ECB violations
1910 University Avenue, Bronx • Block 02868 • Lot 0098
35 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Nov 17, 2023 | 35675334N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. NOTE: AT EXP#1, CRACKED BRICKS, BUILDING BULGING AND LEANING... | $1,250 | $1,474 | Feb 2, 2024 |
| Oct 3, 2023 | 39096319Y | RESOLVE | CLASS - 2 | OBSERVED OUTSIDE IN THE COURT YARD GAS LINES NOT BEING PROTECTED ALSO IN APARTMENT 1W HAVING AN OPEN END GAS LINE WHI... | $0 | $0 | Dec 15, 2023 |
| Oct 3, 2023 | 39096439Z | RESOLVE | CLASS - 2 | OBSERVED OUTSIDE IN THE COURTYARD GAS LINES NOT BEING PROTECTED. ALSO IN APARTMENT 1W HAVING AN OPEN END GAS LINE WHI... | $0 | $0 | Jan 12, 2024 |
| Sep 20, 2023 | 39095391Y | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED EGRESS PATHWAY AT EXPOSURE #2 OBSTRUCTED BY TEMP WOOD STRUCTUR... | $1,250 | $1,416 | Jun 6, 2024 |
| Sep 20, 2023 | 39095384X | ACTIVE | CLASS - 1 | OCCUPANCY CONTRARY TO BUILDING DEPT RECORDS. BUILDING DEPT RECORDS IDENTIFY 30 CLASS 'A' APTS IN (5) STORY BLDG. OBSE... | $2,500 | $0 | Jun 6, 2024 |
| Sep 20, 2023 | 39095387L | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT. ALL WORK PLUMBING, ELECTRICAL AND GENERAL CONSTRUCTION TO CREATE BASEMENT APT #2W ( 1 BEDROOM ... | $0 | $0 | Aug 21, 2025 |
| Sep 19, 2023 | 35675228J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. AT THE TIME OF THE INSPECTION I OBSERVED AT EXP #1 THERE CRA... | $0 | $0 | Jan 5, 2024 |
| Sep 14, 2023 | 39094839Z | ACTIVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERT OF OCCUPANCY OR BUILDINGS DEPT RECORDS. LEGAL CLASS 'A' APARTMENT #1E ... | $2,500 | $0 | Jun 6, 2024 |
| Sep 14, 2023 | 39094846R | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED IN APT #1E SIGNIFICANT FLOOR DEFECTS SUCH AS BUCKLING... | $1,250 | $0 | Jun 6, 2024 |
| Sep 14, 2023 | 39094843L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER : USE OF PROHIBITED DOOR AND/ OR HARDWARE PER BC 1008.1.8; 27... | $1,250 | $0 | Jun 6, 2024 |
| Jun 23, 2023 | 35486444L | RESOLVE | CLASS - 2 | OCCUPANCY IN CONTRARY TO THAT ALLOWED BY C/O AND/OR DEPARTMENT OF BUILDING RECORD. ILLEGALLY CONVERTED CLASS "A" APAR... | $0 | $0 | May 10, 2024 |
| Oct 5, 2020 | 39029865L | RESOLVE | CLASS - 1 | BOILER CORRODED/LEAKING AT BACK-FRESH AIR LOUVERS BROKEN-BOLT MISSING FROM BURNER MOUNT-NO TEMP GAGE ON DOMESTIC HW L... | $1,250 | $0 | Nov 20, 2020 |
| Aug 15, 2017 | 35289685J | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING CONDUCTOR IN ACCORDANCE W/ CODE. OBSERVED IN BASEMENT: GROUNDING CONDUCTOR HANGING ABOVE... | $4,800 | $0 | Oct 20, 2017 |
| Jul 28, 2017 | 35284673J | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY ECB #35260542N I... | $0 | $0 | Sep 15, 2017 |
| Jun 22, 2017 | 35274912Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35260541L ISSUED ON 05/08/17 AND TO FI... | $0 | $0 | Sep 1, 2017 |
| May 8, 2017 | 35260886R | RESOLVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT.OBSERVED LIGHTSIN HALLS AND STAIRCASETHROUGHOUT BUILDINGS.NO APPLICATION ON FILE FOR... | $0 | $0 | Sep 1, 2017 |
| May 8, 2017 | 35260542N | RESOLVE | CLASS - 1 | NO ACCESS TO WATER GROUND CLAMP.MAIN WATER SUPPLY PIPE INSIDE OF OIL TANK ROOM WHICH IS ACCESSIBLE ONLY BY CLIMBING T... | $0 | $0 | Sep 1, 2017 |
| May 8, 2017 | 35260541L | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH CODE.OBSERVED GROUNDING CONDUCTOR HANGING ABOVE M... | $0 | $0 | Sep 1, 2017 |
| May 8, 2017 | 35260825N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 5-8-17 NO BOILER INSPECTION RECORDS ON FILE AT THE DOB... | $0 | $0 | Jun 30, 2017 |
| May 8, 2017 | 35260543P | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS,APPARTUS,DEVICE,APPLIANCE OR WIRING IN USE.NOTED:TEMPORAR... | $800 | $0 | Sep 1, 2017 |
| Jan 5, 2017 | 35190868M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35208058N ISSUED ON 11/17/16 & TO FILE A C OF C PURSUANT TO 28... | $400 | $0 | Mar 3, 2017 |
| Jan 5, 2017 | 35190867K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35208059P ISSUED ON 11/17/16 & TO FILE A C OF C PURSUANT TO 28... | $400 | $0 | Mar 3, 2017 |
| Nov 17, 2016 | 35208055H | RESOLVE | CLASS - 1 | SEC. 408.2 MISC VIOLATION. FUTURE CONNECTION EXIST ON HOUSE GAS LINE -TEE & CAPS @ GAS METER ROOM-BOILER LINE & COOKI... | $0 | $0 | Jan 6, 2017 |
| Nov 17, 2016 | 35208054X | RESOLVE | CLASS - 1 | FAILURE TO HAVE NOW OR ALTERED PLG SYSTEM TESTED OBSERVED ON 11/17/16 @ 9:30AM IN CELLAR-NEW GAS PIPING 4"INSTALLED F... | $1,000 | $0 | Jan 6, 2017 |
| Nov 17, 2016 | 35221531X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE: 1)WATER DAMAGE TO CEILING AT 1ST FL LOBBY 2)BULKHEAD DOOR NO... | $250 | $0 | Jan 6, 2017 |
| Nov 17, 2016 | 35208059P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER-OBSERVED ON 11-17-16@ 9:30AM IN CELLAR. MISSING BRICKS IN BOILER RO... | $250 | $0 | Feb 14, 2017 |
| Nov 17, 2016 | 35208058N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 11-17-16 @ 9:30AM IN GAS METER ROOM IN CELLAR ROOM OBS... | $1,000 | $0 | Jan 20, 2017 |
| Nov 17, 2016 | 35208056J | RESOLVE | CLASS - 2 | SEC. 404.1 MISC VIOLATION. OBSERVED ON 11-17-16 @ 9:30AM IN CELLAR GASHOUSE PIPING FOR BOILER LINE NO PROPERLY LABELE... | $400 | $0 | Jan 20, 2017 |
| Nov 17, 2016 | 35208060M | RESOLVE | CLASS - 1 | GAS BEING SUPPLIED TO BLDG W/O INSPECTION OR CERTIFICATION BY DOB. OBSERVED ON 11-17-16 @ 9:30AM IN CELLAR-GAS METER ... | $1,000 | $0 | Jan 6, 2017 |
| Nov 17, 2016 | 35221530Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTE: PARAPET WALL AT ROOF LEVEL MISSING APPROX 6'-0"LONG COPINGS. R... | $250 | $0 | Jan 6, 2017 |
| May 19, 2016 | 35177826H | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED: 2 BULKHEAD DOORS NOT SELF CLOSING. REMEDY: COMPLY W/NOTICE OF VIOLATION. | $2,500 | $0 | Jul 15, 2016 |
| Jun 19, 2015 | 32074748K | RESOLVE | CLASS - 2 | B254,26,50A,50B. 50A-BOILER DOOR BOLTS NOT DOGGED DOWN LOWER RIGHT HAND SIDE FRONT; 50B-OIL PUMP MISSING PULLY GUARD;... | $500 | $0 | Aug 7, 2015 |
| Sep 16, 2013 | 32073789M | RESOLVE | CLASS - 2 | B254,15,32A,46B,48A,50A,B. 50A- MISSING BOLTS @ BOILER DOOR. 50B- MISSING PULLYGUARD @ OIL PUMP: 15. | $500 | $0 | Nov 1, 2013 |
| Aug 8, 2008 | 32060223K | RESOLVE | CLASS - 3 | 301.1,B354,26,32A,44C. | $500 | $0 | Oct 3, 2008 |
| Dec 17, 1998 | 34177785Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. DEFECT IS: SEPARATING, DEFECTIVE & SINKING FL INBATH & BDRM IN APT 3C 3RD FL SOUTH WING. REMEDY:... | $0 | $0 | Jul 23, 1999 |