ECB violations

25-29 West Tremont Avenue, Bronx • Block 02869 • Lot 0167

49 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jan 23, 2026 39174901K RESOLVE CLASS - 1 ATOI AT ABOVE PREMISES OBSERVED STACKS OF TILE MORTARS AND CEMENT BROADS BEING STORED ON 1ST FLOOR HALLWAY NEXT TO AN... $0 $0 Apr 3, 2026
Nov 21, 2025 39547214H RESOLVE CLASS - 1 AT THE TIME OF INSPECTION OF A 6 STORY BUILDING WITH ALTERATION WORK BEING DONE I OBSERVED SIDEWALK SHED WITH ERECTED... $0 $0 Jan 30, 2026
Oct 8, 2025 39163006K RESOLVE CLASS - 1 CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. RE... $1,250 $0 Dec 19, 2025
Feb 15, 2022 39056227K RESOLVE CLASS - 2 PHONE NOT WORKING $625 $0 Jun 3, 2022
Feb 28, 2020 39018574H RESOLVE CLASS - 1 MISSING LIGHT FIXTURES IN LIVING ROOM, BATHROOM, DEFECTIVE LIGHT FIXTURES IN BED ROOMS, DEFECTIVE OUTLET RECEPTACLES ... $1,600 $0 Aug 28, 2020
Dec 11, 2019 35460757R RESOLVE CLASS - 1 ELECTRICAL WORK W/O A PERMIT FOR THE INSTALLATION OF SEVERAL OUTSIDE LIGHT FIXTURES. FOR THE USE OF BX CABLE IN WET L... $800 $0 Jan 31, 2020
Jan 30, 2019 35382716J RESOLVE CLASS - 2 FAILURE TO MAINTAIN. AT TIME OF INSPECTION OBSERVED SIDEWALK SHED IN PLACE WITH MISSING END CAPS FOR BOLTZ AND ROTTED... $2,400 $0 May 10, 2019
Jan 4, 2019 35359767Y RESOLVE CLASS - 1 UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.IN MARCH 05,2018.A ELECTRICAL VIOLATION WAS ISSUE T... $0 $0 Feb 15, 2019
Dec 5, 2018 35380812K RESOLVE CLASS - 1 FAILURE TO MAINTAIN ADEQUATE HOUSE KEEPING.AT TIME OF INSPECTION OF AN ACTIVE JOB SITE I OBSERVED POOR HOUSE KEEPING ... $2,500 $0 May 10, 2019
Dec 5, 2018 35380815X RESOLVE CLASS - 1 3301.1.2 ALL EQUIPMENT SHALL BE USED IN ACCORDANCE WITH THE SPECIFICATIONS OF THE MANUFACTURERS. NOTED: AT TIME OF IN... $625 $0 Apr 12, 2019
Dec 5, 2018 35380813M RESOLVE CLASS - 1 3314.6.1 SAFE POINT ANCHORAGE. NOTED: AT TIME OF INSPECTION I OBSERVEDA ROPE C-HOOK SUSPENDED SCAFFOLD TIE BACK ANCHO... $625 $0 May 10, 2019
Dec 5, 2018 35380814Y RESOLVE CLASS - 1 FAILURE TO MAINTAIN /DISPLAY ON SITE DOCUMENTS REQUIRED BY CHAPTER 33 NOTED: AT TIME OF INSPECTION I OBSERVED ACTIVE ... $625 $0 May 10, 2019
Jun 27, 2018 35341860N RESOLVE CLASS - 3 RAMP ERECTED 3/31/08 UNDER JOB #210042407. HAS LOOSE BRICKS AT ONE AREA ALONG ITS PATHWAY; ALONG THE SIDE, UNEVEN HEI... $0 $0 Aug 30, 2018
May 23, 2018 35313427Y RESOLVE CLASS - 1 AN UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS #353129... $2,530 $0 Jul 20, 2018
Apr 19, 2018 35337174L RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/ VIOLATION #35322090M ISSUED ON 03/08/18 AND TO ... $1,250 $0 Jun 26, 2018
Apr 19, 2018 35337173J RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35322089P ISSUED ON 03-08-18 & TO FILE A C OF C PURSUAN... $0 $0 Jun 15, 2018
Mar 8, 2018 35322090M RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.@ THE TIME OF INSPECTION,OBSERVED 4TH FL,3RD,2ND AND 1ST FLOOR ... $3,125 $0 May 4, 2018
Mar 8, 2018 35322089P RESOLVE CLASS - 1 OCCUPANCY CONTRARY TO CERTIFICATE OF OCCUPANCY AND BUILDING DEPARTMENTRECORDS.@ THE TIME OF INSPECTION OBSERVED @ CEL... $0 $0 May 8, 2018
Mar 5, 2018 35312921P RESOLVE CLASS - 1 ELECTRICAL WORK W/OUT A PERMIT. APT#5G: FEEDER,BRANCH CIRCUITS WIRING,LIGHTS,SWITCHES. 'NOT ON FILE'. 'PLEASE NOTE' T... $1,600 $0 Jun 8, 2018
Feb 26, 2018 35312835Z RESOLVE CLASS - 2 UNAPPROVED/UNSUITABLE/UNSAFE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. BROKEN... $800 $0 Apr 20, 2018
Feb 20, 2018 35312901H RESOLVE CLASS - 1 UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALDEVICES, APPLIANCES OR WIRING IN USE. THE ENTIR... $1,600 $0 Apr 6, 2018
Jan 17, 2018 35311676X RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER MISSING HANDRAILS ATSTAIRCASE FLOORS 1-4. REMEDY: REPAIR/REPLACE. $1,000 $0 Mar 16, 2018
Jan 17, 2018 35311675Y RESOLVE CLASS - 2 WORK W/O A PERMIT. TIME OF INSPECTION I OBSERVED A 1/2" PLYWOOD ERECTED AS FULL HEIGHT PARTITION FOR STORAGE OF 1ST F... $800 $0 Mar 16, 2018
Jan 17, 2018 35311677H RESOLVE CLASS - 2 OCCUPANCY CONTRARY TO C OF O & BLDG DEPT RECORDS-AT TIME OF INSPECTIONI OBSERVED A LOUNGE AREA ARRANGED W/2 COUCHES 2... $600 $0 Mar 16, 2018
Jan 3, 2018 35296056M RESOLVE CLASS - 2 FAILURE TO NOTIFY DEPT 24 HOUR PRIOR TO SUSPENDED SCAFFOLD REMOVAL. NOTED: AT TIME OF INSPECTION SUSPENDED SCAFFOLDS ... $800 $0 Mar 15, 2018
Oct 31, 2017 38259105X RESOLVE CLASS - 1 C/U 05A10,05I10,05M07,16F10,98BB05,03B07,80B07,70M07,64M07.(05A10)CEASE USE ITEM DOOR ZONE RESTRICTOR HAS BEEN ALTERE... $1,000 $0 Dec 15, 2017
Oct 30, 2017 32092064Z RESOLVE CLASS - 1 CEASE USE. 51. HAZARDOUS CONDITION BOILER SEALED. FOUND EASTMOND BOILER W/ HOLES IN THE FLUE. DONT OPERATE BOILER UNT... $1,000 $0 Dec 15, 2017
Jul 13, 2015 35136855X RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG.NOTED IN APT 3G. LIVING ROOM PLASTER CEILING APPROX 18FT X 14FT COLLAPSED & CEILINGS IN KITC... $1,000 $0 Sep 4, 2015
Dec 31, 2014 35114739L RESOLVE CLASS - 1 GAS BEING SUPPLIED TO BLDG W/O INPSECTION AND CERTIFICATION BY DOB. ATTIME OF INSPECTION (11:17AM) I OBSERVED NEW GAS... $0 $0 Apr 24, 2015
Dec 31, 2014 35114740Z RESOLVE CLASS - 1 FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. GAS LINE SUPPLYING BOILER HOKED UP ILLEGALLY AND W/O APPROVAL ... $1,000 $0 Apr 24, 2015
Dec 30, 2014 35108398L RESOLVE CLASS - 1 FAILURE TO PROVIDED UNOBSTRUCTED EXIT PASSAGEWAY @ REAR OF COUNT YARD.OBSTRUCTED NOTED:UNDER FIRE ESCAPE LADDER OCCUM... $1,000 $0 Feb 20, 2015
Dec 30, 2014 35108399N RESOLVE CLASS - 2 28-118.3.2,OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERT OF OCCUPANCYOR BLDG DEPT RECORDS.OCCUPANCY NOTED:@ BSMT LEV... $600 $0 Feb 20, 2015
Nov 5, 2012 38223995M RESOLVE CLASS - 2 03M11,39O02,52M07,67M07,70O02,76Q03. 03M- REPLACE HAND RAIL IN CAR. 52M- PROVIDE CROSBY FOR HOIST ROPES SPIN OUT. 67M... $250 $0 Dec 21, 2012
Jun 28, 2011 34909456Y RESOLVE CLASS - 3 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. MISSING SECOND HANDRAIL ON EXTERIOR HANDICAP RAMP LEVEL OUT RA... $100 $0 Aug 19, 2011
Jun 28, 2011 34926787N RESOLVE CLASS - 2 RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN THE LEGALLY APPROVED # OF FAMILILIES. BASEMENT STORAGE RO... $0 $0 Dec 23, 2011
Jun 28, 2011 34909457X RESOLVE CLASS - 1 OCCUPANCY CONTRARY TO THAT ALLOWED BY BLDG DEPT RECORDS SRO. BASEMENT-ROOM IN BASEMENT, 2 BEDS, SRO, TV, RADIOS, CLOT... $0 $0 Aug 24, 2011
Nov 6, 2008 38192769P RESOLVE CLASS - 2 35Q03.40P16.70D02.70Z09.35Q03 INSTALL COVERS FOR ELECTRICAL BOXES UNDER CAR $0 $0 Jan 2, 2009
Sep 3, 2008 38190932R RESOLVE CLASS - 2 5L10.32L10.16L10.28L10.40P10. 5L CAR DOOR DON'T OPEN ALL THE WAY 32L CAR SHOES NEED REPAIR 16L HOISTWAY DOOR CHEKS 6,... $0 $0 Oct 31, 2008
Feb 11, 2008 34614330K RESOLVE Non-Hazardous FAILURE TO MAINTAIN HAZARDOUS DEFECTS ARE OBJECTS STORED ON FILE EXCAPES AND FIVE ESCAPE WINDOWS SILLS CREATE A HAZAR... $800 $0 Apr 7, 2008
Dec 6, 2007 34614267R RESOLVE Hazardous FAILURE TO POST PERMIT FOR SIDEWALK SHED APPL NUMBER 210016533 REMEDY: POST PERMIT $250 $0 Feb 1, 2008
Sep 5, 2007 38168888H RESOLVE Non-Hazardous 25D06,20M07,66O02,39P16. 25-D-06 SECURE TOP EMERGENCY EXIT (COVER) 20-M-07 5TH FLR VISION GLASS IS MISSING ON HATCH D... $180 $0 Nov 2, 2007
Jul 20, 2007 34586113Z RESOLVE Hazardous FAILURE TO MAINTAIN EXTERIOR BLDG WALL. NOTED: BRICK PARAPET WALL LEANING OUT OF PLUMB. APPROX 3" TO 4" MISSING MORTA... $2,000 $0 Oct 19, 2007
Mar 29, 2007 34568079P RESOLVE Non-Hazardous FAILURE TO MAINTAIN EXTERIOR BLDG WALL.BRICK PARAPIT WALL LEANING OUT OF PLUMBS APPROX 3"TO 4"MISSING MORTAR THRU OUT... $800 $0 May 18, 2007
Aug 9, 2006 34530615X RESOLVE Hazardous WORK W/O A PERMIT. WORK NOTED: METAL LENTALS REPLACED ON VARIOUS WINDOWS ON ALL FLOORS THRU-OUT PREMISES FRONT AND RE... $0 $0 Mar 9, 2007
Aug 9, 2006 34530616H RESOLVE Non-Hazardous FAILURE TO MAINTAIN DEFECTS ARE:AT VARIOUS WINDOWS FRONT & REAR OF PREMISES THERE ARE CRACKED,SPLIT, & SPALLING WINDO... $350 $0 Mar 9, 2007
Dec 15, 2005 38155724Z RESOLVE Non-Hazardous 20-Q-7/5-B-10/20-I-10/16-I-10. 20/Q NO GUARD ON HOISTWAY DOORS 2ND, 4TH ABD 6TH FLOORS. 5/B SPACING BETWEEN CAR DOORS... $180 $0 May 19, 2006
Oct 11, 2000 34261118M RESOLVE Non-Hazardous FAILURE TO PROVIDE,ELEVATOR LANDING SIGNS AN ALL FLOORS FAILURE TO PROVIDE 3"FLOOR NUMBER SIGNS AT STAIR LANDING ON A... $600 $0 Nov 24, 2000
Jun 6, 2000 38099079L RESOLVE Non-Hazardous 08V01 18Q03 17M07 75U16 50Y02 51#11 50U11 18-6TH FL. 17-H/DOOR VISION PANEL 2ND+6TH FLOORS 51-VERY NOISY,YEAR BOTTMING $0 $0 Jul 28, 2000
Apr 14, 1997 38059165L RESOLVE Non-Hazardous 03U,40U,50Y,36R,. 03- PROVIDE CAPACITY PLATE INSIDE CAR #50 PREFORM AND FILE 5 YEAR TEST AND TAG #36 REMOVE GATE OPEI... $200 $0 Dec 26, 1997