ECB violations
1802 Crotona Avenue, Bronx • Block 02948 • Lot 0003
39 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 27, 2026 | 39190045R | ACTIVE | CLASS - 1 | ATOI OBSERVED IN BASMENT OBSTRUCTED SPRINKLER HEADS IN BOILER ROOM AND PVC PIPE BEING USED ON EJECTOR PUMP.PER PC 712... | $2,500 | $2,500 | Aug 21, 2026 |
| Jun 13, 2025 | 39151086L | RESOLVE | CLASS - 1 | SUMMONS ISSUED FOR FAILURE TO PROVIDE UNOBSTRUCTED PASSAGEWAY DUE TO HALLWAY LEADING OUT TO EXIT PASSAGEWAY PARTIALLY... | $1,280 | $1,280 | Jul 16, 2026 |
| Jun 3, 2025 | 39149753N | RESOLVE | CLASS - 2 | CLASS 2 ITEMS: REPLACE WORN COUNTERWEIGHT GUIDE ROLLERS AS NEEDED. REPAIR SEPARATED EMT CONDUIT FOR PIT LIGHT FIXTURE. | $0 | $0 | Aug 15, 2025 |
| Apr 8, 2024 | 39111115P | RESOLVE | CLASS - 1 | I OBSERVED ON THE ROOF THE USE OF FLEXIBLE CORDS TO SUPPLY POWER FROM THE OUTDOOR CONDENSER TO THE INDOOR WALL MOUNTE... | $800 | $0 | Jan 20, 2026 |
| Apr 8, 2024 | 39111118K | RESOLVE | CLASS - 1 | I OBSERVED IN THE MAIN ELECTRICAL ROOM THE DATA WIRING AND EQUIPMENT STATED IN ECB# 39067272N ISSUED ON 08/10/2022 ST... | $2,500 | $0 | Jan 20, 2026 |
| Apr 8, 2024 | 39111119M | RESOLVE | CLASS - 1 | I OBSERVED IN THE MAIN ELECTRICAL ROOM , DATA EQUIPMENT AND WIRING AS STATED IN PREVIOUS ECBS# 35373081K ISSUED ON 11... | $800 | $0 | Jan 20, 2026 |
| Apr 8, 2024 | 39111116R | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT BOILER ROOM AN ACTIVE LEAK FROM THE FIRST BOILER DUE TO A DEFECTIVE CONTROL SYSTEM ON THE ... | $625 | $0 | Jan 20, 2026 |
| Apr 8, 2024 | 39111120J | RESOLVE | CLASS - 1 | I OBSERVED IN DOB RECORDS THE SUBMISSION OF A C OF C ON 09/19/2022 STATING THE RESPONDENT COMPLIED WITH ECB# 35373081... | $0 | $0 | Apr 2, 2026 |
| Apr 8, 2024 | 39111114N | RESOLVE | CLASS - 1 | I OBSERVED IN DOB RECORDS THE SUBMISSION OF A C OF C FOR ECB #39067272N ISSUED ON 08/03/2022 STATING DATA EQUIPMENT I... | $0 | $0 | Apr 2, 2026 |
| Apr 8, 2024 | 39111117Z | RESOLVE | CLASS - 1 | I OBSERVED IN DOB RECORDS THE FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDERS AS STATED IN ECB# 39067273P ISSUED ON ... | $0 | $0 | Jan 20, 2026 |
| Apr 8, 2024 | 39111113L | RESOLVE | CLASS - 2 | I OBSERVED THE INSTALLATION OF BRANCH CIRCUIT WIRING, EQUIPMENT DISCONNECTS AND RACEWAYS TO SUPPLY POWER TO SPLIT A.C... | $800 | $0 | Jan 20, 2026 |
| Feb 8, 2024 | 39105617Y | RESOLVE | CLASS - 2 | OBSERVED ACTIVE WATER LEAK IN THE BASEMENT/CELLAR. AS PER 102.3 OF THE PLUMBING CODE 102.3 MAINTENANCE. INSTALLATIONS... | $0 | $0 | Apr 19, 2024 |
| Aug 3, 2022 | 39067273P | RESOLVE | CLASS - 2 | I OBSERVED IN THE ELECTRICAL ROOM THE VIOLATING CONDITIONS OF THE DATA EQUIPMENT FOR THE BUILDING SECURITY SYSTEMS ST... | $0 | $0 | Sep 30, 2022 |
| Aug 3, 2022 | 39067270J | RESOLVE | CLASS - 2 | CELLAR LEVEL BOILER ROOM BOTH FIRE RATED DOORS HOLES CUT IN THEM AND MANUAL AIR LOUVERS INSTALLED NO RATING ON THEM, ... | $0 | $0 | Sep 30, 2022 |
| Aug 3, 2022 | 39067234M | RESOLVE | CLASS - 2 | NEUTRALIZER DRAIN PIPING LEAKING UNDER BOILER-CONDENSATE DRAIN FROM AC UNIT LEAKING UNDER BOILER-FLOOD IN BOILER ROOM. | $310 | $0 | Sep 30, 2022 |
| Aug 3, 2022 | 39067272N | RESOLVE | CLASS - 1 | I OBSERVED AT THE ENTRANCE OF ELECTRICAL EQUIPMENT ROOM THE DATA SERVER EQUIPMENT STILL IN PLACE. AS STATED IN ECB #3... | $300 | $0 | Sep 30, 2022 |
| Oct 23, 2019 | 39011670X | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOFTOP AREA MULTIPLE DEFECTIVE EXHAUST FANS. ALSO NOTED IN 6TH FLOOR STAIRWELL A A MOTION SENSOR L... | $400 | $0 | May 14, 2021 |
| Jul 12, 2019 | 39005434N | RESOLVE | CLASS - 2 | BOILER PIPING NEEDS MORE INSULATION- BOILER ROOM TOO HOT-INSUFFICIENT AMBIENT AIR TO BOILER ROOM ; CORRECT ALL VIOLAT... | $0 | $0 | Aug 30, 2019 |
| Jun 25, 2019 | 35423798K | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS#35422403M... | $2,500 | $0 | Sep 10, 2020 |
| Jun 25, 2019 | 35423797Z | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT.FOR THE INSTALLATION OF 46 METERS,TWO MAIN SERVICE DISCONNECT SWITCES,TWO ADDITIONAL DIS... | $0 | $0 | Sep 10, 2020 |
| May 7, 2019 | 35422403M | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE W/ SECTION. OBSERVED IN ELECTRIC METER ROOM IN SERVICE... | $800 | $0 | Oct 11, 2019 |
| Feb 28, 2019 | 35359828Z | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. IN 1/9/19 AN ADMINISTRATIVE CODE VIOLATION WAS ISSU... | $0 | $0 | May 10, 2019 |
| Feb 26, 2019 | 35386433H | RESOLVE | CLASS - 1 | BUILDING OR OPEN LOT OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCYNOTED: AT TIME OF INSPECION I OBSERVED NEW BUIL... | $625 | $0 | May 10, 2019 |
| Jan 9, 2019 | 35359771R | RESOLVE | CLASS - 1 | UNLAWFUL ACTS:FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.IN DECEMBER 18,2018,TWO VIOLATIONS WAS ISSUE TO THE... | $0 | $0 | Mar 15, 2019 |
| Dec 28, 2018 | 35373051J | RESOLVE | CLASS - 1 | NEW BUILDING OR OPEN LOT OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY. OBSERVED NEW BUILDING CONSTRUCTED UNDER A... | $3,125 | $0 | Feb 15, 2019 |
| Nov 8, 2018 | 35373081K | RESOLVE | CLASS - 1 | ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY.OBSERVED AT ENTRANCE OF ELECTRICAL EQUIPMEN... | $1,200 | $0 | Feb 15, 2019 |
| Nov 8, 2018 | 35372213Z | RESOLVE | CLASS - 1 | NEW BUILDING OR OPEN LOT OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY.NOTED: NEW BUILDING CONSTRUCTED UNDER JOB ... | $1,250 | $0 | Feb 15, 2019 |
| Nov 8, 2018 | 35373083Y | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE/MAINTAIN ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIPMENT.OBSERVED IN ELECTRICAL EQUIPMENT ROOM. OFFIC... | $0 | $0 | Feb 15, 2019 |
| Nov 8, 2018 | 35373082M | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS DEVICES,APPLIANCES OR WIRING IN USE.OBSERVED TH... | $400 | $0 | Feb 15, 2019 |
| May 1, 2018 | 32096766L | RESOLVE | CLASS - 2 | B254,50A-50E:AS PER CLASS 2(B254)28.301.1 FAILURE TO MAINTAIN;HOT WATER PIPING FROM STORAGE TANK NOT CAPPED.PRESSURE ... | $0 | $0 | Jun 15, 2018 |
| Sep 27, 2017 | 35293731N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS. EXIT DISCHARGES & PUBLIC COR... | $250 | $0 | Nov 17, 2017 |
| Sep 27, 2017 | 35293714L | RESOLVE | CLASS - 2 | FAILUR ETO MAINTAIN BLDG IN CODE.COMPLIANT MANNER.OBSERVED IN SPRINKLER CONTROL ROOM TO SPARE SPRINKLER HEADS STORED ... | $250 | $0 | Dec 1, 2017 |
| Sep 27, 2017 | 35293713J | RESOLVE | CLASS - 2 | FGC 411.1.MISC VIOS:RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT.OBSERVED IN LAUNDRY ROOM RESIDENTIAL GAS FLEX H... | $800 | $0 | Dec 1, 2017 |
| Dec 20, 2016 | 35208071H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER-OBSERVED ON 12-20-16 AT 11:40AM IN SPRINKLER ROOM-NO HEATING INSTAL... | $1,000 | $0 | Feb 3, 2017 |
| Dec 20, 2016 | 35208072J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER-OBSERVED ON 12-20-16@ 11:45AM PVC PIPING INSTALL ON SPRINKLER DRAIN... | $500 | $0 | Feb 3, 2017 |
| Mar 19, 2015 | 35079362J | RESOLVE | CLASS - 2 | FAILURE TO INSTALL GROUND-FAULT CIRCUIT INTERRUPTER(GFCI)PROTECTION ASREUIRED.THE ENTIRE BLDG TEMPORARY WIRING:NO GFC... | $1,200 | $0 | May 15, 2015 |
| Mar 19, 2015 | 35079361H | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT.THE ENTIRE BLDG:SERVICE SWITCHES 2-400AMP,2 100AMP 1-200AMP SERVICE ENTRANCE CONDUCTORS,... | $800 | $0 | May 15, 2015 |
| Nov 9, 2007 | 34619329X | RESOLVE | Hazardous | FAILURE TO MAINTAIN: DEFECT NOTED: METAL CHAIN LINK FENCE AROUND LOT IS RUSTED & OUT OF PLUMB & LEANING OUTWARDS TOWA... | $2,000 | $0 | Mar 14, 2008 |
| Jul 20, 2007 | 34589058Z | RESOLVE | Hazardous | FAILURE TO MAINTAIN HAZARDOUS DEFECTS ARE METAL FENCE ERECTED ON THE NORTH & WEST ENDS OF LOT ARE RUSTED OUT OF PLUMB... | $800 | $0 | Sep 21, 2007 |