ECB violations
1801 Clinton Avenue, Bronx • Block 02948 • Lot 0016
26 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 16, 2025 | 39163871P | RESOLVE | CLASS - 1 | CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. RE... | $1,250 | $1,250 | May 1, 2026 |
| Aug 24, 2023 | 39093993M | ACTIVE | CLASS - 2 | I OBSERVED ON THE ROOFTOP THE RACEWAY SUPPLYING POWER TO THE EXHAUST FAN NOT PROPERLY SUPPORTED OR SECURED AS REQUIRE... | $4,000 | $0 | Nov 17, 2023 |
| Aug 24, 2023 | 39093991Z | ACTIVE | CLASS - 1 | I OBSERVED IN THE REAR COURTYARD THE INSTALLATION OF BRANCH CIRCUIT WIRING, RACEWAYS, DISCONNECT SWITCHES TO SUPPLY P... | $8,000 | $0 | Nov 17, 2023 |
| Aug 24, 2023 | 39093992K | ACTIVE | CLASS - 1 | I OBSERVED IN THE REAR YARD THE USE OF FLEXIBLE WIRING TO SUPPLY POWER FROM THE SPLIT UNIT A.C. CONDENSER TO THE INDO... | $8,000 | $0 | Nov 17, 2023 |
| Apr 6, 2023 | 39083186R | ACTIVE | CLASS - 2 | AS PER ONE MODULAR SLANT/FIN HEATING BOILER. ONE MODULE IS LEAKING AND FLOODING UP BOILER ROOM FLOOR. | $625 | $0 | Aug 4, 2023 |
| Feb 23, 2022 | 35644412H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED FIRE PROOF SELF-CLOSING SYSTEM AT 3RD FLOOR LOURGE ROO... | $0 | $0 | May 20, 2022 |
| Nov 8, 2021 | 35635950K | RESOLVE | CLASS - 1 | FGC411.1 I OBSERVED@MAIN LEVEL IN LAUNDRYRM RESIDENTIAL GAS FLEX USED ON COMMERCIAL LAUNDRY EQUIPMENT AS PER FGC411.1... | $2,500 | $0 | Mar 4, 2022 |
| Oct 12, 2021 | 39049124M | RESOLVE | CLASS - 2 | FOUND TO HAVE LEAKING RETURN LINE AT BOILER, BOILER ROOM DOOR NOT SELF CLOSING. | $0 | $0 | Dec 3, 2021 |
| Dec 22, 2020 | 39033761Z | RESOLVE | CLASS - 3 | FOUND AT TIME OF INSPECTION THAT A UNION ON THE RETURN LINE IS LEAKING. | $250 | -$250 | Feb 5, 2021 |
| Aug 3, 2020 | 37020126Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#39005232P ISSUED ON 7/10/2019,AND TO FILE ... | $3,125 | -$3,125 | Oct 30, 2020 |
| Sep 25, 2019 | 38271935R | RESOLVE | CLASS - 1 | (C/U 16L10): (16,L,10) TOP FLOOR DOOR SPRING CLOSER DEFECTIVE BROKEN UNSAFE CONDITION | $3,125 | $0 | Feb 21, 2020 |
| Jul 10, 2019 | 39005232P | ACTIVE | CLASS - 2 | FOUND BYPASS VALVE AT BACK FLOW PREVENTER, BACK FLOW PREVENTER SHALL NOT HAVE BYPASS VALVE. REMOVE ALL COMBUSTIBLE ST... | $625 | $0 | Aug 30, 2019 |
| Jun 18, 2019 | 37015169H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #32097665R ISSUED ON 08-15-2018 AND TO FILE... | $3,125 | -$3,125 | Sep 27, 2019 |
| Apr 4, 2019 | 38268915M | RESOLVE | CLASS - 1 | 42.G.11:IMPROPER FUSES ON CONTROLLER | $1,280 | $0 | May 31, 2019 |
| Aug 15, 2018 | 32097665R | ACTIVE | CLASS - 2 | 32A.50A.50B.50C.50D-AS PER CLASS(B254)28.301.1 FAILURE TO MAINTAIN.32A:EXPOSED ELECTRICAL WIRING.50A:SPILL SWITCH INS... | $625 | $0 | Oct 5, 2018 |
| May 11, 2018 | 32096670R | RESOLVE | CLASS - 2 | 50. COMBUSTIBLE MATERIAL IN BOILER ROOM CORRECT ALL VIOLATING CONDITION & SUBMIT C OF C. | $312 | $0 | Jun 29, 2018 |
| Jan 2, 2018 | 35281692L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35293712H ISSUED ON 09/27/17 & TO FILE A C OF C PURSUAN... | $2,000 | -$2,000 | Feb 16, 2018 |
| Nov 14, 2017 | 35280705R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35293712H ISSUED ON 09/27/17 & TO FILE A C OF C PURSUAN... | $2,000 | $0 | Jan 5, 2018 |
| Sep 27, 2017 | 35293711X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. OBSERVED THE TOP OF THE STAIRWELL WHERE THE INSPECTOR'S TEST IS LO... | $1,250 | $0 | Nov 17, 2017 |
| Sep 27, 2017 | 35293730L | ACTIVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: @ STAIRCASE'B' THROUGHOUT, SEVERAL STEP CRACK & HORIZONTAL ... | $200 | $0 | Apr 13, 2018 |
| Sep 27, 2017 | 35293712H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.OBSERVED NO VENTILATION IN THE GAS METER ROOM AND THE ALARM C... | $1,000 | $0 | Nov 17, 2017 |
| Dec 20, 2016 | 35208069Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER FAILURE TO OBSERVED(LAW)OF DRAINAGE SYSTEM PER PC 702.1;27-911. COM... | $500 | $0 | May 12, 2017 |
| Dec 20, 2016 | 35208068R | ACTIVE | CLASS - 1 | SEC. 408.2 MISC VIOLATION. OBSERVED ON 12/20/16 @ 10:45AM ON 1ST FL BOILER ROOM. FUTURE TEE & CAPS EXIST DOWN STREAM ... | $800 | $0 | May 12, 2017 |
| Dec 20, 2016 | 35222826H | RESOLVE | CLASS - 1 | FGC411.1. MISCELL. VIO : OBSERVED ON 12/20/16 AT 10:45AM 1ST FL RESIDENTIAL GAS FLEX HOSES ON COMMERCIAL GAS DRYERS I... | $4,000 | -$4,000 | Feb 17, 2017 |
| Dec 20, 2016 | 35208073L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. FAILURE TO HAVE FIXTURE TRAPED OR VENTED. OBSERVED ON 12/20/16, 10... | $1,250 | -$1,250 | Feb 17, 2017 |
| Dec 20, 2016 | 35208070X | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 12-20-16 @10:45AM FAILURE TO PROVIDE A SYSTEM OF AUTOM... | $500 | -$500 | May 12, 2017 |