ECB violations
West 176 Street, Bronx • Block 02877 • Lot 0261
37 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 17, 2024 | 39125071J | RESOLVE | CLASS - 2 | OBSERVED PAINTED SPRINKLER CAPS THROUGHOUT BUILDING. ALSO OBSERVED PAINTED SPRINKLER HEAD IN THE LAUNDRY ROOM LOCATED... | $625 | $0 | Jan 20, 2026 |
| Apr 11, 2024 | 37028013Y | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8B AND 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTE... | $1,280 | $0 | Aug 2, 2024 |
| Jul 26, 2022 | 39066705P | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). | $1,250 | $0 | Sep 16, 2022 |
| Jan 13, 2020 | 39015693R | RESOLVE | CLASS - 1 | I OBSERVED ON THE 3RD FLOOR REAR YARD THE INSTALLATION OF SPLIT AC UNITS ,NO ACTIVE OR PREVIOUSLY ISSUED PERMITS ON F... | $1,600 | $0 | Aug 27, 2021 |
| Jan 13, 2020 | 39015694Z | RESOLVE | CLASS - 2 | I OBSERVED THE INSTALLATION OF BX CABLING INTO PLASTIC OUTLET BOXES, THIS FAILS TO PROVIDE ELECTRICAL CONTINUITY AS R... | $1,200 | $0 | Jan 8, 2021 |
| Jan 13, 2020 | 39015692P | RESOLVE | CLASS - 1 | I OBSERVED IN THE HALLWAYS THROUGHOUT THE BUILDING THE IMPROPER WIRING OF THE CONVENIENCE RECEPTACLES. ALL THE RECEPT... | $1,600 | $0 | Jan 8, 2021 |
| Jul 8, 2019 | 35414971K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NO FIRE STOPPINGPER BC712.3;27-345.AT PARKING LEVEL NO FIRE STO... | $0 | $0 | Aug 30, 2019 |
| Sep 12, 2018 | 38265279R | RESOLVE | CLASS - 2 | 67X10,68M7,68M7,71X10. 67X10-PHONE NOT WORKING IN CAR; 68M7-PROVIDE MAINTENANCE LOG; 68M7-PROVIDE MAINTENANCE CONTROL... | $625 | $0 | Nov 30, 2018 |
| Sep 12, 2018 | 38265280Y | RESOLVE | CLASS - 2 | 67X10,68M7,68M7. 67X10-IN CAR PHONE NOT WORKING; 68M7-PROVIDE MAIN TENANCE LOG; 68M7-PROVIDE MAINTENANCE CONTROL PROG... | $625 | $0 | Nov 30, 2018 |
| Jul 10, 2018 | 32097268N | RESOLVE | CLASS - 2 | B254,50A,50B. AS PER CLASS 2 (B254) 28-301.1 FAILURE TO MAINTAIN 50A-"U" RATED EXPANSION TANK WITH NO PRESSURE RELIEF... | $315 | $0 | Jan 11, 2019 |
| May 15, 2018 | 35341602K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN OCDE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. FIRE STOP MISSING IN THE GAS... | $0 | $0 | Aug 31, 2018 |
| Apr 20, 2018 | 35329109P | RESOLVE | CLASS - 1 | UN;AWFUL ACTS. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. FAILURE TO COMPLY W/THE COMM'S ORDER TO CORRECT SUMM... | $0 | $0 | Jun 14, 2018 |
| Apr 5, 2018 | 35326095J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. NOTED: @ TIME OF INSP @ UPK LEVEL THE DOORS TO EACH CLASSROOM DOE'S NOT SELF-CLOSE. REM: ... | $0 | $0 | Jun 1, 2018 |
| Nov 13, 2017 | 35296957J | RESOLVE | CLASS - 2 | FAILUR ETO INSTALL GROUND FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED OBSERVED IN LAUNDRY ROOM.RECEPTACLE... | $2,400 | $0 | Mar 9, 2018 |
| Nov 13, 2017 | 35296956H | RESOLVE | CLASS - 1 | EC-110.2 (B) SERVICE IN EXCESS OF 1000 KVA HAS NOT BEEN SUBMITTED FOR APPROVAL.OBSERVED IN THE ELECTRICAL ROOM.THE IN... | $0 | $0 | Apr 24, 2018 |
| Nov 13, 2017 | 35296932N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:NO FIRE STOPPING PER BC 712.3;27-345.NOTED:OBSERVED NUMBEROUS HOLES... | $500 | $0 | Mar 9, 2018 |
| Oct 26, 2017 | 38258823X | RESOLVE | CLASS - 2 | 67X10,42B10-67)REPAIR IN CAR PHONE. 42)REPAIR DPM TO COMPLY WITH CODE. | $500 | $0 | Mar 2, 2018 |
| Oct 26, 2017 | 38258822Y | RESOLVE | CLASS - 2 | 42B10. REPAIR DOOR POSITION MONITOR AS PER CODE. | $500 | $0 | Mar 2, 2018 |
| Oct 25, 2017 | 38258820K | RESOLVE | CLASS - 1 | CEASE USE. 42B10,57BB11,52B14,67X10,100B10,40S9. (42B)DOOR POSITION MONITOR INOPERATIVE. THIS IS A SAFETY DEVICE. REP... | $500 | $0 | Mar 2, 2018 |
| Nov 9, 2016 | 35221327Z | RESOLVE | CLASS - 2 | FGC411.1/MISCELLANEOUS VIOLATION.RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT.OBSERVED ON 11/09/16 RESIDENTIAL G... | $800 | $0 | Jul 28, 2017 |
| Nov 9, 2016 | 35221325P | RESOLVE | CLASS - 1 | FGC404.1/MISCELLANEOUS VIOLATION GAS PIPING PROHIBITED LOCATION FIRE PUMP ROOM.OBSERVED ON 11/09/16 GAS LINE INSTALLE... | $1,600 | $0 | Jul 28, 2017 |
| Nov 9, 2016 | 35221326R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.OBSERVED ON 11/09/16EXTRA SPRINKLER LEADS AND WRENCH AT THE TIME OF... | $500 | $0 | Dec 30, 2016 |
| Oct 5, 2016 | 35213714Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NOTED: AT 1ST STY GARAGE APP... | $2,500 | $0 | Dec 16, 2016 |
| Apr 6, 2016 | 35177342L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO FIRE STOPPING AT PER BC 712.3. NOTE: AT TIME OF INSPECTION ... | $5,000 | $0 | Jun 3, 2016 |
| Feb 25, 2016 | 35171509R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING AT PER BC 712.3. AT 1ST STORY GARAGE APPRX 14... | $2,500 | $0 | Apr 15, 2016 |
| Apr 17, 2014 | 35087949Z | RESOLVE | CLASS - 1 | PARTIAL STOP WORK ORDER ISSUED @ 1650 UNDERCLIFF AVE WORK DOES NOT CONFORM TO APPROVED CONST DOCUMENTS OR APPROVED AM... | $1,000 | $0 | Jun 6, 2014 |
| Apr 17, 2014 | 35087948R | RESOLVE | CLASS - 1 | PARTIAL STOP WORD ORDER ISSUED @ 1650 UNDERCLIFF AVE,USE OF SUPPORTED SCAFFOLD W/O A SCAFFOLD USER CERT.NOTED-UPON IN... | $1,600 | $0 | Jun 6, 2014 |
| Feb 3, 2014 | 35088661Y | RESOLVE | CLASS - 2 | BC3303.7.2 FAILURE TO HAVE ADEQUATE FIRE EXTINGUISHERS UPON INSPECTIONAS NOTED ON ACTIVE CONSTRUCTION SITE THERE IS A... | $0 | $0 | Mar 21, 2014 |
| Feb 3, 2014 | 35088662X | RESOLVE | CLASS - 1 | BC3303.8 STANDPIPE IS NOT PAINTED RED. AS NOTED AT TIME OF INSPECTION STANDPIPE IS NOT PAINTED RED FROM 2ND FLOOR TO ... | $400 | $0 | Apr 18, 2014 |
| Oct 17, 2013 | 35077207K | RESOLVE | CLASS - 2 | 3314.5 SCAFFOLDS AT 6TH FLOOR WERE NOT FULLY PROVIDED BETWEEN UNRIGHTS AND THE GUARDRAIL SYSTEM SUPPORTS IN ACCORDANC... | $0 | $0 | Dec 6, 2013 |
| Oct 17, 2013 | 35077204P | RESOLVE | CLASS - 1 | FAILURE TO INSTITUTE/MAINTAIN SAFETY EQUIPMENT MEASURES OR TEMPORARY CONSTRUCTION.NO HANDRAILS.NO HAND RAILING HAS YE... | $1,000 | $0 | Dec 20, 2013 |
| Oct 17, 2013 | 35077205R | RESOLVE | CLASS - 1 | 3309.1 ROOF PROTECTION HAS NOT BEEN PROVIDED AT EXPOSURE 4 (SOUTH WALL) FOR ADJU BUILDING.ONLY 9 PLASTIC TARP NAILED ... | $1,600 | $0 | Dec 30, 2013 |
| Oct 17, 2013 | 35077208M | RESOLVE | CLASS - 1 | 3301.1.2 NO FDNY PERMIT/CERTIFICATE WAS PRODUCED AT SITE FOR OXYGEN AND ACETYLENE TANKS OBSERVED TIED TO COLUMN ON 5T... | $1,600 | $0 | Dec 30, 2013 |
| Oct 17, 2013 | 35077200H | RESOLVE | CLASS - 2 | SITE HAS NOT BEEN FULLY ENCLOSED WITH A FENCE THAT MEETS SECTION 3307.7 OF CHAPTER 33 OF NYC BLDG CODE. LARGE SECTION... | $0 | $0 | Dec 6, 2013 |
| Oct 17, 2013 | 35077203N | RESOLVE | CLASS - 2 | FAILURE TO POST "NO SMOKING" SIGNS AT CONSTRUCTION SITE PER FIRE CODE.NO "NO SMOKING" SIGNS WERE OBSERVED THROUGHOUT ... | $0 | $0 | Dec 6, 2013 |
| Oct 17, 2013 | 35077206Z | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE/INSTALL SCREW JACKS AND OR MUD SILLS FOR SUPPORTED SCAFFOLDING AT 6TH FLOOR. RMDY: PROVIDE AND INS... | $0 | $0 | Dec 6, 2013 |
| Oct 17, 2013 | 35077202L | RESOLVE | CLASS - 1 | FAILURE TO INSTITUTE/MAINTAIN SAFETY EQUIPMENT MEASURES OR TEMPORARY CONSTRUCTION.NO GUARDRAILS.NO GUARD & RAILING HA... | $2,400 | $0 | Dec 30, 2013 |