Issued Violation Status Severity Description Penalty Balance due Hearing
May 7, 2026 39187756X RESOLVE CLASS - 2 CONTRARY TO DOB/OFFICIAL RECORDS WHICH INDICATES A 6 STORY MULTIPLE DWELLING WITH ONLY CLASS 'A' APTS: AT TIME OF INS... $0 $0 Aug 7, 2026
May 7, 2026 39187753K ACTIVE CLASS - 1 W/O A PERMIT. NOTED: AT TIME OF INSPECTION APPRX 24 SQ FT OF CEILING WATER DAMAGE WAS OBSERVED REPLACED W/O FIRE RATE... $2,500 $2,500 Aug 7, 2026
May 7, 2026 39187754M RESOLVE CLASS - 2 W/O A PERMIT. NOTED: FULL HEIGHT PARTITION WALLS OBSERVED ERECTED AT VARIOUS LOCATIONS TO CREATE ADDL'T BDRMS IN APTS... $0 $0 Aug 7, 2026
May 7, 2026 39187755Y ACTIVE CLASS - 1 W/O A PERMIT. NOTED: AT TIME OF INSPECTION - GAS LINES OBSERVED ALTERED TO REMOVE ILLEGAL TAPS TO DRYERS FROM STOVE P... $2,500 $2,500 Aug 7, 2026
Apr 24, 2026 39186336P ACTIVE CLASS - 1 W/O A PERMIT. NOTED: 220V ELECTRICAL LINE INSTALLED AT APT 6D FOR A DRYER OUTLET. AT CELLAR - 110V LINES INSTALLED FO... $2,500 $2,500 Feb 12, 2027
Apr 24, 2026 39186335N ACTIVE CLASS - 1 W/O A PERMIT. NOTED: ILLEGAL GAS TAPS - PIPES & FLEX HOSE FROM STOVE LINE: INSTALLED IN AN UNSAFE MANNER FOR DRYERS I... $2,500 $2,500 Jul 31, 2026
Apr 24, 2026 39186334L ACTIVE CLASS - 2 W/O A PERMIT. NOTED: AT TIME OF INSPECTION - CELLAR APT OBSERVED DISMANTLED: PLUMBING, PARTITIONS, ELECTRICAL REMOVED... $1,250 $1,250 Feb 12, 2027
Apr 24, 2026 39186338Z ACTIVE CLASS - 1 W/O A PERMIT. NOTED: AT TIME OF INSPECTION - CELLAR APT OBSERVED CREATED RE-LOCATED FROM ORIGINAL LOCATION. PLUMBING ... $2,500 $2,500 Feb 12, 2027
Apr 24, 2026 39186340H ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: LACK OF REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER... $2,500 $2,500 Feb 12, 2027
Apr 24, 2026 39186339K ACTIVE CLASS - 1 FAILURE TO OBEY A VACATE ORDER FROM THE COMMISSIONER PER 28-207.4. NOTED: AT TIME OF INSPECTION - CELLAR APT OBSERVED... $10,000 $10,000 Feb 12, 2027
Apr 24, 2026 39186337R RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27- 37... $1,250 $0 Feb 12, 2027
Mar 9, 2026 39551395H RESOLVE CLASS - 1 AT THE TIME OF INSPECTION OF A 6-STORY BUILDING, I OBSERVED WORKERS ON ROOF LEVEL INSTALLING WOOD JOIST UPON REQUESTI... $2,500 $0 May 15, 2026
Mar 9, 2026 39551398N RESOLVE CLASS - 2 AT THE TIME OF INSPECTION, I OBSERVED FIRE REPAIR WORK AT THE SOUTH SIDE ROOF OF A 6-STORY BUILDING, WORKERS WERE INS... $5,000 $5,000 Dec 17, 2026
Feb 2, 2026 39175655Z ACTIVE CLASS - 1 FAILURE TO OBEY A VACATE ORDER FROM THE COMMISSIONERPER28-207.4. NOTED: AT TIME OF INSPECTION - APT 1C WAS OBSERVED R... $10,000 $10,000 Nov 13, 2026
Jan 16, 2026 39174305Y ACTIVE CLASS - 1 THE ONLY ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT... $1,250 $1,250 Mar 18, 2027
Jan 9, 2026 35718825P ACTIVE CLASS - 1 FAILURE TO COMPLY WITH COMMISSIONER'S ORDER DOB-FTC-VIO #122225FEU20401BS, DOB-FTC CONTROL #350341 DATED 12/22/2025. ... $6,250 $6,250 Oct 8, 2026
Nov 24, 2025 35685684M RESOLVE CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER. AT TIME OFINSPECTION OBSERVED WORK PERFORMED WITHOUT DOB ... $0 $0 Aug 7, 2026
Nov 3, 2025 39165817N ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED MAIN STAIRWELL IN COMPLETE DISR... $12,500 $12,500 Aug 10, 2026
Dec 20, 2024 39133417H RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT-MANNER; NOTED: OBSERVED HOLES IN CEILING & WALLS(HALLWAY IN APT), FLOO... $0 $0 Mar 7, 2025
Dec 19, 2024 35689527R RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 WEST CRACK... $2,500 $0 Mar 7, 2025
Dec 19, 2024 35689528Z RESOLVE CLASS - 1 FAILURE TO PROVIDE AN UNOBSTRUCTED EXIT PASSAGEWAY. NOTE: AT TIME OF INSPECTION, I OBSERVED OBJECTS ON FIRE ESCAPES A... $312 $0 Mar 7, 2025
Jul 9, 2024 39118685Z RESOLVE CLASS - 2 EMERGENCY PHONE NOT WORKING, REPAIR, SECURE COUNTERWEIGHT CABLES WITH PROPER FASTENINGS;BRAKE MAINTANCE TAGS EXPIRED $0 $0 Sep 20, 2024
Apr 16, 2024 35682545Z RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTE: AT TIME OF INSPECTION OBSERVED SEVERAL ITEMS ON FIRE ESCAPES A... $1,250 $0 Dec 3, 2024
Apr 16, 2024 35682546K RESOLVE CLASS - 1 FAILURE TO MAINTAIN EXTERIOR BUILING FACADE AND APPURTENANCES. NOTE: OBSERVED AT EXPOSURE 1(EAST) AND EXPOSURE 2(SOUT... $2,500 $0 Dec 3, 2024
Dec 8, 2023 39100957H RESOLVE CLASS - 1 DOOR RESTRICTOR NOT WORKING PROPERLY,;FIX; PROVIDE CLEAR ACCESS TO MOTOR ROOM; REPAIR PHONE IN ELEVATOR $1,250 $0 Jun 28, 2024
Feb 10, 2021 35527151X RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#39011071Y ISSUED ON 10/10/2019 AND TO ... $0 $0 Apr 30, 2021
Nov 25, 2020 35519197L RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#39011071Y ISSUED ON 10/10/19 & TO FILE A CERT OF CORREC... $0 $0 Aug 13, 2021
Sep 29, 2020 35521036N RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMMISSIOER'S ORDER CONTAIED IN SUMMONS/VIOLATION #39011071Y ISSUED ON 10/10/19 & TO FILE A C... $0 $0 Jun 25, 2021
Mar 12, 2020 39019570P RESOLVE CLASS - 1 DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED (CU). IN CAR PHONE NOT WORKING. OVERHEAD SHEAVE WORN CABLE SI... $1,250 $0 Sep 18, 2020
Jan 8, 2020 35461217K RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35442334X ISSUED ON 10-10-19 & TO FILE A C OF C PURSUAN... $0 $0 Jul 10, 2020
Jan 8, 2020 35461218M RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35442334X ISSUED ON 10-10-19 & TO FILE A C OF C PURSUAN... $0 $0 Dec 11, 2020
Oct 10, 2019 35442332M RESOLVE CLASS - 1 UNAPPROVED, UNSAFE, UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. I OB... $0 $0 Jul 10, 2020
Oct 10, 2019 39011072X RESOLVE CLASS - 2 I OBSERVED ACTIVE WATER LEAK IN THE ELEVATOR MACHINE ROOM. , REPAIR AND/OR REPLACE $312 $0 Feb 14, 2020
Oct 10, 2019 35400130Z RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35267311H ISSUED ON 05/18/17 AND TO FI... $0 $0 Jul 10, 2020
Oct 10, 2019 39011073H RESOLVE CLASS - 2 GAS METER ROOM LOCATED IN CELLAR HAS WASHING MACHINE, DRYER AND ALSO A TABLE WITH CHAIRS ALSO HAS CLOTHES HANGING FRO... $0 $0 Nov 29, 2019
Oct 10, 2019 35442331K RESOLVE CLASS - 2 ELECTRICAL WORK W/O A PERMIT. I OBSERVED IN THE BASEMENT THE INSTALLATION OF BRANCH CIRCUITS, CIRCUIT BREAKER PANEL &... $0 $0 Jul 10, 2020
Oct 10, 2019 35442333Y RESOLVE CLASS - 2 FAILURE TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS I OBSERVED THROUGHOUT THE BUILDINGS HALLWAYS IM... $0 $0 Jul 10, 2020
Oct 10, 2019 39011071Y RESOLVE CLASS - 1 FUTURE CONNECTION EXIST DOWN STREAM FROM APPLIANCE. IN THE CELLAR A TEE WITH A PLUG ON THE BULL IN INSTALLED ON THE R... $0 $0 Apr 23, 2021
Oct 10, 2019 39011070M RESOLVE CLASS - 2 NOTED: OBSERVED AT REAR EAST ELEVATION BETWEEN NORTH AND SOUTH BUILDINGS, HORIZONTAL AND VERTICAL CRACK NEAR PARAPET ... $0 $0 Feb 14, 2020
Oct 10, 2019 35442335H RESOLVE CLASS - 1 FILED A CERTIFICATE OF CORRECTION OR OTHER RELATED MATERIALS CONTAINING MATERIAL FALSE STATEMENT(S). I OBSERVED DURIN... $0 $0 Jul 24, 2020
Oct 10, 2019 35442334X RESOLVE CLASS - 1 FILED A CERTIFICATE OR CORRECTION OR OTHER REALTED MATERIALS CONTAINING MATERIAL FALSE STATEMENT(S). AS PER PREVIOUSL... $0 $0 Nov 27, 2020
Jan 25, 2019 38267880R ACTIVE CLASS - 2 40M7,37M7,67X10,70M7-40M7)PROVIDE ACCESS TO MACHINE ROOM, MISSING KEYS. 37M7)PROVIDE ACCESS TO OVERHEAD, MISSING KEYS... $625 $0 Mar 21, 2019
Aug 20, 2018 35387289R RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35324834P ISSUED ON 03-22-18 & TO FILE A C OF C PURSUAN... $0 $0 Jan 11, 2019
Jul 11, 2018 35341897R RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:AT EXPOSURE#2 THERE CRACKS IN BRICKS AND MORTAR FROM PARAP... $6,250 $0 Aug 31, 2018
Jul 11, 2018 35340746P RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35324834P ISSUED ON 03/22/18 AND TO FI... $1,250 $0 Aug 31, 2018
May 16, 2018 35338271H RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/ VIOLATION #35324834P ISSUED ON 03/22/18 AND TO ... $1,250 $0 Jul 27, 2018
May 16, 2018 35338270X RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/ VIOLATION #35322347Z ISSUED ON 03/22/18 AND TO ... $625 $0 Jul 27, 2018
May 16, 2018 35334159J RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED AT EXP#2 BUILDING LEFT SIDE, PARAPET WALL HAS CRACK GOIN... $1,562 $0 Jul 27, 2018
Mar 22, 2018 35322347Z RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: AT CELLAR LEVEL ... $2,500 $0 Jun 1, 2018
Mar 22, 2018 35324835R RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED ON 03/22/2018 AT ABOVE ADDRESS NEW GAS PIPING IN CELL... $312 $0 Jul 27, 2018