ECB violations
1838-1840 Vyse Avenue, Bronx • Block 02998 • Lot 0029
54 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 6, 2026 | 39176323R | ACTIVE | CLASS - 1 | OBSERVED IN THE BASEMENT GAS LINES RUNNING THROUGH THE DUMB WAITER SHAFT, CORROSION ON GAS LINES. OPEN ENDED WASTE LI... | $2,500 | $2,500 | Nov 13, 2026 |
| Feb 10, 2025 | 39137886Z | ACTIVE | CLASS - 2 | OBSERVED ON ROCKMILLS MP100 4000000 BTU DUAL FUEL BOILER WITH AN IC BURNER WITH A OIL LEAK AT THE METERING PUMP. CORR... | $3,125 | $3,125 | Jun 13, 2025 |
| Mar 22, 2024 | 39109611L | ACTIVE | CLASS - 2 | I OBSERVED THE IMPROPER TERMINATION OF CONDUCTORS AND RACEWAYS IN THE BASEMENT WATER METER ROOM AND ALONG THE PASSAGE... | $250 | $0 | Oct 25, 2024 |
| Mar 22, 2024 | 39109612N | RESOLVE | CLASS - 2 | I OBSERVED AT THE REAR COURTYARD AT EXPOSURE #3 A WALL LIGHT AND A SECTION OF CONDUIT RACEWAY HANGING UNSUPPORTED AS ... | $400 | $400 | Jul 5, 2024 |
| Mar 22, 2024 | 39109609M | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT WATER METER ROOM THE WATER MAIN GROUND IN A STATE OF DISREPAIR, WITH THE CONDUIT BROKEN, T... | $0 | $0 | May 31, 2024 |
| Mar 22, 2024 | 39109610J | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT WATER METER AREA, AND ALONG EXPOSURE #4 THE INSTALLATION OF WIRING TO INSTALL LIGHTING. DU... | $800 | $0 | May 31, 2024 |
| Feb 12, 2024 | 39105845X | ACTIVE | CLASS - 2 | OBSERVED IN THE BASEMENT UNSUPPORTED GAS PIPING. AS PER 102.3 OF THE PLUMBING CODEMAINTENANCE. INSTALLATIONS, BOTH EX... | $625 | $0 | Mar 11, 2025 |
| Jan 18, 2024 | 39103691N | RESOLVE | CLASS - 2 | EMERGENCY EXIT GATES THROUGHOUT BUILDING CHAINED, AND LOCKED SHUT, CELLAR LEVEL., PROVIDE LEGAL HARDWARE | $312 | $0 | Mar 18, 2025 |
| Jan 18, 2024 | 39103690L | RESOLVE | CLASS - 2 | EMERGENCY EXIT ROOF DOOR DOES NOT FUNCTION, (OPEN OR CLOSE) B-SIDE ROOF LEVEL EXPOSURE 4., REPAIR AND/OR REPLACE | $312 | $0 | Feb 4, 2025 |
| Aug 10, 2022 | 39067777Z | RESOLVE | CLASS - 2 | AT ROOF LEVEL TO FIRST FLOOR, STAIR CASE B, WALLS/ CEILING DAMAGES DUE PEELING STUCCO/MORTAR AND SIGNS OF WATER PENET... | $312 | $0 | Nov 4, 2022 |
| May 20, 2022 | 35636537L | RESOLVE | CLASS - 1 | UNSAFE UNSUITABLE ELECTRICAL WIRING AND EQUIPMENT IN USE I OBSERVED AT THE 1ST FLOOR EXIT LIGHTS WIRE MOLD RACEWAY NO... | $1,600 | $0 | Aug 19, 2022 |
| May 20, 2022 | 35636538N | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS I OBSERVED IN THE BASEMENT AT THEWATER METER THE GROUNDING ELECTRICAL CONDUCTOR ... | $4,800 | $0 | Aug 19, 2022 |
| Dec 20, 2019 | 35515409X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #39012327N ISSUED ON 11-04-2019 AND TO ... | $0 | $0 | Jun 26, 2020 |
| Dec 20, 2019 | 35514488Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35372242H ISSUED ON 11/19/18 & TO FILE A C OF C PURSUAN... | $0 | $0 | Jan 8, 2021 |
| Nov 9, 2019 | 35512794H | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35372242H ISSUED ON 11/19/18 AND TO FILE... | $0 | $0 | Oct 23, 2020 |
| Nov 4, 2019 | 39012326L | RESOLVE | CLASS - 1 | I OBSERVED IN THE REAR COURTYARD/ EXPOSURE 4 CONDUITS BROKEN, UNSUPPORTED, WITH EXPOSED CONDUCTORS SUPPLYING POWER TO... | $400 | $0 | Dec 20, 2019 |
| Nov 4, 2019 | 39012328P | RESOLVE | CLASS - 2 | I OBSERVED IN THE REAR COURTYARD/ EXPOSURE 4 THE PREVIOUS VIOLATING CONDITIONS AS SPECIFIED IN ECB #35372517H ISSUED ... | $1,250 | $0 | Feb 28, 2020 |
| Nov 4, 2019 | 39012327N | RESOLVE | CLASS - 1 | UPON MY RE-INSPECTION AT 1838 VYSE AVE AND CHECKING BIS I NOTED THAT A C OF C WAS FILED ON 3/18/19 IN REGARDS TO ECB ... | $0 | $0 | Feb 28, 2020 |
| Nov 4, 2019 | 39012333J | RESOLVE | CLASS - 2 | AC UNIT BLOCKING WINDOW TO EXIT INTO THE REAR YARD FROM ROOM. AT GROUND LEVEL, REPAIR AND/OR REPLACE | $0 | $0 | Dec 20, 2019 |
| Oct 4, 2019 | 35430293K | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35372242H ISSUED ON 11/19/18 & TO FILE A C OF C PURSUAN... | $0 | $0 | Dec 11, 2020 |
| Jul 24, 2019 | 35426813N | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35372242H ISSUED ON 11/14/18 & TO FILE A C OF C PURSUAN... | $0 | $0 | Oct 23, 2020 |
| Jun 7, 2019 | 35400125Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35372516X ISSUED ON 11/14/18 AND TO FI... | $0 | $0 | Aug 2, 2019 |
| Jun 7, 2019 | 35423591N | RESOLVE | CLASS - 1 | FILED A CERT OF CORRECTION OR OTHER RELATED MATERIALS CONTAINING MATERIAL FALSE STATEMENTS. ON MARCH 18, 2019 A CERTI... | $0 | $0 | Aug 12, 2019 |
| Jun 6, 2019 | 35423466Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTE: EXIT DOOR LEADING FROM THE BUILDING AND INTO THE SIDE YA... | $310 | $0 | Aug 2, 2019 |
| Jun 6, 2019 | 35423465M | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR DEPARTMENT OF BUIDLINGS RECORDS. NOTED: OBSERVE... | $0 | $0 | Sep 13, 2019 |
| May 18, 2019 | 35399248Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35372242H ISSUED ON 11/14/18 AND TO FILE... | $0 | $0 | Oct 23, 2020 |
| Apr 29, 2019 | 39002438R | RESOLVE | CLASS - 2 | SURFACE BLOW DOWN NOT INSTALLED-DRAIN FOR SAFETY VALVE NOT PROPERLY SUPPORTED-NO BODY DRAIN ON SAFETY VALVE-NO ANTI S... | $312 | $0 | Jun 21, 2019 |
| Feb 28, 2019 | 35395392P | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35372242H ISSUED ON 11/14/18 AND TO FI... | $0 | $0 | Oct 23, 2020 |
| Jan 11, 2019 | 35359780Z | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.IN NOVEMBER 14,2018.AN ELECTRICAL VIOLATION WAS ISS... | $0 | $0 | May 24, 2019 |
| Nov 19, 2018 | 35393000H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/ VIOLATION #353446772 ISSUED ON 07/12/18 AND TO F... | $625 | $0 | Feb 7, 2019 |
| Nov 14, 2018 | 35372243J | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED IN THE CELLAR A THREE QUARTER INCH GAS PIPE LINE WITH... | $0 | $0 | Nov 5, 2021 |
| Nov 14, 2018 | 35372515Y | RESOLVE | CLASS - 2 | BC110.26.00.FAILURE TO PROVIDE ILLUMINATION ABOVE SERVICE EQUIPMENT.OBSERVED IN BASEMENT AREA NO AND/OR IMPROPER ILLU... | $400 | $0 | Feb 1, 2019 |
| Nov 14, 2018 | 35372516X | RESOLVE | CLASS - 2 | LUMINARIES AND LUMPHOLES NOT INSTALLED IN AN APPROVED MANNER.OBSERVED THROUGHOUT BUILDING THE INSTALLATION OF CEILING... | $250 | $0 | Feb 1, 2019 |
| Nov 14, 2018 | 35372517H | RESOLVE | CLASS - 1 | EC342.30.FAILURE TO SUPPORT CONDUIT(INC)OBSERVED IN COURTYARD AT REAR OF BUILDING CONDUITS,UNSUPPORTED,BROKEN WITH EX... | $1,600 | $0 | Feb 1, 2019 |
| Nov 14, 2018 | 35372518J | RESOLVE | CLASS - 2 | BC400.14.FLEXIBLE CORDS SHALL BE PROTECTED FROM DAMAGE.OBSERVER TIGHT FIXTURE IN BASEMENT BOILER ROOM WITH FLEXIBLE C... | $400 | $0 | Feb 1, 2019 |
| Nov 14, 2018 | 35372242H | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT. OBSERVED IN THE CELLAR A THREE QUARTER INCH GAS PIPE LINE WITH A UNION FILTERING THAT WAS INST... | $0 | $0 | Oct 23, 2020 |
| Jul 12, 2018 | 35344677Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES.NOTED:@EXP#1,NORTH WEST SECTION,(PARAPET) WALL LEANING INWARD TOWARDS... | $3,125 | $0 | Oct 26, 2018 |
| Jun 19, 2018 | 35334598L | RESOLVE | CLASS - 2 | FAILRUE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: AT BLDG FRONT CENTER COURT YARD,BOTH NORTH & SOUTH PARAPET WA... | $3,125 | $0 | Aug 17, 2018 |
| May 8, 2018 | 35326121Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.NOTED:AT EXPO#1 NORTH WEST SECTION PARAPET WALL LEANING INWARD TO... | $1,250 | $0 | Sep 14, 2018 |
| Apr 17, 2018 | 35325161Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:AT ROOF LEVEL PARAPET WALL IS LEANING TOWARDS THE ROOF IT ... | $1,250 | $0 | Jul 20, 2018 |
| Jun 7, 2017 | 35267638J | RESOLVE | CLASS - 1 | SEC. 401.1 MISC VIOLATIONS: GAS PIPING NOT LABELED. OBSERVED IN HALLWAY OF CELLAR GAS PIPING NOT LABELED TO INDICATE ... | $400 | $0 | Sep 8, 2017 |
| Jun 7, 2017 | 35268061Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. NOTED: AT TIME OF INSPECTION... | $0 | $0 | Aug 4, 2017 |
| Jun 7, 2017 | 35268062K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: AT EXP#1 ENTRANCE COURTYARD AT PARAPET HAS SPALLING CONCRETE ... | $0 | $0 | Aug 4, 2017 |
| Jun 7, 2017 | 35268010Z | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. OBSERVED AROUND EXTERIOR PERIMETER & IN HALLWAYS. THE REMOVAL OF OLD WALL PACK FIXTURES... | $400 | $0 | Sep 8, 2017 |
| Jun 7, 2017 | 35268009L | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,DEVICES,MATERIALS,APPLIANCES OR WIRING IN USE. OBSERVED T... | $1,600 | $0 | Sep 8, 2017 |
| Nov 29, 2016 | 35221109K | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE POWER FOR EMERGENCY EXIT LIGHTING. NOTED: MOST OF EMERGENCY LIGHT IN EACH FLOOR ARE NOT OPERATIONA... | $250 | $0 | Feb 3, 2017 |
| Nov 29, 2016 | 35221920J | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER RE: INSTALLATION/MAINENANCE OF PLUMBING MATERIALS EQUIPMENT PER PC 102... | $500 | $0 | Feb 3, 2017 |
| Nov 29, 2016 | 35221912J | RESOLVE | CLASS - 1 | SEC. 408.2 DRIPS-FUTURE CONNECTS EXITS DOWN STREAM OF APPLIANCE. OBSERVED ON 11/29/16 AT ABOVE ADDRESS FUTURE GAS CON... | $1,600 | $0 | Jan 20, 2017 |
| Feb 24, 2016 | 35128393K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. FACADE AT EXP#2 BETWEEN 2ND & 4TH FLOOR STUCCO SIDING APPROX 12FT ... | $500 | $0 | Apr 15, 2016 |
| Feb 24, 2016 | 35128392Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT ROOF LEVEL & BULKHEAD WATER INTENSION VISIBLE LEAKING FROM ROOF... | $500 | $0 | Apr 15, 2016 |