| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 30, 2025 | 39171903K | ACTIVE | CLASS - 2 | OBSERVED THROUGHOUT THE BUILDING OBSTRUCTED SPRINKLER HEADS , MISSING TRAP WRAP INSULATION UNDER BATHROOMS SINKS AND ... | $1,250 | $1,250 | Jul 17, 2026 |
| Dec 30, 2025 | 39171904M | ACTIVE | CLASS - 2 | OBSERVED ON THE GROUND FLOOR: THE WATER METER AND SPRINKLER MAIN ARE LOCATED IN THE SAME ROOM AS THE ELECTRICAL SERVI... | $1,250 | $1,250 | Aug 21, 2026 |
| Apr 8, 2025 | 39144221J | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED PAINTED SPRINKLER HEAD IN STAIRWELL B. LOCATED ON THE... | $625 | $0 | Oct 3, 2025 |
| Apr 7, 2025 | 39144082Z | ACTIVE | CLASS - 2 | CLASS 2 ITEM: HOIST ROPES SHOW SIGNS OF ROUGE. REPLACE. | $625 | $315 | Jun 20, 2025 |
| Sep 5, 2023 | 39094064M | RESOLVE | CLASS - 2 | COMBUSTION AIR FAN TO BOILER ROOM NOT INTERLOCKED WITH BURNER AND FAN IS NOT OPERATING. NO BODY DRAIN INSTALLED FROM ... | $0 | $0 | Apr 24, 2026 |
| Sep 5, 2023 | 39094080M | RESOLVE | CLASS - 2 | ILLEGAL HARDWARE, (BOLT LOCK) INSIDE THE ELECTRICAL & SPRINKLER CONTROL MECHANICAL ROOM LOCATED ON GROUND LEVEL/BREWE... | $0 | $0 | Jun 28, 2024 |
| Sep 5, 2023 | 39094098K | RESOLVE | CLASS - 1 | I OBSERVED ON THE UPPER AND LOWER ROOFS THE IMPROPER INSTALLATION OF EQUIPMENT DISCONNECT SWITCHES. THE EQUIPMENT DIS... | $0 | $0 | Jun 28, 2024 |
| Sep 5, 2023 | 39094073Y | ACTIVE | CLASS - 2 | OBSERVED ON THE 3RD FLOOR IN THE WATER HEATER ROOM SPRINKLER HEAD IS OBSTRUCTED BY CEILING. AS PER 102.3 MAINTENANCE.... | $3,125 | $3,125 | May 6, 2024 |
| Sep 5, 2023 | 39094097Z | ACTIVE | CLASS - 2 | I OBSERVED IN THE LOBBY THE USE OF EXTENSION CORDS TO SUPPLY POWER FOR THE X-RAY SCANNER. AS PER EC 400.8 THE USE OF ... | $400 | $400 | Mar 28, 2025 |
| Sep 5, 2023 | 39094099M | RESOLVE | CLASS - 2 | I OBSERVED ON THE 3RD FLOOR THE HOT WATER HEATER ROOM WITH NO REMOTE SHUT-DOWN AS REQUIRED IN MC 1006.8.1 FOR THE GAS... | $1,250 | $1,250 | Oct 24, 2025 |
| Apr 10, 2023 | 39083518Y | RESOLVE | CLASS - 1 | I OBSERVED ON BOTH THE UPPER AND LOWER ROOFS THE FAILURE TO INSTALL AN EQUIPMENT DISCONNECT ON THE HVAC UNITS. AS PER... | $0 | $0 | Jan 11, 2024 |
| Apr 10, 2023 | 39083388P | ACTIVE | CLASS - 2 | SPRINKLER HEAD ON THE WATER HEATER ROOM LOCATED ON THE 3RD FLOOR IS OBSTRUCTED BY CEILING. AS PER102.3 MAINTENANCE. I... | $312 | $0 | Aug 4, 2023 |
| Apr 10, 2023 | 39083519X | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOFTOP BOILER ROOM ENTRANCE NO REMOTE SHUT-DOWN FOR THE FUEL BURNING SYSTEMS AS REQUIRED IN MC 100... | $3,125 | $3,125 | Jan 2, 2024 |
| Apr 10, 2023 | 39083520N | RESOLVE | CLASS - 2 | I OBSERVED ON THE LOWER ROOF THE UNPERMITTED USE OF EMT IN AN OUTDOOR INSTALLATION, SUPPLYING POWER TO THE ROOF HVAC ... | $1,250 | $1,250 | Jun 16, 2023 |
| Apr 10, 2023 | 39083333H | RESOLVE | CLASS - 2 | SAFETY VALVE IS LEAKING-BACK FLOW VALVE LEAKING AND FLOODING UP BOILER ROOM FLOOR-BALL VALVE ON HOT WATER PIPE TO MIX... | $625 | $625 | Jan 26, 2024 |
| Feb 19, 2020 | 39017842K | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN 3.10.12 OF APPENDIX K3 OF 2014 BC. REMEDY: FILE APPLIC... | $0 | $0 | Nov 6, 2020 |
| Jan 8, 2019 | 35372223M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FAILURE TO PROVIDE EMERGENCY AND STANDBY POWER FOR THE ... | $625 | $0 | Mar 29, 2019 |
| Jan 8, 2019 | 35372222K | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS. NOTED: OBSEVED ON THE 2ND FLOOR-... | $0 | $0 | Mar 1, 2019 |
| Apr 6, 2018 | 35314465J | RESOLVE | CLASS - 2 | BC3301.9.2.FAILURE TO PROVIDE/POST PERMITS AT JOB SITR PURSUANT TO SUBSECTION.AT TIME OF INSPECTION OBSERVED THAT THE... | $0 | $0 | Jul 6, 2018 |
| Apr 6, 2018 | 35314464H | RESOLVE | CLASS - 2 | BC1704.1.1 FAILURE TO FILE FOR TR-1. AT TIME OF INSPECITON AFTER SEARCH AT BIS NOTED THAT THERE IS NO TRI FOR STRUCTU... | $0 | $0 | Jun 1, 2018 |
| Jan 30, 2013 | 34957073N | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATION: INSTALLATION OF CEMENT BLOCKS AT UPPE... | $2,400 | $0 | Apr 19, 2013 |
| Feb 23, 2012 | 34962744L | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/ THE COMMS ORDER CONTAINED IN NOV#34852547P ISSUED ON 12/20/11.NOTE:LOAD BEARING WALL REMOVED.NO ... | $0 | $0 | Apr 20, 2012 |
| Dec 20, 2011 | 34852547P | RESOLVE | CLASS - 1 | WORK W/O A PERMIT: ILLEGAL WORK NOTED - 1) AT 1ST FLR HAVING REMOVED REAR ENVELOP WALL & CONNECTED 1ST FLR LEVEL W/AD... | $0 | $0 | Feb 24, 2012 |
| Jun 7, 2001 | 34270871R | ACTIVE | Non-Hazardous | WORK WITHOUT A PERMIT. <NOTED>CONSTRUCTIONS OF CONCRETE WALLS AT THE FRONT AND SIDE (E.173ST) OF PROPERTY APPROX 70'X... | $2,500 | $0 | Aug 3, 2001 |
| May 25, 1999 | 34188136H | ACTIVE | Non-Hazardous | WORK W/O A PERMIT. WORK NOTED: CONSTRUCTION OF CONCRETE BLOCK WALLS ATFRONT & SIDE OF PROPERTY APPROX 70'X70'X23'. RE... | $10,000 | $0 | Nov 26, 1999 |
| Mar 23, 1998 | 34166321M | ACTIVE | Non-Hazardous | WORK WITHOUT A PERMIT. WORK NOTED: HAVING CONSTRUCTED MASONRY BLOCK WALLS APPROX 50'X50' AT FRONT & SIDE. REMEDY: FIL... | $2,500 | $0 | Jun 12, 1998 |