ECB violations

Academy For Language And Tech, Bronx • Block 02866 • Lot 0070

108 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
May 13, 2014 35094786Z RESOLVE CLASS - 2 OIL TANK ROOM - REAR RUSTING BEAMS & REBAR. REMEDY: MAINTAIN BUILDING AS PER CODE. $0 $0 Aug 1, 2014
May 13, 2014 35094780H RESOLVE CLASS - 2 RE-ISSUE # 35019545H. DOORS RACKED STAIR J & D 3RD FL. GYM EXIT 8 - DOOR CHECK NOT OPERATIONAL. CAFETERIA - STWY J/I ... $0 $0 Aug 1, 2014
May 13, 2014 35094781J RESOLVE CLASS - 2 RE-ISSUE # 35019543Y. OPENING IN WALLS & CEILING AT GYM & ELEC ROOM - FIRE STOP MISSING. REMEDY: MAINTAIN BUILDING AS... $0 $0 Aug 1, 2014
May 13, 2014 35094783N RESOLVE CLASS - 2 RE-ISSUE # 35019541K. KICK DOWN DOOR STOP INSTALLED THROUGHOUT 5TH,4TH FLOORS, STAIRS C & D 2ND FLOOR, ROOMS 111, 214... $0 $0 Aug 1, 2014
May 9, 2014 35094785R RESOLVE CLASS - 2 SPALLING IN THE FOLLOWING ROOMS/AREAS WALLS &/OR CEILINGS, ROOMS 501,502,512,514,551, 5TH FLOOR STWY 5/E,5/J, ROOMS 4... $0 $0 Aug 1, 2014
May 7, 2013 35019544X RESOLVE CLASS - 2 EXIT FROM CAFETERIA IS OBSTRUCTED BY GARBAGE CANS, MILK CRATES & (FANS) REMEDY: REMOVE ALL OBSTRUCTIONS. $0 $0 Jul 19, 2013
May 7, 2013 35019542M RESOLVE CLASS - 2 3RD & 4TH FLR CORRIDORS, OBSTRUCTED BY CARTS, TABLES, CHAIRS, CABINETS, BOXES AND OTHER COMBUSTIBLE ITEMS. ALSO BANNE... $0 $0 Jul 19, 2013
May 7, 2013 35019543Y RESOLVE CLASS - 2 OPENINGS IN WALLS & CEILING OF ELECT ROOM W/NO FIRE STOPPING. REMEDY: PROVIDE FIRE STOPPING. $0 $0 Jul 19, 2013
May 7, 2013 35019541K RESOLVE CLASS - 2 KICK DOWN DOOR STOPS INSTALLED ON DOORS AT STAIR C,D,E & F AT 4TH FLR,STAIRS C&D AT 2ND FLR, RMS 111,(112),205,209,25... $0 $0 Jul 19, 2013
May 7, 2013 35019545H RESOLVE CLASS - 2 DOOR RACKED AT STAIR J&D 3RD FLR STAIR E&I 2ND FLR AND STAIR B AT 1ST FLR. REMEDY: REPAIR/REPLACE DOORS. $0 $0 Jul 19, 2013
Jun 28, 2012 34981300Y RESOLVE CLASS - 2 HANDRAIL DISPLACED/MISSING AT MAIN ENTRY EXTERIOR MARBLE STAIR CENTER HANDRAIL. REMEDY: REPLACE HANDRAIL. $0 $0 Sep 21, 2012
Jun 28, 2012 34981301X RESOLVE CLASS - 2 WATER DAMAGED PLASTER WALLS AT 5TH STORY CORRIDOR ADJOINING EXIT 9 & 10 & EXIT 5/6 & GYMNASIUM OFFICE. REMEDY: REPAIR... $0 $0 Sep 21, 2012
Jun 28, 2012 34981302H RESOLVE CLASS - 2 DOORS NOT CLOSING AT 1ST STORY STAIR'E' VESTIBULE DOORS JAMBS SPLIT/WOOD DETERIORATED. REMEDY: REPAIR &/OR REPLACE DO... $0 $0 Sep 21, 2012
Feb 8, 2011 34901689Z RESOLVE CLASS - 2 CRACKED BRICK MASONRY. AT ROOF TANK ROOM & ADJACENT STORAGE ROOM. CRACKED AND SEPARATING BRICK CORNER COLUMNS FLR TO ... $0 $0 Mar 18, 2011
Feb 8, 2011 34901691H RESOLVE CLASS - 3 PLASTER SURFACES DEFECTIVE. AT 2" FLR STWY 'H' BROKEN AND SPALLING WALL & CEILING PLASTER. 1ST FLR STWY 'E' EXIT DOOR... $0 $0 Mar 18, 2011
Feb 8, 2011 34901690X RESOLVE CLASS - 2 DEFECTIVE EXTERIOR GRATES. AT LEFT FRONT, THE METAL GRATE SUPPORTS AREERODING W/BROKEN MASONRY (COVERED W/SNOW AT TIM... $0 $0 Mar 18, 2011
Feb 8, 2011 34901692J RESOLVE CLASS - 2 HAND RAILING DEFECTIVE. AT MAIN ENTRANCE, THE LEFT & RIGHT CENTER HANDRAILS ARE LOOSE W/6" TO 10" DEFLECTION OFFERING... $0 $0 Mar 18, 2011
Feb 8, 2011 34901688R RESOLVE CLASS - 2 DEFECTIVE DOORS. RACKED DOORS NOT CLOSING PROPERLY AT *5TH FLR STWY 'I','C' *3RD FLR STWY 'J' - *1ST FLR STWY 'G','D'... $0 $0 Mar 18, 2011
May 20, 2010 34847223M RESOLVE CLASS - 2 FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. PROVIDE REQUIRED CORRIDOR NORTH. NOTED: DESKS CHAIRS, BOOKSHELVES, & ... $0 $0 Sep 17, 2010
May 20, 2010 34847222K RESOLVE CLASS - 2 OCCUPANCY CONTRARY TO DOB RECORDS. NOTED: BULKHEAD STAIRWAY/LANDING STAIR C FLOOR TO ROOF NOW OCCUPIED AS CLASSROOM/S... $0 $0 Sep 17, 2010
Jan 23, 2009 34760777M RESOLVE CLASS - 2 REISSUE: 34620180P INTERIOR DOOR CLOSERS ARE MISSING LOCATED ON FLRS 1ST THROUGH THE 5TH FLR. REMEDY: REPLACE MISSING... $0 $0 May 15, 2009
Jan 23, 2009 34760775Z RESOLVE CLASS - 2 REISSUE: 34620181R FIRE SMOKE CORRIDOR DOORS ARE MISSING LOCATED ON THE 1ST FLR NEXT TO THE BOY BATHROOM. REMEDY: REP... $0 $0 May 15, 2009
Jan 23, 2009 34760776K RESOLVE CLASS - 2 REISSUE: 34593424L STAIR LANDING IS CRACKED & LIFTING LOCATED BY ROOM 460 ON THE 4TH FLR LEVEL. REMEDY: REPAIR STAIR ... $0 $0 May 15, 2009
Jan 23, 2009 34760778Y RESOLVE CLASS - 2 BRICK COLUMN IS VERTICAL CRACKED IN THE 2ND FLR GYMNASIUM APPROX 8'FEET LONG & 1/4 INCH WIDE. REMEDY: REPAIR/REPLACE ... $0 $0 May 15, 2009
Jan 23, 2009 34760779X RESOLVE CLASS - 2 CONCRETE FLR AT THE MAIN ENTRANCE IS SINKING INTO THE GROUND APPROX 5 INCHES & ABOUT 32 SQ FEET. REMEDY: REPAIR CONCR... $0 $0 May 15, 2009
Jan 30, 2008 34593424L RESOLVE Non-Hazardous REISSUE VIO 34576867X. STAIR LANDING HAS CRACK IN PAINT & LIFTING (MINIOR) THROUGHOUT 1 FLR TO 5 FLR LANDING NEXT TO ... $0 $0 Apr 18, 2008
Jan 30, 2008 34620181R RESOLVE Hazardous FAILURE TO MAINTAIN FIRE DOOR SMOKE STOP DOOR MISSING TWO LOCATION 1STNEXT TO BOY'S BATHROOM REMEDY: REPLACE MISSING ... $0 $0 Apr 18, 2008
Jan 30, 2008 34620180P RESOLVE Hazardous REISSSUE VI 34576866Y DOOR CLOSER'S ARE MISSING OR BROKEN THROUGH OUT ALL FLOOR APOX. 85 % MISSING REMEDY: REPLACE OR... $0 $0 Apr 18, 2008
Jun 1, 2007 34576867X RESOLVE Hazardous REISSUE:34526223P CRACKS THE STAIR LANDINGS & TREADS ON THE 4TH FLS.REMEDY:REPAIRS CRACKS. $0 $0 Aug 17, 2007
Jun 1, 2007 34576866Y RESOLVE Hazardous REISSUE:34393503N DOORS ARE MISSING CLOSERS LOCATED ON EVERY FLS AT 1-5.REMEDY:REPLACE MISSING DOOR CLOSERS. $0 $0 Aug 17, 2007
May 12, 2006 34393575M RESOLVE Non-Hazardous CORRIDOR SMOKE DOORS MISSING @ 5, 4, 3 FLOORS. MISSING DOOR AT 2ND FLOOR ADJACENT TO 21B. REMEDY: INSTALL DOORS. $0 $0 Aug 18, 2006
May 12, 2006 34526223P RESOLVE Hazardous CRACKS THROUGHOUT LANDING'S AT STAIR TREADS ADJ TO 460 REMEDY:REPAIR CRACKS $0 $0 Aug 18, 2006
May 12, 2006 34393503N RESOLVE Hazardous FAILURE TO MAINTAIN NOTED. MISSING DOOR CLOSERS. DOOR RACKED FROM 1ST TO 5TH FLOORS AT VARIOUS LOCATIONS. REMEDY: REP... $0 $0 Aug 18, 2006
May 12, 2006 34393504P RESOLVE Hazardous PIPES LEAKING @ CELLAR BOILER RM. REMEDY; REPAIR LEAKS. $0 $0 Aug 18, 2006
May 12, 2006 34393506Z RESOLVE Hazardous DEFECTIVE LIGHT FIXTURE @ STAIR 5 BETWEEN 3 FL & 4 FL. ALSO @ BOILER, EXIT LIGHT IS NOT OPERABLE. REMEDY: REPAIR OR R... $0 $0 Aug 18, 2006
May 12, 2006 34393508M RESOLVE Hazardous EXIT LIGHTING DEFECTIVE @ T4 (NON ILLUMINATED). REMEDY: REPAIR OR REPLACE EXIT LIGHTING. $0 $0 Aug 18, 2006
May 12, 2006 34393507K RESOLVE Hazardous MISSING PROTECTIVE RAILING @ PLATFORM LANDING FOR T3. REMEDY: INSTALL RAILING. $0 $0 Aug 18, 2006
Jan 20, 2005 34466287M RESOLVE Non-Hazardous WATER LEAK FROM CEILING AT 3 FLR BOYS BATHROOM REMEDY:REPAIR LEAK $0 $0 Mar 18, 2005
Jan 20, 2005 34466288Y RESOLVE Non-Hazardous PLASTER COATING ON CEILINGS IS MISSING CRACKED & SPALLING IN RM #456 3 FLR BOYS BATHROOM &2 FLR TEACHERS BATHROOM REM... $0 $0 Mar 18, 2005
Feb 3, 2004 34423448Y RESOLVE Non-Hazardous USE OF ILLEGAL HARDWARE CAFETERIA EXIT KEY LOOSE DOOR KNOB OPEN POSIITON REMEDY:REMOVE ILLEGAL HARDWARE $0 $0 Mar 26, 2004
Feb 3, 2004 34423449X RESOLVE Non-Hazardous EXIT DOOR SWINGS AGANIST FLOW OF EGRESS CAFETERIA FIRE EXIT REMEDY:REPAIR 1 OR REPLACE DOOR $0 $0 Mar 26, 2004
Nov 14, 2003 34420909Y RESOLVE Non-Hazardous FAILURE TO MAINTAIN EXTERIOR DEFECT IS NEEDS POINTING THROUGHOUT MASONRY WALLS REMEDY MAKE ALL NECESSARY REPAIR $0 $0 Jan 23, 2004
Nov 14, 2003 34420910L RESOLVE Non-Hazardous FAILURE TO MAINTAIN EXTERIOR DEFECT EXTERIOR STAIRS ARE CRACKED AND DEFECTIVE LOCATION EXIT #8 REMEDY MAKE ALL NECESS... $0 $0 Jan 23, 2004
Jan 13, 2003 34387796P RESOLVE Non-Hazardous WORK W/O A PERMIT : EXPIRED PERMIT PERMIT # 200549718 SIDE WALK SHED EXIRED 12-31-02 PERMIT # 200549727 EXP 12-2 FOR ... $0 $0 Apr 4, 2003
Jan 13, 2003 34387795N RESOLVE Hazardous FAILURE TO MAINTAIN : DEFECTS : CONCRETE CEILING SPALLING CRACKED & COLLAPSING - REBAR EXPOSED LOCATION N.E. SIDE OF ... $0 $0 Apr 4, 2003
Jan 13, 2003 34387797R RESOLVE Non-Hazardous FAILURE TO MAINTAIN : DEFECT : STEEL RIPER & TREAD STEP UNDER STAIRS HAS PITTED - ROTTED CAUSING A TRIP HAZARD LOCATI... $0 $0 Apr 4, 2003
Jun 22, 2001 34297368J RESOLVE Non-Hazardous FAILURE TO MAINTAIN BLDG DEFECTS ARE HOLES IN CLASSROOM WALL IN T5 $0 $0 Sep 21, 2001
Jun 22, 2001 34297367H RESOLVE Non-Hazardous FAILURE TO MAINTAIN BLDG DEFECTS ARE EXT DOOR CHECKS ON T2 & T3 ARE DAMAGE OR MISSING REMEDY REPAIR /REPLACE DOOR CHE... $0 $0 Sep 21, 2001
Jun 22, 2001 34297366X RESOLVE Non-Hazardous FAILURE TO BLDG EXTERIOR DEFECTS ARE FLOOD LIGHTS AT ENTRY TO T1 & T4 ARE DAMAGE ELECTRICAL WIRES EXPOSED REMEDY REPL... $0 $0 Sep 21, 2001
Mar 2, 2001 34281760H RESOLVE Non-Hazardous EXIT DOOR:NOT SELF CLOSING ROTTEN DOORS AND FRAMES AT EXIT#2,#7,#8 &9, #10 AT STAIRWELL, DOORS AND FRAMES ARE SHATTER... $0 $0 Jul 20, 2001