON 07-02-21 AN DTO FI... | $0 | $0 | Mar 11, 2025 |
| Jul 16, 2021 | 35577891R | ACTIVE | CLASS - 2 | FAILURE TO MAINAIN EXTERIOR BUILDING FACADE AND APPURTENANCES.AS NOTED:BUILDING HAS CRACKED BRICKS THROUGHOUT BUIDLIN... | $1,250 | $1,250 | Dec 17, 2024 |
| Jul 2, 2021 | 39043885J | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT 5TH FLR APT 5D - AT KITCHEN AREA; EXIT PASSAGEWAY TO FIR... | $6,250 | $6,250 | Aug 20, 2021 |
| Jul 2, 2021 | 39043886L | ACTIVE | CLASS - 1 | W/O A PERMIT. NOTED: AT 5TH FLR APT 5D - (1) A PARTITION WALL & SWING DOOR ERECTED AT LIVING RM TO SUB-DIVIDE RM & CR... | $12,500 | $12,500 | Aug 20, 2021 |
| Jun 1, 2021 | 37021671Y | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $10,000 | $10,000 | Oct 15, 2021 |
| Jan 29, 2021 | 39035674J | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; INSTALL... | $1,250 | $1,250 | Apr 16, 2021 |
| Nov 9, 2020 | 39031709M | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; INSTALL... | $3,125 | $3,125 | Aug 27, 2021 |
| Jul 30, 2020 | 39026122R | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. INSTALL... | $6,250 | $6,250 | Sep 18, 2020 |
| Apr 24, 2019 | 38269427H | ACTIVE | CLASS - 1 | (CLASS 1)42.X.10,02.X.10,02.X.10,13.X.10,12.X.10,25.M.07,16.K.10,64.M.15,70.O.02;(CLASS 1+42-X-10)DOOR POSTION MONITO... | $1,250 | $1,250 | Jul 26, 2019 |
| Feb 11, 2019 | 38267869X | RESOLVE | CLASS - 2 | 02L10,25M07,67X10,15M07. 02L10-ALARM DEFECTIVE REPAIR; 25M07-IN CASE OF FIRE USE STAIRS SIGNGE MISSING PROVIDE; 67X10... | $0 | $0 | Dec 17, 2024 |
| Oct 15, 2018 | 37013354K | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT A REQUIRED CYCLE 8B REPROT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPUR... | $6,250 | $6,250 | Mar 29, 2019 |
| Sep 17, 2018 | 38265319M | ACTIVE | CLASS - 1 | (97,X,17)*RTS)RETURN ELEVATOR DEVICE TO SERVICE AND FILE FOR REINSPECTION | $1,250 | $1,250 | Nov 16, 2018 |
| May 22, 2012 | 34955205R | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. NOTED: AT 3RD FL APT 3H,NORTH SECTION OF BLDG,CLASS'A' APT,A FULL HIGH,& LENGH WISE PORTITION W/A ... | $0 | $0 | Aug 17, 2012 |
| Apr 22, 2011 | 34873562X | RESOLVE | CLASS - 1 | NO RECORD OF DAILY INSPECTION OF SUSPENDED SCAFFOLD PERFORMED BY AUTHORIZED PERSON AT SITE. + STOP WORK ISSUED + - 4 ... | $2,400 | $0 | Jun 17, 2011 |
| Apr 22, 2011 | 34873561Y | RESOLVE | CLASS - 1 | SEC. 3314.10.09. TIEBACKS SHALL BE INSTALLED. SINGLE TIEBACKS INSTALLED AT AN ANGLE ARE PROHIBITED + STOP WORK ORDER ... | $1,600 | $0 | Jun 17, 2011 |
| Nov 13, 2006 | 34418276K | RESOLVE | Hazardous | FAILURE TO PROVIDE ELEVATOR LANDING SIGN THAT SHALL READ "IN CASE OF FIRE USE STAIRS UNLESS OTHERWISE INSTRUCTED" @ T... | $0 | $0 | Jan 5, 2007 |
| Jul 11, 2006 | 38159595J | RESOLVE | Non-Hazardous | 12Q3/31H11/8V1/34Q3/26T15/39P7/66O2. 12 CAR LIGHT. 34 INSTALL COVERS WHERE NEEDED. | $0 | $0 | Aug 25, 2006 |
| Jul 17, 2003 | 34397019J | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT IS: THROUGHOUT VARIOUS LOCATIONS OF THE NORTH SOUTH EAST AND WEST F... | $800 | $0 | Jan 2, 2004 |
| Sep 25, 2001 | 38118598Y | RESOLVE | Non-Hazardous | 25Q3-30O2-50Y14-35P17-15B4-57O2-73O2-31M7-61O2-1B11-2B11-10A11 30=CLEAN CAR TOP OIL SOAK AND SHAFTWAY 15=PATCH HOLE R... | $2,500 | $0 | Nov 16, 2001 |
| Sep 11, 2000 | 34261191Z | RESOLVE | Non-Hazardous | FAILURE TO FILE A REPORT OF COMPLIANCE WITH LOCAL-LAW 16/84,CERTIFYING TO THE INSTALLATION OF REQUIRED FIRE PROTECTIO... | $200 | $0 | Dec 8, 2000 |
| Sep 11, 2000 | 34261200L | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE ELEVATOR LANDING SIGNS "IN CASE OF FIRE USE STAIRS UNLESS OTHERWISE INSTRUCTED" ON ALL FLOORS.FAIL... | $400 | $0 | Jan 19, 2001 |
| Sep 17, 1997 | 38064113X | RESOLVE | Hazardous | 17Q11,17B12,10I12,22S12,01X11,11I12,28H11,30O02,37D11,31Q12,50A11,75R05,08I12,50Y14,11X11,36T07,34R11,03M07,35O02,15R... | $500 | $0 | May 8, 1998 |
| Mar 16, 1993 | 38030906K | RESOLVE | Non-Hazardous | 02L,11Q,13M,03#,53M,57O, 03.INSTALL HAND RAIL WHERE REMOVED IN CAR | $250 | $0 | Oct 21, 1993 |
| Jul 10, 1992 | 38027678K | RESOLVE | Non-Hazardous | 02L,10R,17I,50Q,57O,57Z,73#, 50. END COVER MISSING 73. PERFORM 5 YEAR TEST AND FILE ELEV. 3 FORM, PROPERLY TAG DEVICE | $1,000 | $0 | Sep 11, 1992 |
| Mar 19, 1991 | 38004371Y | RESOLVE | Non-Hazardous | 57O02, 02L11, 18M07, 74O02. 74-CLEAN TOP OF CAR. | $0 | $0 | May 3, 1991 |